• A
PPLICATION
PRG-E programmer is a programmer for start, f ame supervision and safe stop recommended for
industria or commercia use burner, with a discontinuous use cyc e (on/off burner in a period ess
than 24 hours), for power ower than 120 KW (100 000 Kca /h). For use in c osed combustion
chamber, the user must arrange a safe system of pre-purge before each start sequence, or ask a
programmer PRG-E with purge timer incorporated. Used in gas, oi or other kind of fue burners.
The produc fulfills he requiremen s of rule ABNT NBR 12313 – revision Sep . /2000. The
options are:
⇒ PRG-E- I – Input for f ame sensor by ionization, when gas is used as fue in burners that work
with this kind of sensor. See e ectrodes, sensors, ine SEL-HT-I or SEL-HT-E (e ectrode
assemb ed under draft or samp e from the specia -c ient).
⇒ PRG-E-F - Input sensor infrared f icker of the f ame.
Detecting presence of f ame when using gas, oi or other fue that causes f ame ight emission
with characteristics mentioned above.
See information of the sensors, ine SEL-SV-F.
⇒ PRG-E- U - Input for u travio et radiation sensor, when gas, ight oi s or any kind of fue that
stimu ate f ame with u travio et rays emission are used. See sensors; ine SEL-SV-U.
⇒ PRG-E- L – Input for photo-resistance sensor of cadmium su fide – visib e radiation, when oi s
or any other fue that stimu ate f ame with ye ow ight emission in dark combustion chamber
are used. See sensors; ine SEL-SV-L.
•
T
ECHNICAL DATA
⇒ Watch dog micro process – to provide safe fai ure.
⇒ Feeding 115 or 220Vac +10 -15% (phase / phase or phase / neu ral non-grounded) - 50/60
Hz ± 3%.
⇒ Power Consumption: 4 VA
⇒ Fuses: Foresee wo ex ernal fuses, one for in ernal circui s´ pro ec ion (100 mA delayed),
and o her o pro ec ou le circui s in accordance o he foreseen load in he projec ,
respec ing he boundaries of his specifica ion. O PRG-E does no e have in ernal fuse.
⇒ Protection against tension outbreaks.
⇒ Input for f ame sensor: I, F, U or L (to order, see fie d code).
⇒ Input for the f ame ionization. u travio et, visib e ight, infrared.
⇒ Minimum current of f ame (uA-dc):
I
2 /
U
200 /
L
500 /
F
2000
NOTE: The cable of he sensor of fire should be ins alled separa e from he o her cables ha
in egra e he group of command of he burner. The bes cable ype recommended for his
purpose is i used for igni ion.
⇒ Protection against fai ure due to short-circuit of the mass ionization sensor
⇒ With previous f ame verification or fa se f ame signa , before beginning the ignition.
⇒ Ignition time (Tig): 6 sec.
⇒ Purge time: 10 or 20 seconds (to order, see fie d code).
⇒ Maximum out et currents: 2 A in 250 Vac (resistive) for the ignition N.A. contacts and vs of fue ;
100 mA in 12 Vdc in the a arm version open co ector or 1A in 250Vac for contact N.A. of re ay
(iso ated or with common in the feeding system)

PROGRAMMER FOR FLAME START AND SUPERVISION, AND SAFE
STOP OF BURNER
PRODUCT: PRG-E--1-C-P TECHNICAL SHEET 2/4
Costumer Service 55 11 3019-1616
For fur her de ails see echnical bulle in
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho
• São Paulo • SP • Bra il • Phone/Fax: (55 11) 3019-
1616
http://www. elcon.com.br
Representative or Retailer
2/4
SELCON
Indus rial
Au oma ion
Selc n Ltda., keeps the right t m dify this technical sheet
whenever it is necessary –
February/10
⇒ E ectrica connections: Through whip (8 cab es); with quick adapter po arized socket( see figure
above)
⇒ Confirmation time for f ame in et: < 1 sec.
⇒ Response time for f ame fai ure: < 4 sec.
⇒ E ectrica usefu ife expectancy of out et contacts: > 100.000 operations
⇒ Mechanica usefu ife expectancy of out et contacts: > 100.000 operations
⇒ Work temperature: 0 a 60ºC
⇒ Storage ambient temperature: -5° a 65°C.
⇒ Maximum ambient air moisture for operation: 90% (40 ± 2°C) – NBR 5291
⇒ Ambient protection degree: IP 55 (except quick socket connector -IP 50)
⇒ Outer covering: ABS b ack P astic Box
⇒ Assemb y: In she tered f at surface
⇒ Fixation: through two ugs attached to the side of the outer covering
⇒ Weight: 350 grams
⇒
Warranty: 06 months (see erm of warran y)
•
Dimensional Draft (mm)
25
2
5
64
4
87
56
3
3
.
5
VM
AM
LJ
AZ
VD
BR
PT
MA
Indústria Brasi eira
PRODUTO :
CNPJ 56.935.877/0001-29
MOD. 1
IDENTIFICATION:
AL =
VS =
ALARME
VALVE
TIG =
IGNITION CONVERTER
G =
IGNITION ELECTRODE
I =
SENSOR ELECTRODE
U = VISIBLE SENSOR
L = VISIBLE SENSOR
R = RESET
200
200
VM
AM
LJ
AZ
VD
BR
PT
MA
ALIM.~
R
I
G
~250/2A
~250/2A
=12V/100mA
-
+
AL
VS
L
AZ
BR
TIG
U
LJ
AZ
VD
BR
PT
MA
I
G
~250/2A
VS
L
AZ
BR
TIG
U
CZ
~250/2A
AL
CZ
CZ
LJ
AZ
VD
BR
PT
MA
I
G
~250/2A
~250/2A
~250/1A
VS
L
AZ
BR
TIG
U
73
SEEN BY “A”
"A"
AL
~250/1A
100mA-Ret.
FU
ALIM.~
R
100mA-Ret.
FU
ALIM.~
R
100mA-Ret.
FU

