1. Notes on documentation
These instructions are intended for qualified personnel who are
familiar with the assembly, installation and operation of the ISYGLT
system. It is essential that you read these operating instructions
through before commissioning and keep them accessible for further
use.
SEEBACHER cannot accept any liability for damage or malfunctions
resulting from failure to observe these instructions.
1.1. Retention of documents
These instructions and all other applicable documents are part
of the product. They must be handed over to the device operator.
The operator will store the documents so that they can be made
available if necessary.
1.2. Symbols used
Observe the following safety and other instructions in the manual:
Handling instruction
The hand indicates that you should carry out an act.
Danger!
Immediate danger to life!
Attention!
General notes, useful information and special features
Directory of Content
1. Notes on documentation
1.1. Retention of documents
1.2. Symbols used
2. Safety instructions
2.1. Intended usage
2.2. Predictable mishandling
2.3. Safe handling
2.4. Qualification of staff
2.5. Changes to the product
2.6. Use of spare parts and additional equipment
2.7. Liability notes
3. Warranty
4. Declaration of Conformity
5. Service address
6. Maintenance / Care / Disposal
7. Storage
8. Assembly
9. Product description
10. Technical Data
10.1. Pin assignment
11. Wiring diagram

3
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
The module is integrated into a surface-mounted or flush-moun-
ted housing. Extreme environmental conditions impair the func-
tion of the product.
• Protect module from shocks
• Use module indoors only
• Protect module from humidity
In addition to these safety instructions, you must also observe
the special safety instructions listed in the individual chapters for
the individual acts.
2.4. Qualification of staff
Assembly, commissioning, operation, maintenance, decommis-
sioning and disposal may only be carried out by qualified staff.
Work on electrical parts may only be carried out by a trained
electrician in accordance with the applicable regulations and
directives. Other activities in connection with the ISYGLT module,
such as assembly and installation of system components with
tested standard plug connections, as well as operation and con-
figuration of the ISYGLT module may only be carried out by trai-
ned staff.
2.5. Changes to the product
Unauthorized modifications to the ISYGLT module which are not
described in this or the other applicable instructions can lead to
malfunctions and are prohibited for safety reasons.
2.6. Use of spare parts and additional equipment
The module may be damaged if unsuitable spare parts and addi-
tional equipment are used. Only use original spare parts and
additional equipment from the manufacturer.
2.7. Liability notes
SEEBACHER accepts no liability or warranty whatsoever for
damage and consequential damage caused by non-compliance
with the technical regulations, instructions and recommendati-
ons. SEEBACHER shall not be liable for any costs or damage
incurred by the user or third parties as a result of the use of this
equipment, in particular improper use of the equipment, misuse
or malfunction of the connection, malfunction of the equipment
or connected devices.
SEEBACHER accepts no liability for printing errors.
2. Safety instructions
Observe the following general safety instructions when installing
and commissioning the device:
Assembly and installation of the ISYGLT module may only be carried
out by a qualified electrician. Other activities in connection with the
ISYGLT module, such as assembly and installation of system com-
ponents with tested standard plug connections, as well as operation
and configuration of the ISYGLT module may only be carried out by
trained staff.
Observe the electrical installation regulations of the country in which
the device is installed and operated as well as its national accident
prevention regulations. In addition, observe internal company regu-
lations (work, operating and safety regulations).
Before working on the ISYGLT module system, it must be
disconnected from the power supply and secured against
being switched on again. After completion of the assembly,
installation and maintenance work, an electrical check must
be carried out! Check all protective conductor connections
and the voltages at all connection plugs as well as at each
individual module slot.
2.1. Intended usage
The sensor is exclusively suitable for regulation (control) in con-
junction with ISYGLT system components. Any other use is not
intended. The limit values stated in the technical data must not be
exceeded under any circumstances. This applies in particular to
the permissible ambient temperature range and the permissible
IP protection type. For applications with a higher required IP pro-
tection type, the ISYGLT module must be installed in a housing
or a cabinet with a higher IP protection type.
2.2. Predictable mishandling
The module must not be used in the following cases in particular:
•explosive area
When operating in explosive areas, sparking can lead to defla-
gration, fire or explosions.
2.3. Safe handling
This module corresponds to the state of the art and the recog-
nised safety regulations. Each device is tested for function and
safety before delivery.
Only operate this module in perfect condition in accordance with
the operating instructions, the applicable regulations and directi-
ves of the country in which the device is installed and operated,
and the applicable safety and accident prevention regulations.

4
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
6. Maintenance / Care / Disposal
The product is maintenance-free. The device has highly sensitive
sensors and lens systems. Soiled devices can be cleaned with a
dry wipe. If this is not sufficient, a wipe slightly moistened with soap-
water mixture can be used. Do not clean the lens system with
abrasive or aggressive cleaning products.
Disposal (European Union)
Do not dispose of product in household waste! Products with this
symbol
7. Storage
The product must be stored in a dry place, protected from dirt and
mechanical stress. After damp or dirty storage, the product may only
be operated after a condition check by an authorised electrician.
8. Assembly
(Only by certified electrician!)
Mount the product only when it is in a power-free state!
Switch off the power supply, check that there is no voltage, secure
against being switched on again!
The device may only be operated at voltages according to the tech-
nical data and loaded with the currents defined therein. Only use
suitable equipment (system modules).
Check that there are no loose parts in the product. If this is the case
and the presence of such parts is not explicitly described, do not
install or commission the product.
Only use suitable cables and fixing screws.
Assembly site
• The product is intended for installation in a surface-mounted or
flush-mounted housing.
Assembly steps
(Read completely before assembly!)
• Mount the device in any position, but in such a way that the inco-
ming of light is not affected.
• Make the electrical connections according to the wiring diagram.
• Only after a complete connection and a visual test by a qualied
electrician, the system may be put under voltage.
Seebacher GmbH
Marktstrasse 57
83646 Bad Tölz
GERMANY
Phone: +49 (0) 80 41 / 77 77 6
Fax: +49 (0) 80 41 / 77 77 2
www.seebacher.de
info@seebacher.de
5. Service address
4. Declaration of Conformity
The valid declaration of conformity for the module can be requested
from us free of charge by stating type and article no. as follows:
By phone: +49(0)8041/77776
By fax: +49(0)8041/77772
By mail: info@seebacher.de
3. Warranty
We provide warranty within the framework of the statutory provisi-
ons. These are limited to the intended use of the module and refer
to the repair or replacement of the ISYGLT module. Please send the
device with an attached error description to our company address
given below.
must be disposed of according to the EU directive WEEE 2012/19/
EU on waste electrical and electronic equipment at the local collec-
tion points for waste electrical and electronic equipment!

