Roger MCX2D User manual

Roger Access Control System
MCX2D Operating Manual
Product version: 1.0
Firmware version: 1.1.14 or newer
Document version: Rev. H

MCX2D Operating Manual 12.11.2020
2/13
1. DESIGN AND APPLICATION
MCX2D is I/O expander dedicated to RACS 5 system. The device after connection to MC16 access
controller and MCT series terminals enables to control 2 doors. The expander offers I/Os and distributes
power supply and RS485 communication bus. The expander operates with backup battery which depending
on particular requirements can be charged with 0.3A, 0.6A or 0.9A current. The expander is equipped with
removable terminal blocks which facilitate electrical connections during installation and maintenance.
MCX2D expander is offered separately or as a component of MC16-PAC-2-KIT.
Characteristics
RACS 5 system I/O expander
Power supply distribution for door devices
RS485 bus distribution for MCT terminals
4 parametric (EOL) inputs
4 transistor outputs
6 power supply outputs
Backup battery charging
RS485 interface
Removable screw terminals
Power supply
The expander requires 13.8VDC power supply and it is recommended to apply PS2D power supply unit for
that purpose. Due to relatively high current between expander and PSU, all connections should be made
using possibly short cables with adequate cross sections. PSxD series PSUs (Roger) are offered with two
30cm/1mm² cables dedicated to supply the expander. Multiple MCX2D expanders can be supplied from the
same PSU and in such case each connection must be made with individual pair of cables. When expander’s
supply voltage is too low then the battery cannot be fully charged and when the voltage is too high then the
battery can be damaged. MCX2D which is supplied from PSU equipped with own backup (e.g. UPS) can be
supplied with 12-15VDC but then it cannot be equipped with own backup battery.
Fig. 1 Two MCX2D expanders supplied from the same PSU

MCX2D Operating Manual 12.11.2020
3/13
Backup battery
MCX2D enables battery charging with 0.3A, 0.6A or 0.9A current up to the level of voltage supplied to the
expander (nominal 13.8VDC). The current is selected with jumpers (fig. 2). When battery voltage drops to
approximately 10V then it is disconnected from expander. The battery is reconnected when the 13.8V
supply to expander is restored. In order to ensure battery charging up to 80% level within 24h (according to
EN 60839 standard) following current settings must be applied:
300mA for 7Ah battery
600mA for 17Ah battery
900mA for 24Ah battery
RS485 bus
MCX2D is an addressable device connected to RS485 communication bus of the MC16 controller. At the
same time the expander distributes the bus to MCT terminals at each door. The expander can be operated
with default ID=100 address or it can be assigned with the address in range of 101-115. All devices on
RS485 bus of MC16 controller including MCX expanders and MCT terminals must have unique addresses
in range of 100-115. MCX2D is addressed within low level configuration by means of RogerVDM software or
manually within memory reset procedure.
In most cases communication works with any cable type (standard telephone cable, shielded or unshielded
twisted pair etc.) but the recommended cable is unshielded twisted pair (U/UTP cat.5). Shielded cables
should be limited to installations subject to strong electromagnetic interferences. The RS485 communication
standard used in the RACS 5 system guarantees proper communication in a distance of up to 1200 meters
as well as high resistance to interferences.
Note: Do not use more than single pair in UTP cable for RS485 communication bus.
LED indicators
Expanders are equipped with LED indicators which are used to signal integral functions. According to further
mentioned procedures, the service mode is started by placing jumper on MEM contacts and restarting the
expander.
Table 1. LED indicators
Indicator
Colour
Integral functions
ACL
Red
In normal mode the LED indicates backup power supply from battery
instead of PSU.
RUN
Red
Single pulse every 4 sec. : normal mode
Quick pulsing: service mode
Slow pulsing (0.5s/0.5s): No communication with controller
Very slow pulsing (1s/1s): Configuration memory error
In case of Memory reset this LED is used for manual addressing.
TXD
Red
LED indicates data transmission to controller
RXD
Green
LED indicates data receiving from controller
VDR, TML,
VOUT, AUX
Green
LED indicates voltage at particular output.
LCK
Red
LED is on when corresponding LCK output is switched on.
Inputs
Expander offers DC and DR parametric inputs of NO, NC, 3EOL/DW/NO and 3EOL/DW/NC type. Input
types and electric parameters such as response time and parametric resistors are defined within low level

