PROGRAMMER FOR FLAME START AND SUPERVISION, AND SAFE
STOP OF BURNER
PRODUCT: PRG-E--1-C-P TECHNICAL SHEET 1/4
Costumer Service 55 11 3019-1616
For fur her de ails see echnical bulle in
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho Velho
• São Paulo • SP • Bra il • Phone/Fax: (55 11) 3019-
http://www. elcon.com.br
Representative or Retailer
1/4
SELCON
Indus rial
Au oma ion
Selc n Ltda., keeps the right t m dify this technical sheet
whenever it is necessary –
February/10
• A
PPLICATION
PRG-E programmer is a programmer for start, f ame supervision and safe stop recommended for
industria or commercia use burner, with a discontinuous use cyc e (on/off burner in a period ess
than 24 hours), for power ower than 120 KW (100 000 Kca /h). For use in c osed combustion
chamber, the user must arrange a safe system of pre-purge before each start sequence, or ask a
programmer PRG-E with purge timer incorporated. Used in gas, oi or other kind of fue burners.
The produc fulfills he requiremen s of rule ABNT NBR 12313 – revision Sep . /2000. The
options are:
⇒ PRG-E- I – Input for f ame sensor by ionization, when gas is used as fue in burners that work
with this kind of sensor. See e ectrodes, sensors, ine SEL-HT-I or SEL-HT-E (e ectrode
assemb ed under draft or samp e from the specia -c ient).
⇒ PRG-E-F - Input sensor infrared f icker of the f ame.
Detecting presence of f ame when using gas, oi or other fue that causes f ame ight emission
with characteristics mentioned above.
See information of the sensors, ine SEL-SV-F.
⇒ PRG-E- U - Input for u travio et radiation sensor, when gas, ight oi s or any kind of fue that
stimu ate f ame with u travio et rays emission are used. See sensors; ine SEL-SV-U.
⇒ PRG-E- L – Input for photo-resistance sensor of cadmium su fide – visib e radiation, when oi s
or any other fue that stimu ate f ame with ye ow ight emission in dark combustion chamber
are used. See sensors; ine SEL-SV-L.
•
T
ECHNICAL DATA
⇒ Watch dog micro process – to provide safe fai ure.
⇒ Feeding 115 or 220Vac +10 -15% (phase / phase or phase / neu ral non-grounded) - 50/60
Hz ± 3%.
⇒ Power Consumption: 4 VA
⇒ Fuses: Foresee wo ex ernal fuses, one for in ernal circui s´ pro ec ion (100 mA delayed),
and o her o pro ec ou le circui s in accordance o he foreseen load in he projec ,
respec ing he boundaries of his specifica ion. O PRG-E does no e have in ernal fuse.
⇒ Protection against tension outbreaks.
⇒ Input for f ame sensor: I, F, U or L (to order, see fie d code).
⇒ Input for the f ame ionization. u travio et, visib e ight, infrared.
⇒ Minimum current of f ame (uA-dc):
I
2 /
U
200 /
L
500 /
F
2000
NOTE: The cable of he sensor of fire should be ins alled separa e from he o her cables ha
in egra e he group of command of he burner. The bes cable ype recommended for his
purpose is i used for igni ion.
⇒ Protection against fai ure due to short-circuit of the mass ionization sensor
⇒ With previous f ame verification or fa se f ame signa , before beginning the ignition.
⇒ Ignition time (Tig): 6 sec.
⇒ Purge time: 10 or 20 seconds (to order, see fie d code).
⇒ Maximum out et currents: 2 A in 250 Vac (resistive) for the ignition N.A. contacts and vs of fue ;
100 mA in 12 Vdc in the a arm version open co ector or 1A in 250Vac for contact N.A. of re ay
(iso ated or with common in the feeding system)