SAND PS4812 Series User manual

00000425
PS4812 Series
Manual
intelligent digitalpressureindicator

Notes
DangerousDangerous Attention Riskof Electronic Shock
When we connectthe power,please do nottouch ACwire to avoidshock
WarningWarning This instrument isan open device,so when to make applications for
the risk, Suchas: they willcause harm and damage to other equipment,
make sure toinstall security devicesto automatic devices.
You should carefullycheck the wiringis correct beforeInstrument power supply
terminal, to avoidserious damage toinstrumentation.
Make sure towiring, signal deviceshave access tocorrect and appropriateterminal;
Pleases do notuse any leftterminal .
This instrument isan open case,to be installedin a dust,humidity, shockand strong
shocks from distributionbox; Do notalter, disassemblethe instrument.
The instrument shouldbe installed asfar as possibleaway from thehigh voltage and
electromagnetic interference region,to ensure stableand reliable instrument.
Do not touchthe meter powerterminals or repairthe body toavoid electric shock.
Please avoid thisharsh environment ofthe instrument:
The dust andcorrosive gases overthe place;
High humidity andhigh radiation areas;
Strong vibration andstrong impact ofworkplace.
Functional andtechnical specifications
PS4812 series intelligentdigital pressure indicatoris the production company to develop
new industrial control instruments, which can completely replace the imported products of
similar high-grade pressure indicator. Highly cost-effective, and can adapt to volatile
network occasion. Thepressure indicator appearance,complete functions, interferencewith
excellent performance toensure reliability ofthe system work.
Figures show bits:double-color 4;
Within theresolution: 32000;
External Resolution:
0001,0002,0005,0010 Panel Switch(power failure protectionsetting of 40 years);
Nonlinear:
0.05% 1 word, 0.1% 1 word, 0.2% 1 word, 0.5% 1 word;
Pressure Range: programmableoptions;
Engineering units: MPa,psi, bar,kgf / cm2programmable options;
Decimal point location:Programmable;
Alarm settings:Twoprogrammable alarm settings;
Relay contact output:250VAC, 5A;
Linear output:
0 ~ 10mA,0 ~ 20mA,4 ~ 20mA,0 ~ 5V, 1 ~5V, 0 ~10V programmable options;
Instrument Communication: RS485interface (optional);
Mailing address: 0001~ 0255;
Communication baud rate:2400bps, 4800bps, 9600bps,19200bps, 38400bps;
Power supply: 85~ 265VAC;
Ambient temperature:-10 ~ +85 ;
Humidity: 80% RH;
Continuous trouble-free workingtime: 50000 hours.

.1.
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
1.2 Indicator
1.3 Button
* Function botton: used to access the programming menu and set the points and long by two
kinds of manipulation by way of;
* Shift button;
* Reduction button;
* Increase button;
* + Calibration key: seepage 10 ofthe calibration instructions;
* + Restore button: the pressure value after the error is cleared, pressing two keys
simultaneously for more than 5 seconds to restore pressure to zero;
* + Clear button: while pressing the 2 keys 5 seconds to restore the pressure to zero;
Tel:028-87078792 Fax: 028-87078762 QQ:386563863 ChengDu SAND Electronic Co., Ltd.
PS4812 User Instructions
Welcome touse PS4812 SeriesIntelligent pressure indicatorfrom Chengdu SAND
ElectronicCo.,Ltd.This manualdetails thefunctions of the form and use, please
read carefully before use!
1. Instrumentpanel
1.1 Theinstrument paneldiagram:
First Alarm
Indicator
Calibration
Indicator
Second Alarm
Indicator
PV display window:
Set Status:Parameter code
display settings
Measuring status:Display
real-time pressure values
Pressure unit indicator
SV display window:
Set Status Display
settings parameters
Measuring Status
Shows the value of the
first alarm
Increase button
Reduction button
Function button
Shift button
PS4812 Series Intelligent pressure indicator on the left panel contains two alarm lights, a calibrated
light and four pressure unit lights on the right, its functions as follows:
1) The first alarm indicator AL1: long light alarm light, no alarm light goes out;
2) The second alarm indicator AL2: long bright alarm light, no warning light goes out;
3) Calibration status indicator CAL: calibration of pressure indicator, the light starts flashing, the
calibration end then the light off;
4) The unit of pressure indicator: programmable selection of the corresponding pressure, the
corresponding length indicator light
PS4812 Series IntelligentPressure indicator consists of four functionkeys, respectively,
SEL functionkeys, shift key, to increaseand decrease keysfunction keys asfollows:

.2.
2. Instrumentationwiring
S+S+
S-S-
Cal2Cal2
Cal1Cal1
E-E-
E+E+
Sensor signal S+
Sensor Bridge PowerE+
80%FSO Calibration 2
(This form in accordance with ourcompany's PT series pressure transducerconnection establishment)
NCNC
CC
NONO
Relay normally
closed terminal
Relaypublic-side
First
Alarm
Terminal
Blocks
NCNC
CC
NONO
Serial
COM
11
1010
11111212
1414
15151616
1717
181819192020
21212222
2323 1313
2424
9988776655443322
++++
VVmAmA RS485RS485
++
Alarm 2Alarm 2
NCNC CCNONO
Alarm 1Alarm 1
NCNC CCNONO PowerPower
85~265V85~265V
SignalSignal ExciteExcite CalibrateCalibrate ----
Cal2Cal2Cal1Cal1
E-E-E+E+
S-S-S+S+
3. Overalldimension
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
96mm
91.5mm
48mm
45.5mm
78.5mm
88.5mm
39mm
108mm
Second Alarm First Alarm Power
Sensor
Signal Sensor
Excitation Sensor
Calibration
Ground
Ground
V
Output mA
Output
Second
Alarm
Terminal
Blocks
Relay normally
opend terminal
Relay normally
closed terminal
Relaypublic-side
Relay normally
opend terminal
Sensor
Signal
Sensor
Excitation
Sensor
Calibration
Sensor signal S
Sensor Bridge PowerE
80%FSO Calibration 1
Alarm Terminals Description: Transducer Terminals Description:

.3.
4.2 F
ast set-upworking stateoperating
4.3 System set-up working stateoperating:
4. Parameter setting
4.1 Thethree workingstates ofpressure indicator:
SELSEL
SELSEL
Measure
Working State Fast set-up
Working State
Power
on
Power
on
SELSEL
Click
SELSEL
Press 5" or 20" no operate
SELSEL
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Fast set-up workingstate
et the first alarm valueS
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Tel:028-87078792 Fax: 028-87078762 QQ:386563863 ChengDu SAND Electronic Co., Ltd.
PS4812 series pressure indicator, there are three working states: "Measure working state",
"Fast set-up working state" and the "System set-up working state". After power on both the
pressure indicator into the "Measureworking state".
Boot into measure working state, click key to enter the fast set-up working state. This state
can set the first and second alarm values. PV window display alarm character; SV window display
set-up alarm value, digit shines through the key to set the desired alarm value.
Setup is complete, click key of 5 seconds to return to Measure working state.
SELSEL
Click
Fast set-up working state
et the secondalarm valueS
Power
on
Power
on Measure
Working State Fast set-up
Working State System Set-up
Working State
SELSEL
Click Press 5"
SELSEL
Press 5"
or 20" nooperate
SELSEL
Press 5" or 20" no operate
SELSEL
From the measure working stateby clicking key into thefast set-up working state. (SV
window last digit flashing). Inthe fast set-up working state,press key more than 5seconds
into the system set-up working state.
SELSEL
SELSEL
Press 5"
SELSEL
Fast set-up workingstate
et the first alarm valueSSystem set-up workingstate
Pressure unit setting