MCX2D Operating Manual 12.11.2020
4/13
configuration (RogerVDM). Input functions are assigned within high level configuration (VISO). Multiple
functions can be assigned to the same input at the same time.
In standard scenario of door control, DC inputs are dedicated to connection of door contacts while DR inputs
are dedicated to connection of exit buttons and they do not require low level configuration as they can be
operated with default settings:
DC inputs: NC type / 50ms response time
DR inputs: NO type / 50ms response time
Table 2. Input types
NO input
NC input
NO input can be in normal or in triggered state. In
normal state CAcontacts are opened. Input
triggering is caused by CAcontacts closing.
NC input can be in normal or in triggered state. In
normal state CAcontacts are closed. Input triggering
is caused by CAcontacts opening.
3EOL/DW/NO input
3EOL/DW/NC input
3EOL/DW/NO input is operated in such way that CA
contacts closing is interpreted as triggering of the
first input while CBclosing is interpreted as
triggering of the second input. In VISO software DW
input type is represented by two independent inputs.
Each can be used for different purpose and
assigned with different function.
3EOL/DW/NC input is operated in such way that CA
contacts opening is interpreted as triggering of the
first input while CBopening is interpreted as
triggering of the second input. In VISO software DW
input type is represented by two independent inputs.
Each can be used for different purpose and
assigned with different function.

MCX2D Operating Manual 12.11.2020
5/13
Parametric resistors
The same values of parametric resistors are used for all inputs i.e. 1kΩ; 1,2kΩ; 1,5kΩ; 1,8kΩ; 2,2kΩ; 2,7kΩ;
3,3kΩ; 3,9kΩ; 4,7kΩ; 5,6kΩ; 6,8kΩ; 8,2kΩ; 10kΩ; 12kΩ. In case of 3EOL/DW (Double Wiring) input type,
Alarm A resistor defines a value of resistor used to detect triggering of the first input while Alarm B resistor
defines a value of resistor used to detect triggering of the second input. Alarm A resistor value must differ
from value of Alarm B resistor at least by three positions in the list above. Total resistance of wire used to
connect contacts to input should not exceed 100 Ω. Default values of parametric resistors:
Alarm A = 2,2 kΩ
Alarm B = 5,6 kΩ
Response time
Response time parameter defines minimal impulse time on the input which triggers the input. Each input can
be configured individually in range of 50 to 5000 ms within low level configuration (RogerVDM).
Transistor outputs
Expander offers LCK and BELL transistor outputs. Electric parameters such as polarity are configured within
low level configuration (RogerVDM). Function are assigned to outputs within high level configuration (VISO).
Multiple functions with different priorities can be assigned to the same output at the same time.
In standard scenario of door control, LCK outputs are dedicated to control door locks while BELL outputs
are dedicated to control alarm signalling devices and/or door bells. In standard scenario of operation both
LCK and BELL outputs do not require low level configuration.
Power supply outputs
Expander offers 6 outputs in order to provide power supply to access controller, terminals, door lock and
other external devices.
VDR outputs
VDR power supply output is dedicated to supply door lock, alarm signalling device and other door related
devices. The terminal VDR+ is protected with 1.0A electronic fuse. The terminal VDR- is internally shorted to
ground (GND). Green LED indicator is located at the VDR+ terminal to signal voltage at the output.
TML outputs
TML power supply output is dedicated to supply readers at door. The terminal TML+ is protected with 0.2A
electronic fuse . The terminal TML- is internally shorted to ground. Green LED indicator is located at the
TML+ terminal to signal voltage at the output.
VOUT output
VOUT power supply output is dedicated to supply additional electronic modules and it can be also used to
supply connected access controller. The terminal VOUT+ is protected with 0.2A electronic fuse . The
terminal VOUT- is internally shorted to ground. Green LED indicator is located at the VOUT+ terminal to
signal voltage at the output.
Note: If MC16 access controller is supplied from the expander then it cannot be at the same time supplied
by own PSU and it cannot operate with own backup battery.
AUX output
AUX power supply output is dedicated to supply optional electronic modules. The terminal AUX+ is
protected with 0.2A electronic fuse. The terminal AUX- is internally shorted to ground. Green LED indicator
is located at the AUX+ terminal to signal voltage at the output.
2. INSTALLATION
Each expander is equipped with a holder for installation on DIN35 rail. Therefore expanders can be installed
in ME type enclosures equipped with such rail. Alternatively, expanders can also be mounted using screws
and holes on expander board. It is recommended to install the expander in the same enclosure as PSU. The
cross section of power supply wires must be adequate as to avoid voltage drop greater than 200mV for
rated load. It is recommended to use cables with minimal 1mm2cross section and maximal 30 cm length.
Such cables are offered with PSxD series power supply units.

