SENTRONIC M-system R1M Series User manual

MODEL: R1M-A1
Remote I/O R1M Series
CONTACT INPUT MODULE
(contact input, 32 points)
Functions & Features
• 32-point dry contact inputs
• Easy system expansion via Modbus RTU
• CE marking
40
(1.57)
115
(4.53)
mm (inch)
175 (6.89)
MODEL: R1M-A1[1]-[2]
ORDERING INFORMATION
• Code number: R1M-A1[1]-[2]
Specify a code from below for each [1] and [2]
(e.g. R1M-A1T-M2)
[1] FIELD TERMINAL TYPE
T: M3 screw terminals
C1: FCN type connector (No CE conformance)
[2] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable (model: FCN32)
• R1X configurator software (model: R1CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
GENERAL SPECIFICATIONS
Connection
Power input, transmission: Euro type connector terminal
RS-232-C: 9-pin D-sub connector (male)
(Lock screw No. 4-40 UNC)
I/O: M3 screw terminals or FCN type connector
Isolation: Input to RS-232-C or RS-485 to power
Count memory at power loss: Count value is not saved
when the power supply is lost.
Node address setting: Rotary switch; 1 – F (15 nodes)
RUN indicator LED: Green light blinks in normal conditions.
COMMUNICATION
Baud rate: 38.4 kbps
Communication: Half-duplex, asynchronous, no procedure
Protocol: Modbus RTU
Refer to Modbus Protocol Reference Guide (EM-5650) for
supported functions.
■ RS-232-C
Standard: Conforms to RS-232-C, EIA
Transmission distance: 10 meters max.
■ RS-485
Standard: Conforms to RS-485, EIA
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S
0.9 dia.)
INPUT SPECIFICATIONS
Input: Dry contact, 32 points
Commons: All negatives
Sensing: Approx. 5 V DC (pull-up resistance 22 kΩ)
≤ 1.5 V at ON
≥ 4 V at OFF
Sampling rate: 50 msec.
• Totalizing Counter Function
Number of input channels: 16
(ch.1 thr. 16 available both with instantaneous status and
totalized value)
Max. input frequency: 100 Hz
Minimum pulse width: 5 ms
Counter reset input: Pulse rising (ch.32 assigned)
Max. counter value: 999 999 999 (reset to zero at overflow)
INSTALLATION
Power consumption
•AC: Approx. 10 VA
•DC: Approx. 7 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lbs)
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: R1M-A1
PERFORMANCE
Multi-transmission time: 5 msec.
Insulation resistance: ≥100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to RS-232-
C or RS-485 to power to ground)
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EMI EN 61000-6-4: 2007
EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
EN 61010-1: 2001
Installation Category II
Pollution Degree 2
Input or RS-232-C/RS-485 to power: Reinforced insulation
(300 V)
Input to RS-232-C/RS-485: Basic insulation (300 V)
EXTERNAL VIEW
RS-485
Connector
Power Terminals
Node Address
Setting Rotary SW
Configurator
Jack
RUN Indicator
LED
RS-232-C
9-pin Connector
ABBR. PIN NO. EXPLANATION OF FUNCTION
BA (SD) 2 Transmitted Data
BB (RD) 3 Received Data
AB (SG) 5 Signal Common
CB (CS) 7 Clear to Send
CA (RS) 8 Request to Send
1 Not Used.
4 DO NOT connect. Connecting may
6 causemalfunctions.
9
1 5
6 9
■RS-232-C INTERFACE
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: R1M-A1
MODBUS WIRING CONNECTION
R1M
T1
T2
T3
T4
R1M
T1
T2
T3
T4
T1
T2
T3
T4
R1M
CONNECTOR
RS-232-C
RS-485
*1*1
*1. Internal terminating resistor is used when the device is at the end of a transmission line.
*2. Install shielded cables to all sections and ground them at single point.
