Programmer PRG-SE-C-O1 equipment recommended for start, flame supervision and safe
stop for any type of burner for one stage of flame, in applications commercial or industrial and
gas Fuels or liquids light, with a cycle of use do not continuu (on/off burner Period in less
than 24 hours). For use in camera of combustion closed, the user is the river system must
provide insurance pre-purge before each sequence of start, or require the programmer PRG-SE-
C-O1 with purge timer coupled, since that the times offered are appropriate for application.
Entry for flame sensor for ionization. See electrode sensors for ionization, line SEL-HT-I
(standard) or SEL-HT-E (electrode mounted on a drawing or sample of the client).
T is product meets t e requirements of t e standard NBR 12313 of ABNT-
review Sept./2000.
•
T
ECHNICAL
D
ATA
⇒
⇒⇒
⇒
Watch dog micro process – to provide safe failure.
⇒
⇒⇒
⇒
Supply / frequency: 90 a 250 ca - 50/60 Hz
±
3%.
NOTE: To supply network consisting of p ase/neutral, s ould consider t e
possible need for its reversal (terminals 5 and 6) for flame sensor circuit
not lose sensitivity and t erefore t e capacity to detect signal of flame.
⇒ External Fuse: Foresee fuse for internal circuits’ protection in accordance to the
foreseen load in the project, respecting the boundaries of this specification.
⇒
⇒⇒
⇒
Consumption of energy: 4 A
⇒
⇒⇒
⇒
Protection against tension outbreaks
⇒
⇒⇒
⇒
Fuses: T e designer/user as s ould consider t e use of two external fuses,
one for protection of t e internal circuits of t e PRG-SE-C-O1 (250 mA
retardate), and anot er of protection t e outputs of t e circuits in accordance
wit t e load specified in t e project, wit in t e limits of t is Specification. O
programmer PRG-SE-C-O1 do not own internal fuse.
⇒
⇒⇒
⇒
Temperature of work : 0 a 60ºC
⇒
⇒⇒
⇒
Storage ambient temperature:
-
5° a 65 °C
⇒
⇒⇒
⇒
Maximum relative humidity of environment in operation: 90% (40 ± 2°C) – NBR 5291
⇒
⇒⇒
⇒
Flame Sensor: Ionization.

PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
-O1 TECHNICAL SHEET 2/6
Costumer Service 55 11 3019-1616
For further details see technical bulletin
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moi-
nho Velho • São Paulo • SP • Tel Fax:
(55 11) 3019-1616
http://www.selcon.com.br
2/6
SELCON
Automaç o Industrial
Selcon Ltda., keeps the right to odify this technical sheet
when never it is necessary
February/10
Representative or Distributor
⇒
⇒⇒
⇒
Minimum current flame: 2 microamperes dc (uA)
NOTE: T e cable of flame sensor must be installed separately from ot er
cables t at are part of t e command set of t e burner. T e best type of cable
recommended for t is purpose is used for ignition.
⇒
⇒⇒
⇒
Protection against short circuit failure sensor ionization for mass.
⇒
⇒⇒
⇒
Blocking with local signaling (LED) and remote (contact N.O.)
⇒
⇒⇒
⇒
With verification of premature flame or false flame signal, before starting the burner.
⇒
⇒⇒
⇒
Purge Time: 0, 10 or 20 seconds (see field code for request)
⇒
⇒⇒
⇒
Time of ignition: 6 sec.
⇒
⇒⇒
⇒
Time of ignition: 6 sec.
⇒
⇒⇒
⇒
Time to confirm the signal of flame:
<
1 sec.
⇒
⇒⇒
⇒
Time of answer to the flame flaw:
<
4 seg.
⇒
⇒⇒
⇒
Signaling LED (S): power-purge (LJ) / S FUEL (VD) / ALARM (VM).
⇒
⇒⇒
⇒
Maximum current per output command (TI, VS and AL): 2 A in 250 Vac (resistive).
⇒
⇒⇒
⇒
Electric connections: through socket of fast extraction polarized (see figure below).
⇒ Expected electrical life of output contacts:> 100,000 operations.
⇒ Expected mechanical life of output contacts:> 10,000,000 operations.
⇒ Reset (R), through the interruption and return of the supply in the programmer.
⇒
⇒⇒
⇒
Degree of environmental protection: IP 55 (except connector of fast extraction - IP 50)
⇒
⇒⇒
⇒
Cabinet: box ABS black color
⇒
⇒⇒
⇒
Mounting: On a flat surface protected
⇒
⇒⇒
⇒
Mounting: Through 2 screws mounted on the ears to fix of box.
⇒
⇒⇒
⇒
Weight : 180 grams
⇒
⇒⇒
⇒
Warranty: 6 months (see t e guarantee)

PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
-O1 TECHNICAL SHEET 3/6
Costumer Service 55 11 3019-1616
For further details see technical bulletin
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moi-
nho Velho • São Paulo • SP • Tel Fax:
(55 11) 3019-1616
http://www.selcon.com.br
3/6
SELCON
Automaç o Industrial
Selcon Ltda., keeps the right to odify this technical sheet
when never it is necessary
February/10
Representative or Distributor
•
Dimensional Drawing (mm)
97
31
82
60.5
41.5
68
Ø5 (2x)
36
The time to purge if necessary, get be counted from the permissions of start
(P)
closed
with energized equipment, since the equipment doesn't identify false of the presence
flame, or short circuit of the electrode flame sensor. At the end of the purge time,
starts the ignition of the flame, according to the sequence:
*
Enables the ignition transformer
(TI);
*
Counts the time to pre-ignition;
*
Enables the valve of fuel
(VS);
*
Counts the time of ignition;
*
Confirm the flame signal
(I).
The failure of ignition, flame failure, the presence of
premature flame or false, and short circuit the sensor to the mass, block the operation
of the burner, and PRG-SE-CA-O1 active Output of alarm
(AL).
The reset
(R)
it is made by the momentary interruption of the feeding.

PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
-O1 TECHNICAL SHEET 4/6
Costumer Service 55 11 3019-1616
For further details see technical bulletin
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moi-
nho Velho • São Paulo • SP • Tel Fax:
(55 11) 3019-1616
http://www.selcon.com.br
4/6
SELCON
Automaç o Industrial
Selcon Ltda., keeps the right to odify this technical sheet
when never it is necessary
February/10
Representative or Distributor
•
Scheme of electric connections
SUPPLY
R
G
TI AL VS
P
PRG-SE
654321
L2I
TI
L1 (N)
uA
_
+
ICC> 2uAdc
_
•
Diagram of times
T IM E S
W A I T I N G T O S T A R T F O L L O W I N G
P U R G E
I G N I T I O N
P R E - I G N I T I O N
t 4
t 3
t 2
t 1
6 s
1 s
0 , 1 0 o r 2 0 s
1 s
F U E L V A L V E .
V S
A L A R M L O C K .
F L A M E S E N S O R .
A L
I
K E Y O N / O F F A N D O T H E R P E R M I S S IO N S .
I G N I T IO N T R A N S F O R M E R .
P E R M I S S I O N S ( P R E S S U R E S W I T C H E S , T H E R M O S T A T S , E T C . )
T I
L 2 / L 1 ( N )
P
L E G E N D
( S U G G E S T E D M O D E L S : A C S - T E -
- C 5 O R
A C S T E -
1 -C 6 , F O R O T H E R I G N I T I O N
T R A N S F O R M E R S C O N S U T I N G T H E S E L C O N ) .

PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
-O1 TECHNICAL SHEET 5/6
Costumer Service 55 11 3019-1616
For further details see technical bulletin
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moi-
nho Velho • São Paulo • SP • Tel Fax:
(55 11) 3019-1616
http://www.selcon.com.br
5/6
SELCON
Automaç o Industrial
Selcon Ltda., keeps the right to odify this technical sheet
when never it is necessary
February/10
Representative or Distributor
A L
I
t1
V 1
T I
t4
t3
N O R M A L O P E R A T IO N
L 1 -L 2 (N )
t0
5 /6
1
3
4
2
~
t2
T E R M IN A L S O F
C O N N E C T IO N S
E L E C T R IC S
t0
FALSE SIG N O F FLAM E IN THE START
OPERATIO N W ITH PRESENCE O F
9/10
1
3
4
2
AL
I
V1
TI
L1-L2(N)
~
TERM IN ALS O F
C O NN EC TIO NS
ELE CTRIC S
AL
I
t1
V1
TI
t4
t3
L1-L2(N)
t0
5/6
1
3
4
~
t2
OPERATION WITH FLAW OF IGNITION
2
TERMINALS OF
CONNECTIONS
ELECTRICS

PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
-O1 TECHNICAL SHEET 6/6
Costumer Service 55 11 3019-1616
For further details see technical bulletin
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA.
CNPJ 56.935.877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moi-
nho Velho • São Paulo • SP • Tel Fax:
(55 11) 3019-1616
http://www.selcon.com.br
6/6
SELCON
Automaç o Industrial
Selcon Ltda., keeps the right to odify this technical sheet
when never it is necessary
February/10
Representative or Distributor
•
C
ODE
OR
R
EQUEST
PRG-SE-C
-O1
Obs.: T e sensor and ot er accessories must be specified separately, according to a
specific code.
•
B
EWARE
:
⇒
⇒⇒
⇒ Use t e programmers and/or relays detectors exclusively wit flame sensors
manufactured by t e Selcon.
•
O
THER
P
RODUCTS
A
ND
A
CCESSORIES
:
⇒
⇒⇒
⇒
Relays calls: CHM-SE, P-CHM, CHM-M, CHM-M-IIIM (with base) and CHM-F
⇒
⇒⇒
⇒
Relay tester tightness of shutoff valves: CHM-T
⇒
⇒⇒
⇒
Programmers ignition and flame monitoring: PRG-SE, E-PRG, PRG-Ie,
PRG-Ie-IIIM (with base), PRG-I PRG and PRG-M-M-IIIM (with base)
⇒
⇒⇒
⇒
Optical flame sensors: SEL-SV.
⇒
⇒⇒
⇒
Sensors flame ionization electrodes and igniters: SEL-HT (standard) and SEL-HT-E
(sensors and electrodes mounted on a drawing or sample of client-special).
⇒
⇒⇒
⇒
Signal transmitter called ACS-TX (up to 500 meters between sensor and relay or
programmer).
⇒
⇒⇒
⇒
Signal converter flame-4 -20 mA: ACS-CV
⇒
⇒⇒
⇒
Transformers Ignition ACS-NT (feeding on VAC or VDC)
⇒
⇒⇒
⇒
Panel ignition timer: ACS-IT
⇒
⇒⇒
⇒
Ignitor portable: ACS-IP (operates with batteries)
⇒
⇒⇒
⇒
Panel ignition (operates with batteries): PN-ACS-E
⇒
⇒⇒
⇒
Panel ignition and flame monitoring: PRG-Ie/O3
⇒
⇒⇒
⇒
Different cables: ACS - CB (ignition / sensing / communication / control)
⇒
⇒⇒
⇒
Connector and shield to touch ignition wire: ACS-CP
⇒
⇒⇒
⇒
Junction of articulation : ACS-CN
⇒
⇒⇒
⇒
Panel ignition and monitoring: ACS-PN (under consultation)
⇒
⇒⇒
⇒
services reform burner drivers: under consultation
⇒
⇒⇒
⇒
LINE OF SUPERVISORS PRODUCTION DATA
PRG-SE
C-
SETUP
O -
OPTION
TIME OF PURGE
(d1)
d1 =
0
=> 0 sec.
OR
d1 =
1
=> 10 sec.
OR
d1 =
2
=> 20 sec.
d2 =
1
=> 1 stage