MCX2D Operating Manual 12.11.2020
6/13
Fig. 2 MCX2D expander
Table 3. MCX2D screw terminals
Name
Description
BAT+, BAT-
Backup battery
VIN+, VIN-
13.8VDC input power supply
AUX+, AUX-
13.8VDC/0.2A output power supply (for general purpose)
VOUT+, VOUT-
13.8VDC/0.2A output power supply (to controller)
A, B
RS485 bus (to controller)
Ax*, Bx
RS485 bus (to readers)
TMLx+, TMLx-
13.8VDC/0.2A output power supply (to readers)
VDRx+, VDRx-
13.8VDC/1.0A output power supply (to door lock)
LCKx
15VDC/1A transistor output line (door lock)
BELLx
15VDC/1A transistor output line (alarm signalling device)
DCx
Input line (door contact)
DRx
Input line (exit button)
* x symbol corresponds to the number of particular door controlled via expander

MCX2D Operating Manual 12.11.2020
7/13
Fig. 3 MCX2D installation
Installation guidelines
All electrical connections should be done with disconnected power supply.
If the expander and controller are not supplied from the same PSU then GND terminals of both
devices must be connected with any wire.
3. OPERATION SCENARIOS
In typical scenario of operation, MCX2D expanders are used in MC16-PAC-2-KIT two-door access control
kits (fig. 4 and 6). In the alternative scenario of operation, multiple MCX2D expanders are connected to
multidoor MC16 access controller (fig. 5). In such scenario the maximal number of expanders operated by
MC16 controller depends on its type and it is limited by available range of addresses ID=100-115 on RS485
bus of MC16 controller where all MCX and MCT devices must have unique addresses. For example, in case
of read-in/out doors it is possible to control max. 6 doors in such setup as MC16-PAC-6 + 3 x MCX2D + 12 x
MCT while in case of read-in doors it is possible to control max. 10 doors in such setup as MC16-PAC-10 +
5 x MCX2D + 10 x MCT. In both cases, 15 addresses on RS485 bus are occupied. It is also possible to mix
read-in and read-in/out doors within single MC16 controller if the limitation related to the number of RS485
addresses is preserved.