*2
FG
RS-485
CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
RS-232C
T3
T4
T2
T1
T7
T6
T5
Term.
Resist.
Output
Circuit
When the device is located at the end of a transmission line via twisted-pair cable,
(when there is no cross-wiring), close across the terminal T2 –T3 with the attached
jumper pin (or with a leadwire).
When the device is not at the end, remove the jumper pin.
*
Power
Circuit
+
–
Shielded Twisted-pair Cable
To Other
PC Recorders
Jumper*
FG
U (+)
V (–) POWER
D-SUB CONNECTOR
9
8
7
6
5
4
3
2
1
10
12
11
13
15
14
16
17
18
20
19
21
22
23
24
25
27
26
28
29
30
31
32
33
35
34
36
ch.1
ch.2
ch.3
ch.4
ch.5
ch.6
ch.7
ch.8
COM (–)
ch.9
ch.10
ch.11
ch.12
ch.13
ch.14
ch.15
ch.16
COM (–)
ch.17
ch.18
ch.19
ch.20
ch.21
ch.22
ch.23
ch.24
COM (–)
ch.25
ch.26
ch.27
ch.28
ch.29
ch.30
ch.31
Count Reset Input
ch.32
COM (–)
Input Circuit
Input Circuit
A9
A8
A7
A6
A5
A4
A3
A2
A1
A10
A12
A11
A13
A15
A14
A16
B1
:
B16
ch.1
ch.2
ch.3
ch.4
ch.5
ch.6
ch.7
ch.8
ch.9
ch.10
ch.11
ch.12
ch.13
ch.14
ch.15
ch.16
COM (–)
A9
A8
A7
A6
A5
A4
A3
A2
A1
A10
A12
A11
A13
A15
A14
A16
ch.17
CN1
ch.18
ch.19
ch.20
ch.21
ch.22
ch.23
ch.24
ch.25
ch.26
ch.27
ch.28
ch.29
ch.30
ch.31
Count Reset Input
ch.32
■ FCN TYPE CONNECTOR ■ M3 SCREW TERMINALS
CN2
B1
:
B16
COM (–)
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: R1M-A1
MODBUS COMMUNICATION
■COMMUNICATION PARAMETERS
PARAMETER SPECIFICATION
Data Mode RTU
Baud Rate 9600 /19200 /38400 (*) bps
Parity None /Odd (*) / Even
Bit Length 8
Stop Bit 1 (*) / 2
Node Address 1 (*) to 15
Floating Point Data N/A
Interface RS-232-C/RS-485
(*) Ex-factory setting
■FUNCTION CODES & SUPPORTED CODES
CODE NAME
01 Read Coil Status X Digital output from the slave
02 Read Input Status X Status of digitalinputs to the slave
03 Read Holding Registers X General purpose register within the slave
04 Read Input Registers X Collected data from the fieldby the slave
05 Force Single Coil X Digital output from the slave
06 Preset Single Registers X General purpose register within the slave
07 Read Exception Status
08 Diagnostics
09 Program 484
10 Poll 484
11 Fetch Comm. Event Counter Fetch a status wordand an event counter
12 Fetch Comm. Event Log A status word, an event counter, a message count and afield of event bytes
13 Program Controller
14 Poll Controller
15 Force Multiple Coils X Digital output from the slave
16 Preset Multiple Registers X General purpose register within the slave
17 Report Slave ID Slave type / ‘RUN’ status
18 Program 884/M84
19 Reset Comm. Link
20 Read General Reference
21 Write General Reference
22 Mask Write 4X Register
23 Read/Write 4X Register
24 Read FIFO Queue
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: R1M-A1
■DATA ADDRESS
ADDRESS TYPE DATA NAME
GH2 J3 A1 D1
FORMAT
Coil (0X) 1 – 32 --- --- --- Y bit DO *1
33 – 48 Y --- --- --- bit Cold junction compensation SW
(0: Disable, 1: Enable) *2
Input Status (1X) 1 – 32 Y Y Y --- bit DI *3
33 – 48 Y Y --- --- bit ADC overrange
Input Register 1 – 16 Y --- --- --- I AI in %(1 –8for TypeJ3)
(3X) 17 – 48 Y Y --- --- F AI per channel in engineering unit
49 – 50 Y --- --- --- F Cold junction temperature *2
81 – 96 Y Y --- --- I Channel status
513 Y Y Y Y I Bit System Status
0 to 5 Reserved for system use
6 E2PROM diagnostics (0: Normal, 1: Error)
7 ADC error (0: Normal, 1: Error)
8 to 15 Reserved for system use
514 – 521 Y Y Y Y B16 Model No. (“R1M-x”)
522 – 529 Y Y Y Y B16 Serial No.
