
 
2 
2.1 HIGH LEVEL OPERATION 
(NORMALLY OPEN)
 As the liquid level rises and begins to 
cover the displacer assembly, the 
buoyancy in the liquid reduces the 
counterclockwise rotational force on the 
cone. At some point, the spring will 
exert a greater clockwise rotational force 
and cause the cone to push the valve 
stem downward, and act on the push rod 
and 3-way valve. This allows the 
pressure present at the outlet to vent 
through the weep holes in the valve 
body while blocking the inlet pressure. 
 
2.2 LOW LEVEL OPERATION 
(NORMALLY CLOSED) 
 As the liquid level falls and begins to 
uncover the displacer assembly, its 
buoyancy in the liquid increases the 
counterclockwise rotational force on the 
cone. At some point, the displacer will 
exert a greater clockwise rotational force 
and cause the cone to push the valve 
stem upward, and act on the push rod 
and 3-way valve. This allows the 
pressure present at the outlet to vent 
through the weep holes in the valve 
body while blocking the inlet pressure. 
 
NOTE: THE VALVE CAN BE USED 
WITH OPPOSITE FUNCTION IF 
ROTATED 180 DEG. 
 
3.0 INSTALLATION 
 
3.1 EXTERNAL CAGE TO VESSEL 
 It is suggested that the level switch be 
installed in an external cage for 
maintenance and testing purposes. One 
recommended piping system for 
mounting an external cage to a vessel is 
shown in Figure 1. The valves above 
and below the cage are required for 
testing and maintenance purposes. 
 
If a cage with butt weld connections is 
used, the level switch should be 
removed from the cage before welding. 
This will prevent weld sparks from 
damaging the displacer assembly. 
Remove the switch from the cage as per 
instructions in Paragraphs 5.2.1 
through 5.2.2 of the FULL 
DISASSEMBLY section of this manual. 
After welding, install the level switch as 
per instructions in Section 3.2, 
INSTALLING LEVEL SWITCH IN 
CAGE. 
 If the cage has threaded or flanged 
process connections, the level switch 
does not have to be removed before 
mounting the switch to the vessel. Cages 
with 1” NPT process connections may 
be installed on the vessel with 1”, ¾” 
or ½” O.D. piping. 
 
CAUTION: Be sure the pressure 
rating of all valves, pipe and pipe 
fittings meets or exceeds the working 
pressure of the vessel on which they 
are to be installed. Adequate support 
for long pipe runs should be provided 
to prevent excessive vibrations of the 
level switch. 
 
It is recommended that external cages be 
installed with the process connections as 
close to vertical and the cage length as 
close to horizontal as possible. This will 
insure the proper liquid flow into and 
out of the cage. 
 
3.2 LEVEL SWITCH INSTALLATION 
 Before installing a level switch into an 
external cage or mating flange, verify 
that level switch is set up or the 
operation required (i.e., high or low 
liquid level detection). See Section 4.0, 
CHANGING MODE OF OPERATION 
and Figure 5. NOTE: When direct 
mounting a level switch to a tank or 
vessel, verify that the end displacer 
assembly will be at least ½” (13mm)