PROGRAMMER FOR FLAME START AND SUPERVISION, AND SAFE
STOP OF BURNER
PRODUCT: PRG-E--1-C-P TECHNICAL SHEET 3/4
Costumer Service 55 11 3019-1616
For fur her de ails see echnical bulle in
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho
• São Paulo • SP • Bra il • Phone/Fax: (55 11) 3019-
1616
http://www. elcon.com.br
Representative or Retailer
3/4
SELCON
Indus rial
Au oma ion
Selc n Ltda., keeps the right t m dify this technical sheet
whenever it is necessary –
February/10
Série :
Mode o :
A iment.:
E012
VM
AM
LJ
AZ
VD
BR
PT
MA
Site :
PRODUTO :
SELCON LTDA.
Indústria Brasi eira
R
=12V/100mA
-
+
AL
I
G
~250/2A
~250/2A
VS
L
AZ
BR
TIG
U
ALIM.~
R
100mA-Ret.
FU
F
AZ
BR
If it is the case, purge time starts to be counted from the equipment energizing, as ong as, it does not
identify fa se f ame signa . By the end of time, f ame ignition starts, as shown in the fo owing
sequence:
* Activates ignition converter;
* Counts pre-ignition time;
* Activates a VS fue ;
* Counts ignition time;
* Confirms f ame signa . The ack of f ame b ocks burner operation and activates a arm out et (12Vdc
unti 100mA or 115 / 220 Vca unti 1A through N.A. contact of iso ated re ay or with common in the
feeding system) – See order code. Reset is done through the momentary interruption of feeding.

PROGRAMMER FOR FLAME START AND SUPERVISION, AND SAFE
STOP OF BURNER
PRODUCT: PRG-E--1-C-P TECHNICAL SHEET 4/4
Costumer Service 55 11 3019-1616
For fur her de ails see echnical bulle in
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho
• São Paulo • SP • Bra il • Phone/Fax: (55 11) 3019-
1616
http://www. elcon.com.br
Representative or Retailer
4/4
SELCON
Indus rial
Au oma ion
Selc n Ltda., keeps the right t m dify this technical sheet
whenever it is necessary –
February/10
O
RDER
CODE
- PRG-E--1-C-P
PRG-E
-
SENSOR
-
Feeding
-
C
-
P-
Required
Program
Tension
Frequency
Purge ime
Ou le ype
alarm
I
Ionization
U
U travio et
L
Visib e
(d1)
d1 = 1 =>
115Vac
d1 = 2 =>
220Vac
d2 = 1
=> 50/60 Hz
(d3)
d3 = 0 => 0 seg
.
d3 = 1 => 10 seg.
d3 = 2 => 20 seg.
(d4)
d4 = 0
=> open co ector
NPN -12 Vcc, 100 mA.
d4 = 1 => contact N.A.
iso ated - 250Vac -1A
d4 = 2 => contact N.A. –
common in network -
250Vac -1A
(d5)
d5 = 1
=>
standard
d5 = 2 a n=>
other (under order)
Obs.: The sensor and o her accessories mus be specified separa ely, according o a specific code.
BE
A ARE:
⇒
Use he programmers and/or de ec or relays exclusively wi h flame sensors of Selcon
manufac uring.
•
OTHER
PRODUCTS
AND
ACCESSORIES:
⇒ F ame Re ays – CHM-E, CHM-P, CHM-M CHM-M-IIIMe (with base) and CHM-F
⇒ Tightness Test Re ay of b ocking va ves – CHM -T
⇒ Ignition Programmers and f ame monitoring – PRG-SE, PRG-E, PRG-Ie, PRG-Ie -IIIMe (with
base), PRG-I, PRG-M and PRG–M-IIIMe (with base).
⇒ Optica F ame Sensors– SEL- SV
⇒ F ame sensors by ionization and ignitor e ectrodes – SEL-HT(standard) and SEL-HT-E (sensors
and e ectrodes assemb ed under draft or samp e from the specia -c ient).
⇒ F ame signa transmitter– ACS –TX (unti 500 meters between the sensor and re ay or programmer)
⇒ F ame Signa Converter for 4 -20 mA – ACS - CV
⇒ Ignition transformers – ACS -TE (for feeding in VAC or VCC)
⇒
Temporized ignition pane ACS – IT
⇒ Portab e ignitor (works with common a ka ine battery AA type) : ACS-IP
⇒ Ignition pane (works with common a ka ine battery AA type) : ACS-PN-E
⇒ Ignition pane of ignition and monitoring of f ame : PRG-Ie/03
⇒ Severa Cab es– ACS - CB (ignition / sensoring / communication / contro )
⇒ Connector and protector to touch for ignition cab e – ACS - CP
⇒ Articu ated socket joint – ACS - CN
⇒ Ignition and monitoring pane – ACS-PN (under consu tation)
⇒ Reform services of pi ot burners (under consu tation)
⇒
PRODUCTION DATA SUPERVISION LINE