.4.
4.3.3 pressure range setting:
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
4.3.4 display resolution setting:
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Data last bitto show: 0~ 9
To 1Carry
4.3.1 Pressure unit setting:
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
SELSEL
psi
bar
MPa
kgf/cm2
off: Do not select any pressure units
All pressure units light goes out.
By clicking and key select the desired unit of pressure. Click key to confirm.
Corresponding pressure unit lights lit, and enter the decimal place setting item.
4.3.2 Decimal place setting:
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
By clicking or key to select the desired
decimal place. Click key to confirm. And enter the
pressure range setting item.
SELSEL
By clicking or key to select the desired
pressure range. Click key to confirm. And enter the
display resolution setting item.
SELSEL
Data last bitto show: 0/2/4/6/8
To 2Carry
Data last bitto show: 0/5
To 5Carry
Data last bitto only show:0
To 10Carry
SELSEL
By clicking or key select the display resolution of pressure. ( Recommended selection
0010 ). Click key to confirm. And enter the first alarm pressure value setting item.

.5.
4.3.5 First alarm pressurevalue setting:
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
4.3.6 First alarm waysetting:
4.3.7 First alarm pressurehysteresis band setting:
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Turn off alarm;
Lower than the alarm pressure value
set the alarm;
Higher than the alarm pressure value
set the alarm;
Tel:028-87078792 Fax: 028-87078762 QQ:386563863 ChengDu SAND Electronic Co., Ltd.
SELSEL
SELSEL
By clicking key to set the first
alarm pressure value. Click key to confirm. And
enter the first alarm way setting item.
"0001" way codeNote: When measuringthe pressure islower than thealarm pressure
value.AL1 alarm indicator lights.7 , 8terminals conduction; 8, 9 terminalsdisconnect.
Whenmeasured pressure valueis higher thanthe alarm pressure value, AL1 alarm
indicator is off.7,8 terminals disconnect;8,9 terminals conduction.
"0002" way codeNote: When measuringthe pressure islower than thealarm pressure
value, AL1alarm indicator isoff. 7 ,8 terminals disconnect;8 , 9 terminals conduction.
Whenmeasured pressure valueis higher thanthe alarm pressure value, AL1alarm
indicator lights. 7, 8 terminalsconduction; 8 ,9 terminals disconnect.
By clicking or key select the first alarm way. Click key to confirm.
And enter thesecond alarm pressurevalue setting item.
SELSEL
SELSEL
By clicking key to set First alarm
pressure hysteresis band. Click key to confirm. And
enter the second alarm pressure value setting item.

.6.
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
SELSEL
SELSEL
By clicking key to set the second
alarm pressure value. Click key to confirm. And
enter the second alarm way setting item.
4.3.8 Second alarm pressurevalue setting:
4.3.9 Second alarm waysetting:
Turn off alarm;
Lower than the alarm pressure value
set the alarm;
Higher than the alarm pressure value
set the alarm;
"0001"waycodeNote: When measuringthe pressure is lower thanthe alarm pressure
value.AL1 alarmindicatorlights.10,11 terminals conduction;11, 12 terminals disconnect.
When measured pressure value is higherthan the alarm pressure value,AL1 alarm
indicator is off. 10,11 terminals disconnect; 11,12terminals conduction.
"0002"way code Note:When measuring the pressureis lower than the alarmpressure
value, AL1 alarmindicator is off. 10,11 terminals disconnect; 11,12terminals conduction.
Whenmeasured pressure value ishigher than the alarm pressure value, AL1 alarm
indicator lights. 10,11 terminalsconduction; 11,12 terminals disconnect.
By clicking or key select the first alarm way.Click key to confirm.
And enter the second alarm pressurevalue setting item.
SELSEL
4.3.10 Second alarm pressure hysteresisband setting:
SELSEL
By clicking key to set First alarm
pressure hysteresis band. Click key to confirm. And
enter the Calibration way setting item.

