EX600-TF223-093EN
Page 1 of 3
Instruction Manual
Fieldbus device - SI unit for EtherNet/IPTM
IO-Link compatible
56-EX600-SEN7/8-X10
II 3G Ex ec IIC T4 Gc -10oC ≤ Ta ≤ 50oC
II 3D Ex tc IIIC T66oC Dc IP67
The intended use of this product is to control pneumatic valves and I/O
while connected to the EtherNet/IPTM protocol.
1 Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage. These instructions indicate the level of
potential hazard with the labels of “Caution,” “Warning” or “Danger.”
They are all important notes for safety and must be followed in addition
to International Standards (ISO/IEC) *1), and other safety regulations.
*1) ISO 4414: Pneumatic fluid power — General rules and safety
requirements for systems and their components.
ISO 4413: Hydraulic fluid power — General rules and safety
requirements for systems and their components
IEC 60204-1: Safety of machinery - Electrical equipment of machines.
Part 1: General requirements
ISO 10218-1: Robots and robotic devices - Safety requirements for
industrial robots - Part 1: Robots
•Refer to product catalogue, Operation Manual and Handling
Precautions for SMC Products for additional information.
•Keep this manual in a safe place for future reference.
Danger indicates a hazard with a high level of risk which, if
not avoided, will result in death or serious injury.
Warning indicates a hazard with a medium level of risk
which, if not avoided, could result in death or serious injury.
Caution indicates a hazard with a low level of risk which, if
not avoided, could result in minor or moderate injury.
Warning
•Always ensure compliance with relevant safety laws and
standards.
•All work must be carried out in a safe manner by a qualified person in
compliance with applicable national regulations.
II 3G Ex ec IIC T4 Gc -10oC ≤ Ta ≤ 50oC
II 3D Ex tc IIIC T66oC Dc IP67
Category 3
Gas (G) and Dust (D) environment
Ex - European standards apply
ec – Increased safety
IIC - for all types of gas
T4 - Temperature classification
tc - protected by enclosure
lllC - for all types of dust
T66oC - Max. surface temperature
Gc/Dc - Equipment Protection Level
Ta - ambient temperature
IP67 - Protection structure
Based on the conformity assessment carried out by SMC Corporation.
If the Certificate number includes an X, special conditions for safe use
apply as follows :-
1 Safety Instructions (continued)
•Protect the product from sources of heat which can generate surface
temperatures greater than the temperature classification.
•Protect the product and cable connections against all impact or
mechanical damage using a suitable Ex compliant enclosure.
•Protect the product from direct sunlight or UV light using a suitable
protective cover.
•Do not disconnect the M12 connectors before first switching OFF the
power supply.
•Use only Ex approved connectors and use shielded cable to provide
grounding.
•Use only a damp cloth to clean the product to avoid an electrostatic
charge.
2 Specifications
2.1 General specifications
35 to 85%RH (no condensation)
Ambient storage temperature
500 VAC applied for 1 minute
IP67 (manifold assembled)
2.2 Electrical specifications
3 Name and function of parts
Displays the SI unit status.
Display cover for switch setting.
To open the display cover.
Connector for Fieldbus Outputs.
Groove for identification marker.
Hole for valve plate mounting.
Groove for valve plate mounting.
Bracket for joining to adjacent units.
Connector for signal/power to next unit.
Connector for Fieldbus Inputs.
For all unused M12 connectors
4 Assembly
4.1 Assembling the unit
Warning
Do not install the product unless the safety instructions have been read
and understood.
(1) Connect an I/O unit to the end plate. Digital and analogue units can
be connected in any order. Joint bracket screw tightening torque: 1.5
to 1.6 N•m.
(2) Add more I/O units. Up to 9
I/O units can be connected
to one manifold.
Connect the SI unit. After
connecting the required I/O
units, connect the SI unit.
The connection method is
as above.
Mount the valve plate
(EX600-ZMV#) to the valve
manifold using the valve
screws (M3 x 8) supplied.
(Tightening torque: 0.6 to
0.7 N•m).
Connect the SI unit
assembly
manifold.
Insert the valve plate into
groove.
4 Assembly (continued)
Then fix using the valve plate mounting screws (M4 x 6) supplied
(Tightening torque: 0.7 to 0.8 N•m).
5 Installation
•Do not expose to direct sunlight. Use a suitable protective cover.
•Do not install in a location subject to vibration or impact in excess of
the product’s specifications.
•Do not mount in a location exposed to radiant heat that would result in
temperatures in excess of the product’s specifications.
•Direct mounting
(1) When assembling six or more units, the middle part of the assembly
must be fitted with an intermediate reinforcing brace (EX600-ZMB1)
before mounting using 2 - M4x5 screws (Tightening torque: 0.7 to 0.8
N•m).
(2) Mount and tighten the end plate at one end of the unit and mount the
intermediate reinforcing brace if required using M4 screws
(Tightening torque: 0.7 to 0.8 N•m).
Fix the end plate at the valve side while referring to the operation
manual for the applicable valve series.
•DIN rail mounting
(1) When assembling six or more units, the middle part of the complete
assembly must be fitted with an intermediate reinforcing brace for DIN
rail mounting (EX600-ZMB2), using 2 - M4 x 6 screws.
(Tightening torque: 0.7 to 0.8 N•m).
(2) Mount the end plate bracket (EX600-ZMA2) to the end plate using 2-
M4 x 14 screws (Tightening torque: 0.7 to 0.8 N•m). For the SY
series, use end plate bracket (EX600-ZMA3).
Power
supply
voltage /
current
Control and Input
power supply
Solenoid valve and
Output power supply
Internal current
consumption
120 mA maximum
Solenoid
valve
specification
Output
type
EX600-SEN7
PNP / source (negative
common)
NPN / sink (positive common)
Applicable valve series
Solenoid valve with surge
voltage suppression
Output condition during
communication error
HOLD / CLEAR / Force ON
2.3 Communication specifications
Protocol
EtherNet/IPTM
(conformance version: Composite18)
Standard EtherNet cable
(CAT5 or more, 100BASE-TX)
Full duplex / Half duplex
Occupying area
(number of input/output)
1212 bytes / 1210 bytes max.
Setting by switch: 192.168.0 or 1.1 to 254
By DHCP server: arbitrary address
Device information
Vendor ID: 7 (SMC Corporation)
Device type: 12 (communication adapter)
Star, Linear Bus and Ring (including DLR)
QuickConnectTM, Web server