530 – 537 Y Y Y Y B16 Hardware version No.
538 – 545 Y Y Y Y B16 Firmware version No.
Holding Register 1 – 16 --- --- --- --- I (Reserved for AO in %)
(4X) 17 – 48 --- --- --- --- F (Reserved for AO in engineering unit)
145 – 160 Y Y --- --- I I/O type No.
161 – 176 Y --- --- --- I Burnout type (161 –168 for TypeJ3)
(0: No burnout, 1: Upscale, 2: Downscale) *4
I = 16-bit integer, F = 32-bit floating, B16 = 16-byte character
*1. Discrete output only.
*2. Thermocouple input only.
*3. Trigger contact input for Types GH2 and J3. (Only Address 10001 is enabled.)
*4. Same setting for all channels. For potentiometer inputs, always leave certain residual resistance at 0% side in order to
avoid wrong burnout detection. (0% input or shortcircuit across the terminals 1–2=Wire breakdown at the terminal 3)
ADDRESS DATA FORMAT NAME
Input Status (1X) 1 – 32 bit (1 bit) Contact Input
Input Register (3X) 1 – 32 Unsigned Long (32 bits) Totalized Value
Holding Register (4X) 1 – 32 Unsigned Long (32 bits) Counter Preset Value
■DATA ADDRESS (COUNTER)
Sign
Address n
• 32-bit Floating
Address n+1
Exponent Mantissa
Address n, High-order
• 32-bit Integer, No sign (R1M-A1)
Address n+1, Low order
High order bytesHigh order bytes Low order bytesLow order bytes
■INPUT DATA
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: R1M-A1
■INPUT REGISTERS DESCRIPTION
(1) ANALOG INPUT IN % (30001 to 30016; 30001 to 30008 for J3)
Indicates analog input values in percentage for each channel (1 – 16; 1–8forJ3).
(2) ANALOG INPUT IN ENGINEERING UNIT (30017 to 30048; 30017 to 30032 for J3)
Indicates analog input values in engineering unit for each channel (1 – 16; 1–8forJ3). The unit is specific to each input type: C
for temperature, Volts for voltage, and % for potentiometer. The data are 32-bitfloating values, which requires two consecutive
registers for one module.
(3) CHANNEL STATUS (30081 to 30096)
Indicates the current status of analog inputs (1 – 16; 1–8forJ3). The following list shows the names and descriptions of each bit.
INPUT TYPE & RANGE A/D DATA (Decimal)
DC ±20V±20000
±5V ±5000
±1V ±10000
±0.8V ±8000
±0.2V ±20000
±50mV ±5000
±10mV ±10000
Thermocouple Temperature x 10
RTD Temperature x 10
Potentiometer 0 – 100Ω ±2000
0–500Ω
0–1kΩ
0–10kΩ
BIT NAME DESCRIPTION
6 Input Overrange Indicates the designatedanalog input is in overrange, defined as one or
more of the following condition:
• ADC input value 0X0000 or 0XFFFF
• Burnout status for thermocouple input
• Out of range defined in the temperaturetable (thermocouple and RTD)
• ADC error
0 : Normal
1 : Overrange
7 ADC Error Indicates the status of ADC.
0 : Normal
1 : Error
12 Cold Junction Compensation SW Indicates whether the cold junction compensation is enabled or disabled, for
thermocouple input.