MCX2D Operating Manual 12.11.2020
8/13
Fig. 4 Scenario of operation with MC16-PAC-2-KITs
Fig. 5 Scenario of operation with multiple MCX2D expanders

MCX2D Operating Manual 12.11.2020
9/13
Fig. 6 Connection diagram for MCX2D expander in MC16-PAC-2-KIT
4. CONFIGURATION
Low level configuration (RogerVDM)
The purpose of low level configuration is to prepare device for operation in RACS 5 system.
Programming procedure with RogerVDM software:
1. Connect the device to RUD-1 interface (fig. 7) and connect the RUD-1 to computer’s USB port.
2. Place jumper on MEM contacts (fig. 2).
3. Restart the device by pressing RST button and RUN LED indicator will pulsate.
4. Start RogerVDM program, select MCX v1.x device, v1.x firmware version, RS485 communication
channel and serial port with RUD-1 interface.
5. Click Connect, the program will establish connection and will automatically display Configuration tab.
6. Enter unoccupied RS485 address in range of 100-115 (if necessary) and other settings according to
requirements of specific installation.
7. Click Send to Device to update the configuration.
8. Optionally make a backup by clicking Send to File… and saving settings to file on disk.
9. Remove jumper from MEM contacts and disconnect device from RUD-1 interface.

MCX2D Operating Manual 12.11.2020
10/13
Fig. 7 Connection to RUD-1 interface (low level configuration)
Table 4. List of low level parameters
Communication settings
RS485 address
Parameter defines device address on RS485 bus. Range: 100-115.
Default value: 100.
RS485 communication timeout [s]
Parameter defines delay after which device will signal lost
communication with controller. When set to 0 then signaling is
disabled. Range: 0-64s. Default value: 20s.
RS485 encryption
Parameter enables encryption at RS485 bus. Range: [0]: No, [1]: Yes.
Default value: [0]: No.
RS485 encryption key
Parameter defines key for encryption of communication at RS485 bus.
Range: 4-16 ASCII characters.
Input types
DC1, DR1, DC2, DR2
Parameter defines input type. Range: [1]: NO, [2]: NC, [3]: EOL/NO,
[4]: EOL/NC, [5]: 2EOL/NO, [6]: 2EOL/NC, [7]: 3EOL/NO, [8]:
3EOL/NC, [9]: 3EOL/DW/NO, [10]: 3EOL/DW/NC. Default value for DC
is [2]: NC. Default value for DR is [1]: NO
Parametric (EOL) input resistances
Tamper, Alarm A, Alarm B [Ohm]
Parameter defines resistor for parametric (EOL) inputs.
Input response times
DC1, DR1, DC2, DR2 [ms]
Parameter defines minimal duration of pulse which is required to
trigger the input. Range: 50-5000. Default value: 50.
Output polarity
LCK1, BELL1, LCK2, BELL2
Parameter defines polarity of output. Normal polarity means that the
output by default is switched off while Reversed polarity means that
the output by default is switched on. Range: [0]: Normal polarity, [1]:
Reversed polarity. Default value: [0]: Normal polarity.
Comments

MCX2D Operating Manual 12.11.2020
11/13
DEV, PWR1
Parameter defines any text or comment which corresponds to the
device/object. It is later displayed in VISO program.
Input comments
DC1, DR1, DC2, DR2
Parameter defines any text or comment which corresponds to the
object. It is later displayed in VISO program.
Output comments
LCK1, BELL1, LCK2, BELL2
Parameter defines any text or comment which corresponds to the
object. It is later displayed in VISO program.
Memory reset procedure and manual addressing
Memory reset procedure resets all settings to factory default ones and it enables to manually configure the
address on RS485 bus.
1. Remove all connections from LCK1 and DC1 lines.
2. Place jumper on MEM contacts (fig. 2).
3. Connect LCK1 and DC1 lines.
4. Restart the device by pressing RST button and ACL LED indicator will pulsate.
5. Disconnect LCK1 and DC1 lines and RUN LED indicator will pulsate. The number of consecutive
flashes will correspond to expander’s address on RS485 bus.
6. Press RST button in a certain moment to select certain address (table 5) or press RST button after 16
flashes when ACL and RUN LED indicators are switched on to select default ID=100 address.
7. Remove jumper from MEM contacts and restart the device.
Table 5. RS485 address encoding
Number of RUN LED
flashes
RS485 address
Number of RUN LED
flashes
RS485 address
1
101
9
109
2
102
10
110
3
103
11
111
4
104
12
112
5
105
13
113
6
106
14
114
7
107
15
115
8
108
16
100
Example:
In order to select ID=105 address within memory reset procedure, press RST button after 5 flashes of RUN
LED indicator.
High level configuration (VISO)
The purpose of high level configuration is to define logical functioning of the expander which communicates
with the MC16 access controller and it depends on applied scenario of operation. The example of access
control system configuration is given in AN006 application note which is available at www.roger.pl.
5. FIRMWARE UPDATE
The update requires connection of expander to computer with RUD-1 interface (fig. 8) and starting
RogerVDM software. The latest firmware file is available at www.roger.pl.
Firmware update procedure:
1. Connect the device to RUD-1 interface (fig. 8) and connect the RUD-1 to computer’s USB port.

