
REFRIGERANT METERING DEVICE
CSPHP Models:
These coils have a factory-installed hard-shutoff TXV designed
only for use with R-410A refrigerant. Use only with outdoor
units designed for R-410A.
CSRHP Models:
These coils have a factory-installed hard-shutoff TXV designed
only for use with R-22 refrigerant. Use only with outdoor units
designed for R-22.
NOTE: ALL TXV'S HAVE PRESET SUPERHEAT
SETFINGS AND ARE FIELD NON-ADJUSTABLE.
Step l--Connect Condensate Lines
The coil is designed to dispose of accumulated water through
built-in condensate drain fittings. Two 3/4-in. female
threaded-pipe connections are provided in each coil condensate
pan. Install a trap in condensate line as close to coil as possible.
Make trap at least 3 in. deep and no higher than the bottom of
unit condensate drain opening. (See Fig. 2.) Pitch condensate line
1 in. for every 10 ft of length to an open drain or sump.
#_,S COIL f FAN UNIT
DRAIN PAN LEVEL
A91039
Fig. 2 -Typical Trap Installation
NOTE: If unit is located in or above a living space where
damage may result from condensate overflow, a field-supplied,
external condensate pan should be installed underneath entire
unit, and a secondary condensate line (with appropriate trap)
should be run from the unit into the pan. Any condensate in this
external condensate pan should be drained to a noticeable place.
As an alternative to using an external condensate pan, some
localities may allow the running of a separate 3/4-in. condensate
line (with appropriate trap) per local code to a place where the
condensate will be noticeable. The owner of the structure must be
informed that when condensate flows from secondary drain or
external condensate pan, the unit requires servicing or water
damage will occur. MAINTENANCE
To ensure optimum performance and to minimize possible
equipment problems, periodic maintenance must be performed on
this equipment. Consult your dealer on proper frequency of
maintenance and the availability of a maintenance contract.
Proper maintenance on this equipment requires certain skills and
tools. If you do not possess these, obtain qualified dealer
assistance.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Disconnect all electrical power to air handler (furnace) and
outdoor unit before performing any maintenance or service
on unit. Units may have more than 1 electrical power
supply.
Minimum maintenance should be performed on the equipment as
follows:
1. Check and clean or replace air filter each month or as
required.
2. Check cooling coil, drain pan and condensate drain at start
of each cooling season for cleanliness. Clean as needed.
NOTE: Because of possible damage to equipment, or personal
injury, maintenance should be performed by qualified persons
only.
CUT HAZARD
Failure to follow this warning could result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when
handling parts.
A. Air Filter
An air filter is not provided as an integral part of this cooling coil.
However, a field-supplied filter must be used upstream of the coil
and must be inspected frequently. When filter becomes clogged
with dust or lint, it should be replaced (disposable type) or
cleaned (cleanable type). Inspect filter at least once each month
and replace or clean at least twice a year (more often if necessary).
NOTE: Do not operate coil without a filter in place in return-air
duct. Always replace filter with same size and type filter.
B. Condensate Pan and Drain
Check drain pan and condensate drain at the same time cooling
coil is checked. Clean drain pan and condensate drain thoroughly.
Flush pan and drain tube with clear water. If drain tube or trap is
restricted, clean with high-pressure water. If this does not work,
try a plumber's snake or similar probe device.
C. Cleaning Coil
To gain access to coil. it may be necessary to cut a window in
ductwork.
After cutting out section of ductwork and cleaning coil, cover
opening with new, evenly cut piece of sheet metal and fasten in
place with sheet metal screws.
Coil is easily cleaned when dry. Therefore, check and clean coil
before each cooling season. Inspect coil periodically during
cooling season. If coil is coated with dirt or lint, clean with a
vacuum using soft brush attachment. BE CAREFUL NOT TO
BEND COIL FINS. If coil is coated with oil or grease, disconnect
and remove coil from ductwork. Clean coil with mild detergent
and water solution. Rinse with clear water.