0 : Disable
1 : Enable
Others Reserved For system’s use
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: R1M-A1
■INPUT REGISTERS DESCRIPTION
Indicates I/O type for each channel. The data are 16-bit integer values.
MODEL I/O I/O TYPE SELECTION USABLE RANGE NOTES
R1MS-GH3 DC input 0X00 -10 to 10 V -10 to 10 V
R2M-2G3
R1M-GH2 DC input 0X00 -20 to 20 V -22.7 to 22.7 V ATT SW ON
0X01 -5 to 5 V -5.6 to 5.6 V ATT SW ON
0X02 -1 to 1 V -1.4 to 1.4 V ATT SW ON
0X03 -800 to 800 mV -860 to 860 mV
0X04 -200 to 200 mV -215 to 215 mV
0X05 -50 to 50 mV -53 to 53 mV
0X06 -10 to 10 mV -13.4 to 13.4 mV
R1M-GH2 T/C input 0X10 (PR) 0 to 1770°C
R1MS-GH3 0X11 K (CA) -270 to 1370 °C
R2M-2H3 0X12 E (CRC) -270 to 1000°C
0X13 J (IC) -210 to 1200 °C
0X14 T (CC) -270 to 400 °C
0X15 B (RH) 100 to 1820 °C
0X16 R -50 to 1760 °C
0X17 S -50 to 1760 °C
0X18 C (WRe 5-26) 0to 2320 °C
0X19 N -270 to 1300 °C
0X1A U -200 to 600 °C
0X1B L -200 to 900 °C
0X1C P (Platinel II) 0 to 1395 °C
R1M-J3 RTD input 0X30JPt 100 (JIS ’89) -200 to 500 °C
0X31 Pt 100 (JIS ’89) -200 to 660 °C
0X32 Pt 100 (JIS ’97/IEC) -200 to 850 °C
0X33 Pt 50Ω (JIS ’81) -200 to 649 °C
0X34 Ni 508.4Ω -50 to 280 °C
0X35 Pt 1000 -200 to 850 °C
POT input 0X40 0 to 100 ohms 0 to 100 %
0X41 0 to 500 ohms 0 to 100 %
0X42 0 to 1k ohms 0 to 100 %
0X43 0 to 10k ohms 0 to 100 %
R1M-D1 DO 0X60
R1M-A1 DI 0X70
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: R1M-A1
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
■ M3 SCREW TERMINALS
123456789
10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
T1 T2 T3 T4 T5 T6 T7
104 (4.09)
10 (.39)
105 (4.13)
14 (.55)
163 (6.42)
36–M3 I/O TERMINALS
165 (6.50)
175 (6.89)
3–5 (.20) dia.
MTG HOLES
FOR WALL MOUNT.
6.2 (.24)
15.5 (.61)
[6 (.24)]
40 (1.57)
3 (.12)
46 (1.81)
DIN RAIL
35 mm wide
■ FCN TYPE CONNECTOR
T1 T2 T3 T4 T5 T6 T7
104 (4.09)
10 (.39)
105 (4.13)
14 (.55)
163 (6.42)
165 (6.50)
175 (6.89)
3–5 (.20) dia.
MTG HOLES
FOR WALL MOUNT.
FCN TYPE I/O CONNECTOR
[6 (.24)]
40 (1.57)
40 (1.57)
Connector Pin
Assignment
A1 B1
A16 B16
CN1 CN2
See Caution below
Caution: DO NOT APPLY EXCESSIVE FORCE onto
the connector. The connector may be destroyed.