MCX2D Operating Manual 12.11.2020
12/13
2. Place jumper on FDM contacts (fig. 2).
3. Restart the device by pressing RST button and TXD LED indicator will switch on.
4. Start RogerVDM program and in the top menu select Tools and then Update firmware.
5. In the opened window select device type, serial port with RUD-1 interface and path to firmware file
(*.hex).
6. Click Update to start firmware upload with progress bar in the bottom.
7. When the update is finished, remove FDM jumper and restart the device.
Fig. 8 Connection to RUD-1 interface (firmware update).
6. SPECIFICATION
Table 6. Specification
Supply voltage
13.8VDC; +/- 100mV (backup battery connected)
11-15 VDC (no backup battery)
Current consumption
(average)
MCX2D expander: 50mA
MCX2D expander with maximal load at power outputs and maximal battery
charging current: 3.5A
Battery charging current
Configurable: 0.3A/0.6A/0.9A
Inputs
Four (DCx, DRx) parametric inputs
Transistor outputs
Four (LCKx, BELLx) outputs, each with 15V/1A DC max load
Power supply outputs
Two 13.8VDC/0.2A outputs (VOUT, AUX)
Two 13.8VDC/0.2A outputs (TML)
Two13.8VDC/1.0A outputs (VDR)
Distances
Up to 1200 m between MC16 controller and MCX expander (RS485).
Up to 1200 m between MCX expander and MCT terminals (RS485)
The total distance between controller and any terminal cannot exceed 1200m.
IP Code
IP20
Environmental class
(according to EN
50133-1)
Class I, indoor general conditions, temperature: +5°C to +40°C, relative
humidity: 10 to 95% (no condensation)

MCX2D Operating Manual 12.11.2020
13/13
Dimensions W x S x G
80 x 80 x 20 mm
Weight
65g
Certificates
CE
7. ORDERING INFORMATION
Table 7. Ordering information
MCX2D
2-door expander; battery charge and maintenance; 13.8 VDC supply
MC16-PAC-2-KIT
2-door access control kit; ME-15 metal enclosure; MC16-PAC-2 access controller
module; MCX2D I/O expander; PS2D power supply
RUD-1
Portable USB-RS485 communication interface dedicated to ROGER access
control devices
8. PRODUCT HISTORY
Table 8. Product history
Version
Date
Description
MCX2D v1.0
10/2017
The first commercial version of product
This symbol placed on a product or packaging indicates that the product
should not be disposed of with other wastes as this may have a negative
impact on the environment and health. The user is obliged to deliver
equipment to the designated collection points of electric and electronic
waste. For detailed information on recycling, contact your local authorities,
waste disposal company or point of purchase. Separate collection and
recycling of this type of waste contributes to the protection of the natural
resources and is safe to health and the environment. Weight of the
equipment is specified in the document.
Contact:
Roger sp. z o.o. sp.k.
82-400 Sztum
Gościszewo 59
Tel.: +48 55 272 0132
Fax: +48 55 272 0133
Tech. support: +48 55 267 0126
E-mail: support@roger.pl
Web: www.roger.pl
Other manuals for MCX2D
1
Table of contents
Other Roger I/O System manuals