5
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
The types also differ in the angle of detection of the light sensor. Here the base module is plugged together with an additional PCB.
This results in the following variants:
Base module Additional PCB Description
Art. no. 80085041 Art. no. 80085046 Light control sensor light tube 25° with motion sensor
Art. no. 80085041 Art. no. 80085042 Light control sensor light tube 30° with motion sensor
Art. no. 80085041 Art. no. 80085050 Light control sensor light tube 30° with motion sensor BW10, long range
Art. no. 80085041 Art. no. 80085043 Light control sensor light tube 40° with motion sensor
Art. no. 80085041 Art. no. 80085047 Light control sensor light tube 25° without motion sensor
Art. no. 80085041 Art. no. 80085044 Light control sensor light tube 30° without motion sensor
Art. no. 80085041 Art. no. 80085045 Light control sensor light tube 40° without motion sensor
9. Product description
The digital light control sensor with double wavelength evaluation to adjust the measuring brightness to the sensation of the human eye is avai-
lable with or without ultra-miniaturised motion sensor. The light sensor uses the reflected light measurement method, which delivers the standar-
dised lux value using complex calculation algorithms and keeps it constant in the control method.
The benefits of this technology are the easy installation and commissioning, as well as the compensation of age- and contamination-related
influences of the illuminants and luminaires. This ensures that the required standardised illuminance is precisely maintained with optimised
energy requirements. Master-Slave measurement evaluations are available for systems with complex lighting conditions, which guarantee the
required brightness even in darker areas. Freely definable setpoints are available to the user, which can be activated as required and constantly
regulated by the sensor. For commissioning and service purposes, emergency and bypass functions are available which allow the lighting to be
activated at any brightness.
The light sensor has 2 further inputs, which can be operated either as a freely programmable input or wired with motion sensors. The internal
and optional external motion sensors are freely programmable in the linkage.The parameterisation determines whether the switch-on or only the
switch-off is activated, whether a timeframe after switch-off until the next switch-on is desired, with which brightness the system is started and
much more. Functions such as On/Off, central switch-on, central switch-off, enabling BW switch-on function and the interconnection of up to 3
sensors in a control zone are available via BUS linking.
Inputs
• 2 semiconductor inputs for buttons or motion sensors with potential-free contacts
Function displays
• 1 red LED „Power“ indicates the operating voltage (only active in test mode)
• 1 yellow LED ashes to indicate communication with the master via the subnet (only active in test mode)
Connections
• 1 connection for the subnet (BUS A and B, RS-485)
• 2 connections for the operating voltage (Ub, 0V)
• 2 connections for external contacts such as motion sensors, presence sensors, buttons, etc.

6
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
Type designation LSR-02 (base module + PCB according to selection)
Article no. 80085040
Operating voltage 12-35V DC
Current consumption at 24V DC max. 20mA
Inputs 2 semiconductor inputs for buttons or external motion sensors / presence sensors (potential-free contacts)
Subnet (RS-485) with integrated overvoltage protection
Dimensions LxWxD 30x34x31.2mm (both PCBs completely assembled)
Weight 20g (LSR-02 base module + LSR-02-Z-BW-xx)
Connection screw terminals 1.5mm²
Detection range
motion sensor BW
diameter 5m at 2.5m mounting height; 91°x91°, 104 zones, range max. 5m
Detection range
motion sensor BW10
diameter 15m at 7.0m mounting height; 110°x93°, 104 zones, range max. 12m
Operating temperature -10°C to +50°C
Storage temperature -25°C to +70°C
Humidity 0-85% r. h. non condensing
Protection class IP 20
CE mark yes
10. Technical data
+Ub Operating voltage
0V Operating voltage
A Subnet (BUS A, RS-485)
B Subnet (BUS B, RS-485)
+Ub Operating voltage
0V Operating voltage
E2 Input 2
E3 Input 3
10.1. Pin assignment
Design
• printed circuit boards which can be easily integrated into surface-mounted or ush-mounted housings

7
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
View
Without motion sensor (LSR-02-Z)
with GIRA standard frame
With motion sensor (LSR-02-Z-BW)
with GIRA standard frame
Dimensions
LSR-02 base module plugged
on LSR-02-Z-BW-xx
LSR-02 base module

8
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
LSR-02-Z-xx
Thread M3
Thread M3
LSR-02-Z-BW-xx
Thread M3
LSR-02-Z-BW10-30

9
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
+24V
0V=
BUS-A
BUS-B
1 2 3 4 5 6 7 8
BUS addressS
OFF
ON
ISYGLT
Light sensor
Art. no.: 80085041+80085042
LSR-02-Basis
0V
Art. no.:
LSR-02-Z-BW-30
80085042
+Ub
GND
A
B
+Ub
GND
E2
E3
motion sensor or button
External contacts of
11. Wiring diagram

10
Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
Detection range motion sensor