15.5 (.61)
3 (.12)
46 (1.81)
DIN RAIL
35 mm wide
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: R1M-A1
SYSTEM CONFIGURATION EXAMPLES
RS-485
TC/DC Inputs
(model: R1M-GH)
Contact Inputs
(model: R1M-A1)
Contact Outputs
(model: R1M-D1)
When the cable distance between the PC and the R1Ms is long,
insert an RS-232-C/RS-485 Converter for isolation.
RS-232-C
RS-232-C/RS-485
Converter
(model: R2K-1)
Specifications are subject to change without notice.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

R1M-A1
P. 1 / 4EM-5661 Rev.4
CONTACT INPUT MODULE
(32 points) MODEL R1M-A1
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
This product is for use in general industrial environments,
therefore may not be suitable for applications which require
higher level of safety (e.g. safety or accident prevention sys-
tems) or of reliability (e.g. vehicle control or combustion con-
trol systems).
For safety, installation and maintenance of this product
must be conducted by qualified personnel.
■ PACKAGE INCLUDES:
Remote I/O module ....................................................... (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
For detailed information on Modbus supported functions,
refer to Modbus Protocol Reference Guide (EM-5650).
The R1M is programmable using the PC configurator soft-
ware. For detailed information on the PC configuration,
refer to the R1CON instruction manual. The R1CON PC
Configurator Software is downloadable at M-System’s web
site: http://www.m-system.co.jp.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for use in a Pollution Degree
2 environment and in Installation Category II, with the
maximum operating voltage 300V.
Basic insulation is maintained between the signal input
and RS-232C/RS-485. Prior to installation, check that the
insulation class of this unit satisfies the system require-
ments.
• Altitude up to 2000 meters
•The equipment must be mounted inside a panel.
• Insert noise filters. Okaya Electric Industries Model SUP-
E1H or equivalent for the power source connected to the
unit, and TDK Model ZCAT3035-1330 or equivalent for
the RS-232C cable are recommended.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■ POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 10VA
24V DC rating: 24V ±10%, approx. 7W
■ GENERAL PRECAUTIONS
• Before you remove the module, turn off the power supply
and input signal for safety.
■ ENVIRONMENT
• Indoor use
•When heavy dust or metal particles are present in the air,
install the module inside proper housing with sufficient
ventilation.
• Do not install the module where it is subjected to continu-
ous vibration. Do not apply physical impact to the mod-
ule.
• Environmental temperature must be within -5 to +60°C
(23 to 140°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■ WIRING
• Wrong connection may damage the module.
• Do not connect cables to moving parts or pull them tight-
ly.
• Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The module is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required
for satisfying complete performance described in the data
sheet.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

R1M-A1
P. 2 / 4EM-5661 Rev.4
COMPONENT IDENTIFICATION
■ REAR VIEW
RS-485
Connector Address Setting
Rotary SW Configurator
Jack
Specifications Marking
Power Terminals RS-232C
9-pin Connector RUN Indicator
LED
DIN Rail Adaptor
DIN Rail
35mm wide
INSTALLATION
■ DIN RAIL MOUNTING
Set the body so that its DIN rail
adaptor is at the bottom. Pull
down the DIN rail adaptor.
Position the upper hook at the
rear side on the DIN rail and
push in the lower. Push back the
DIN rail adaptor.
■ WALL MOUNTING
Set the body so that its DIN rail
adaptor is at the bottom. Pull
down the DIN rail adaptor.
Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the module referring to the connection diagram.
RS-232C
T3
T4
T2
T1
T7
T6
T5
Term.
Resist.
Output
Circuit
When the device is located at the end of a transmission line via twisted-pair cable,
(when there is no cross-wiring), close across the terminal T2 –T3 with the attached
jumper pin (or with a leadwire).
When the device is not at the end, remove the jumper pin.