.7.
4.3.11 Calibration way setting:
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Automatic calibration
Manual calibration;
4.3.13 Communication address setting (Optional):
4.3.12 output signal setting
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
output: 0 10mA
output: 0 20mA
output: 4 20mA
output: 0 10V
output: 0 5V
output: 1 5V
SELSEL
By clicking keyselect the communicationaddress . Optional
address: 0001 ~0255 . Click key to confirm.then enter theCommunication baud
rate setting item.
SELSEL
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
0001 is startingaddress
0255 is terminationaddress
Tel:028-87078792 Fax: 028-87078762 QQ:386563863 ChengDu SAND Electronic Co., Ltd.
SELSEL
By clicking or key select the Calibration way. ( Recommended selection 0000 ).
Click key to confirm. And enter into the output signal setting item.
SELSEL
By clicking or key select the output signal . Click key to confirm.
If the no communication function, then enter the key lock setting item
(see 4.3.15). If the with a communication function, then enter the
communication address setting item.
pressure indicator
pressure indicator

.8.
4.3.14 Communication baud rate setting(Optional):
4.3.15 key lock setting:
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Key does notlock
can modify theparameters
Key lock
can not modifythe parameters
4.4 System setting menutable
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
2400bps
4800bps
9600bps Recommend
19200bps
38400bps
Unit
dot
RN
Pressure
Range
Setting
- - - -.
- - -.-
- -.--
-.- --
1000 1500 2000
2500 3000 3500
4000 5000 6000
7000 7500 8000
9999
According to
supporting sensor range,
the pressure unitand
decimal position setting.
psi
bar
MPa
kgf/cm
off
2
Choice of fourpressure
units and provideclose
pressure unit options.
By matching mass
Sensor range Or
According to theuser
Demand set
Decimal Position Setting
(Tobe continued onnext table)
SELSEL
By clicking or key select the Communication baud rate. ( Recommended
selection 9600 ). Click key to confirm. And enter the key lock setting item.
SELSEL
By clicking or key to select whether the key lock, Click key to
confirm. And back enter the pressure units setting item(back 4.3.1).
indicator
Item Name Options Explain Initial Value
Pressure
Units
Setting
By matching mass
Sensor range Or
According to theuser
Demand set
By matching mass
Sensor range Or
According to theuser
Demand set
Decimal
Place
Setting

.9.
LCK
0001
0002
0005
0010
0010
dv
AL1
According to
user requirementssetting
0000 9999 80 RN
SEL1
0000
0001
0002
0000: Turn off alarm
0001: Pressure value less than setting Alarm
0002: Pressure value more than setting Alarm 0002
DLY1 0000 0200
AL2 0000 9999 RN 20
SEL2
0000
0001
0002 0001
DLY2 0000 0200
E_SC
0000
0001 0000: Automaticcalibration method
0001: calibration methodManual
0000
0000
0000
OUT
0~5V
1~5V
0~10V
0~10mA
0~20mA
4~20mA
Addr 0001 0255 0001
Provide 6types standard output
signal users todemand their own
programming setting.
According
to the user
Demand set
bps
2400
4800
9600
19200
38400
Provide 1~255 address
programmable setting (optional)
Provide 5 types standardbaud rate
programmable setting (optional)
9600
0000
0001
0000: Key notlock,
can modify theparameters
0001: key lock,
can not modifythe parameters
0001: the endof the display:0 ~ 9
0002: the endof the show:0,2,4,6,8
0005: the endof the show:0,5
0010: the endof the showonly: 0
0000
(Connected to thebefore table)
Tel:028-87078792 Fax: 028-87078762 QQ:386563863 ChengDu SAND Electronic Co., Ltd.
4.4 System setting menutable
Item Name Options Explain
Display
Resolution
Setting
First
Alarm Value
Setting
Initial Value
First
Alarm Way
Setting
According to
user requirementssetting
0000: Turn off alarm
0001: Pressure value less than setting Alarm
0002: Pressure value more than setting Alarm
First Alarm
Hysteresis
Band Setting
According to
user requirementssetting
According to
user requirementssetting
Second
Alarm value
Setting
Second
Alarm way
Setting
Second Alarm
Hysteresis
Band Setting
Calibration
Way Setting
Output
Signal
Setting
Communication
Address setting
(Optional)
Communication
Baud Rate
Setting
(Optional)
Key Lock
Setting

.10.
5 Pressure calibration operationindicator
5.1 Automatic calibrationof pressure operation:indicator
Automatic calibration beforethe unlock key(the "LCK" parameterset "0000"),and
calibration methods forautomatic calibration (the"E_SC" parameter set"0000").
Guarantee melt pressure transducer is working in environment temperature and
working pressure iszero.
Themelt pressure transducerand intelligent pressureindicator according tothe
instructionto connect well,and also connectedthe 220VAC power supply. Entered
measurementinstrument self-test state,then can beautomatically calibrated, the
concrete operation isas follows:
SELSEL
After about5 seconds, PVwindow shows or . SV valuesin the
window dispaly "16,000~ 25,000" between(ten thousand's place in PV windowat the end
of display). Thisnumber is thepressure transducer 80% range of thecode values. Waiting
in the calibrationprocess of keycan not letgo.
Click down the key while youclick the key, PV windowdisplay ,
SV values in thewindowdisplay"from 2000 to6000" between, thisvalue for thepressure
transducer zero-point codevalue, while theCAL calibration-lightflashes.
SELSEL
After about5 seconds, PVwindow shows .Pressure transducer calibration
information has beenwritten to at this timeat the endof the automatic calibration
operation, calibrationlight goesout. Throughoutthe calibrationprocess key and do
not letgo. (If thisprocess does notshow that the80% range value, or this value error is
too large.please re-operationof the automaticcalibration, andcheckeitherthe
range settings are corrector pressure transducerand connection are correct.)
Then, release the key, the into the F . Click
the key twice, the will be backto m .
Automatic calibrationoperation is complete.
indicator
indicator
indicator
indicator is ast set-up workingstate
indicator easuring working state
SELSEL
SELSEL
SELSEL
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Detection transducer zero-point
code value
Detection transducer 80%range
code value
Press the key
Do not letgo
SELSEL
Indicator
easure working state
back to
m.
the key canrelease at thistime.
SELSEL
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
AL1AL1
AL2AL2
CALCAL
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Indicator easure working stateinto m .
SELSEL
Press the key
Do not letgo and
Click the key
Press the key
Do not letgo
SELSEL

.11.
Tel:028-87078792 Fax: 028-87078762 QQ:386563863 ChengDu SAND Electronic Co., Ltd.
5.2 calibration of pressure operation:Manual indicator
This function isfor pressure transducerwithout calibration signalor calibration signal
error too largethat can notadjust.Before manual calibrationwe should unlockthe key
(the "LCK" parameterset "0000"), and calibration methods for the manual calibration
(the "E_SC" parameterset "0001"). Guaranteepressure transducer probe-pressureis zero.
First , Installingthe pressure transducerto the providestandard pressure sourcedevice.
Then connnect thepressure transducer andpressure indicator according to the instruction
to connect, andthen connected the220VAC power. Indicator power-on self -test into
measure working state,then in accordancewith the operation entering to systemparameter
setting state (4.3 - page3). The rangeis set tothe corresponding pressuretransducer range,
and thencan be manuallycalibrated, the concreteoperation is asfollows:
Press the key while you click the key, PV window display ,
SV window value should be " 2000 5000 " , this value is the pressure
transducer zero-point's codevalue, while theCAL calibration-light flashes. click the
key to confirm the zero-point code. Inthe calibration process pressing the
key can notrelease.
between
SELSEL
SELSEL
Afterconfirming zero-point code,PV window display , then through
a standard pressuresource to thepressure sensor tofull pressure range, then PV win dow
dispaly or , SVwindow value should be between "16,000
32,000 " (ten thousand's placein PV windowat the endof display ), waiting for the value
of relative stability, thenclick the toconfirm and the calibrationlight goes out. PV
window display thevalue of astandard source to provide of the pressure value. Rel eas e
the key and unload pressureto zero, then the into the f
. Click the key twice, i will be backto m .
Manual calibration operationis complete. (If the PVwindow display the standard pressure
value error istoo large, returnto step re-operation.)
indicator will be ast set-up
working state ndicator easure working state
SELSEL
SELSEL
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Detection transducer zero-pointcode
Manual calibration iscomplete
PV window displayzero
Release key atthis time canbe.
SELSEL
Confirm the
Zero-point code
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
AL1AL1
AL2AL2
CALCAL
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
Test fullrange pressure code
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
AL1AL1
AL2AL2
CALCAL
PSIPSI
BarBar
MPaMPa
kg/cmkg/cm22
SELSEL
PVPV
SVSV
PS4812 PRESSURE GAUGEPS4812 PRESSURE GAUGE
AL1AL1
AL2AL2
CALCAL
SELSEL
Press the key
Do not letgo and
Click the key
Press the key
Do not letgo
Pressure to thefull range
SELSEL
Click the key
Confirm the
Full range pressure
code value;
Uunloading pressure
to zero.