*
Power
Circuit
+
–
Shielded Twisted-pair Cable
To Other
I/O Modules
Jumper*
FG
U (+)
V (–) POWER
D-SUB CONNECTOR
9
8
7
6
5
4
3
2
1
10
12
11
13
15
14
16
17
18
20
19
21
22
23
24
25
27
26
28
29
30
31
32
33
35
34
36
ch.1
ch.2
ch.3
ch.4
ch.5
ch.6
ch.7
ch.8
COM (–)
ch.9
ch.10
ch.11
ch.12
ch.13
ch.14
ch.15
ch.16
COM (–)
ch.17
ch.18
ch.19
ch.20
ch.21
ch.22
ch.23
ch.24
COM (–)
ch.25
ch.26
ch.27
ch.28
ch.29
ch.30
ch.31
Count Reset Input
ch.32
COM (–)
Input Circuit
Input Circuit
A9
A8
A7
A6
A5
A4
A3
A2
A1
A10
A12
A11
A13
A15
A14
A16
B1
:
B16
ch.1
ch.2
ch.3
ch.4
ch.5
ch.6
ch.7
ch.8
ch.9
ch.10
ch.11
ch.12
ch.13
ch.14
ch.15
ch.16
COM (–)
A9
A8
A7
A6
A5
A4
A3
A2
A1
A10
A12
A11
A13
A15
A14
A16
ch.17
CN1
ch.18
ch.19
ch.20
ch.21
ch.22
ch.23
ch.24
ch.25
ch.26
ch.27
ch.28
ch.29
ch.30
ch.31
Count Reset Input
ch.32
■ FCN TYPE CONNECTOR ■ M3 SCREW TERMINALS
CN2
B1
:
B16
COM (–)
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

R1M-A1
P. 3 / 4EM-5661 Rev.4
ABBR. PINNO. EXPLANATIONOFFUNCTION
BA (SD) 2 Transmitted Data
BB (RD) 3 Received Data
AB (SG) 5 Signal Common
CB (CS) 7 Clear to Send
CA (RS) 8 Request to Send
1 Not Used.
4 DO NOT connect. Connecting may
6 cause malfunctions.
9
1 5
6 9
■ RS-232C INTERFACE
MODBUS WIRING CONNECTION
R1M
T1
T2
T3
T4
R1M
T1
T2
T3
T4
T1
T2
T3
T4
R1M
CONNECTOR
RS-232C
RS-485
*1*1
*1. Internal terminating resistor is used when the device is at the end of a transmission line.
*2. Install shielded cables to all sections and ground them at single point.
*2
FG
RS-485
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input: Check supply voltage.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

R1M-A1
EXTERNAL DIMENSIONS unit: mm (inch)
123456789
10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
T1 T2 T3 T4 T5 T6 T7
104 (4.09)
10 (.39)
105 (4.13)
14 (.55)
163 (6.42)
36–M3 I/O TERMINALS
165 (6.50)
175 (6.89)
3–5 (.20) dia.
MTG HOLES
FOR WALL MOUNT.
6.2 (.24)
15.5 (.61)
[6 (.24)]
40 (1.57)
3 (.12)
46 (1.81)
DIN RAIL
35 mm wide
■ SCREW TERMINALS
■ FCN TYPE CONNECTOR
T1 T2 T3 T4 T5 T6 T7
104 (4.09)
10 (.39)
105 (4.13)
14 (.55)
163 (6.42)
165 (6.50)
175 (6.89)
3–5 (.20) dia.
MTG HOLES
FOR WALL MOUNT.
FCN TYPE I/O CONNECTOR [6 (.24)]
40 (1.57)
40 (1.57)
Connector Pin
Assignment
A1 B1
A16 B16
CN1 CN2
See Caution below
Caution: DO NOT APPLY EXCESSIVE FORCE onto
the connector. The connector may be destroyed.
15.5 (.61)
3 (.12)
46 (1.81)
DIN RAIL
35 mm wide
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG
This manual suits for next models
1
Table of contents