.12.
7 SimpleFault Repair
Example : PS4812D / 2 /3
The Intelligent PressureIndicator with 3.33mV/ V inputpressure transducer.
With aprogrammable output functionand relay alarmfunction.
8 ModelFormat
6 Measure workingstate
6.1 Measure workingstate
6.2 drift -clear operation:Measure workingstate
PV window displaythe pressure measurementvalue, On the right correspond pressure
units light longLeung. SV windowshows the first alarm pressure value. Normal m
on the leftalarm and calibrationlight is off,when the test pressur value is
lower or higherthan the alarmpressure value, theAL2 or AL1 alarm lights turn on; wh en
the test pressurevalue is torestore Normal, theAL2 orAL1 alarmlights turn off.
easure
working state
First automaticcalibration operation (section5.1 on page10). Aftertime, if thereare
temperature drift ortime shift, youcan hold downthe key atthe same time click
key to clearthe current drift value.if clear wrong ,you can hold downthe key
and key,more than 5seconds to restorezero.
SELSEL
SELSEL
Without anydisplay, checkwhether the correct220VAC connected, if not, check the
switching power whetherhas output .
If theuser connection errorcaused major fault.Please contact meto replace parts for
you , suchas the powersupply board,AD / DAboard, display board.
PV windowdisplay "88.88" or"- - .--". Because thepressure transducer and
wrongconnection or poorcontact. as longas the connectionaccess cantrouble
clearing.
PVwindow display thepressure value jumpword: usually becauseof interference,
andground ispoor contact withthe earth, aslong as the shield can be connected
and with theearth.
indicator
PS4812
/123
//4
/
D
4: 485 communicationwith computer (optional)
3: Withrelay alarm
2: Programmable outputsignal function (optional)
1: Only display, without theoutput signal (optional)
D: 3.33mV/V input (optional)
The defaultis 2.0mV/V input
pressure transducer
pressure transducer

Open thepackage, Please checkthe product whetherit meets yourrequirements,
packaging, products if there is anydamage, if foundin error.Please contact us.
This productis a precisionmeasuring indicator.Can not be beat, pounding, powerful
treatment. Improperoperation due toman-made damage causedby products notunder
warranty.
The following arenot covered underwarranty:
Not in accordancewith the instructions,proper installation, man-madeproduct damage;
Unauthorized users ofthe product forrepairing or reconstruction;
By irresistible externalforces caused bydamage to theproduct;
Unclear or missingproduct label, theproduct looks seriouslydamaged.
If there isany problem whenyou are usingour products, Please keep defective product,
contact with ourcompany, explainthe phenomenonof failureand useof the environment,
our company willprovide timely technicalsupport. Do notunauthorized repair.
9 Service
ChengDu SAND Electronic Co., Ltd.ChengDu SAND Electronic Co., Ltd.
Http://www.sandcop.com
E-mail:[email protected]
Http://www.sandcop.com
E-mail:[email protected]
SAND PS4812 090517SAND PS4812 090517
TEL +86-28-87078792
FAX +86-28-87078762
TEL +86-28-87078792
FAX +86-28-87078762
Table of contents
Popular Measuring Instrument manuals by other brands

Sonel
Sonel MRU-120HD quick start

PCB Piezotronics
PCB Piezotronics 3711F122G Installation and operating manual

Ditel
Ditel MICRA-E Quick installation guide

ABB
ABB TRIO-WIRL ST4000 instruction manual

Endress+Hauser
Endress+Hauser CA80COD operating instructions

Agilent Technologies
Agilent Technologies 2100 Bioanalyzer System user guide