MG R7I4DML3-DC32A User manual

EM-8008-C Rev.1 P. 1 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Discrete output module.......................................................(1)
Surface mounter slider .......................................................(2)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures* to ensure the CE con-
formity.
* For example, installation of noise filters and clamp fil-
ters for the power source, input and output connected
to the unit, etc.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, ≤ 75 mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and output signal for safety.
• Before you remove the connector or mount it, make sure
to turn off the power supply and output signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
MECHATROLINK I/O MODULE
(NPN transistor output, 32 points, e-CON connector,
MECHATROLINK- III use)
MODEL
R7I4DML3-DC32A

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 2 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
Terminals for
Power Supply &
Sencor Excitation
Station Address Setting Rotary SW
Discrete Output Status Indicator LEDs
Status Indicator LEDs
SA1 X10
SA2 X1
PWR
ERR
CON
LNK1
LNK2
LNK1
CNFG.
LNK2
X0 X1 X2 X3 X4 X5 X6 X7 XFXEXDXCXBXAX9X8 X10X11 X12X13 X14X15 X16X17 X1FX1EX1DX1CX1BX1AX19X18
Connector for
MECHATROLINK
Communication
PC Configurator Jack
Output Connector
■STATUS INDICATOR LED
ID COLOR FUNCTION
PWR Green Turns on when the internal power is sup-
plied normally.
ERR Red Turns on at MECHATROLINK-III com-
munication error
CON Green Turns on at MECHATROLINK-III con-
nection is established
LNK1 Green Turns on at MECHATROLINK-III LNK1
is established
LNK2 Green Turns on at MECHATROLINK-III LNK2
is established
■DISCRETE OUTPUT STATUS INDICATOR LED
LED green indicators shows the output signal status.
ON : LED ON
OFF : LED OFF
■STATION ADDRESS
Station Address is selected between 03H and EFH in hexa-
decimal.
The SA1 switch determines the MSD, while the SA2 switch
does the LSD of the address.
(Factory setting: 03H)
Station Address Setting SA1 (MSD) (x10)
Station Address Setting SA2 (LSD) (x1)
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 3 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
1
4
1
4
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y8 Y9 YA YB YC YD YE YF
Y10 Y11 Y12Y13 Y14 Y15 Y16 Y17 Y18 Y19 Y1A Y1B Y1C Y1D Y1E Y1F
• e-CON connector
Recommended cable connector: 37104-( )-000FL (3M Company)
(The cable connector is not included in the package.
Specify wire size instead of ( ); refer to the specifications of the product.)
PIN
No. ID FUNCTION PIN
No. ID FUNCTION
Y101 +24V 24V DC Y181 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y10 Output 16 4Y18 Output 24
Y111 +24V 24V DC Y191 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y11 Output 17 4Y19 Output 25
Y121 +24V 24V DC Y1A 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y12 Output 18 4 Y1A Output 26
Y131 +24V 24V DC Y1B 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y13 Output 19 4 Y1B Output 27
Y141 +24V 24V DC Y1C 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y14 Output 20 4 Y1C Output 28
Y151 +24V 24V DC Y1D 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y15 Output 21 4 Y1D Output 29
Y161 +24V 24V DC Y1E 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y16 Output 22 4 Y1E Output 30
Y171 +24V 24V DC Y1F 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y17 Output 23 4 Y1F Output 31
PIN
No. ID FUNCTION PIN
No. ID FUNCTION
Y0 1 +24V 24V DC Y8 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y0 Output 04Y8 Output 8
Y1 1 +24V 24V DC Y9 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y1 Output 14Y9 Output 9
Y2 1 +24V 24V DC YA 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y2 Output 24YA Output 10
Y3 1 +24V 24V DC YB 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y3 Output 34YB Output 11
Y4 1 +24V 24V DC YC 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y4 Output 44YC Output 12
Y5 1 +24V 24V DC YD 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y5 Output 54YD Output 13
Y6 1 +24V 24V DC YE 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y6 Output 64YE Output 14
Y7 1 +24V 24V DC YF 1 +24V 24V DC
2NCUnused 2NCUnused
3NCUnused 3NCUnused
4Y7 Output 74YF Output 15

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 4 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■POWER SUPPLY, SENSOR EXCITATION
Cable connector: TFMC1,5 / 5–STF–3,5
(Phoenix Contact) (included in the package)
Applicable wire size:
0.2 − 1.5 mm2;stripped length 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm2(Phoenix Contact)
• AI0,34−10TQ 0.34 mm2(Phoenix Contact)
• AI0,5−10WH 0.5 mm2(Phoenix Contact)
• AI0,75−10GY 0.75 mm2(Phoenix Contact)
• A1−10 1.0 mm2(Phoenix Contact)
• A1,5−10 1.5 mm2(Phoenix Contact)
1
2
3
4
5
1. PWR+
2. PWR–
3. FE
4. SNSR.EXC+
5. SNSR.EXC–
Power Supply
Power Supply
Functional earth
Sensor excitation
Sensor excitation
Note: The numbers marked on the connector have no relationship to the pin number of the unit.
Wire according to the instruction manual of the unit.
PC CONFIGURATOR
The following parameter items can be configured with the PC configurator software (model: R7CFG).
Refer to the users manual of the software for detailed operations.
■CHANNEL INDIVIDUAL SETTING
PARAMETER SETTING RANGE DEFAULT
Unused setting (output only) CH enabled
CH disabled
CH enabled
■CHANNEL BATCH SETTING
PARAMETER SETTING RANGE DEFAULT
Output at communication error Output hold
Output clear
Output hold

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 5 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MOUNTING INSTRUCTIONS
■DIN RAIL MOUNTING (PARALLEL)
• Mounting
1) Set the upper hook at the rear side of the unit on the DIN
rail.
2) Push in the lower.
1
2
• Dismounting
1) Push down the DIN rail mounter slider with tip of a mi-
nus screwdriver.
2) Pull the lower of the unit.
3) Remove the upper hook of the unit from the DIN rail.
3
1
2
■SURFACE MOUNTING
1) Insert the two DIN rail mounter sliders until it clicks
once, as shown below.
1
1
2) Mount the unit with M4 screws referring the External
Dimensions. (Torque: 1.4 N∙m)
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm [inch]
41 [1.61]
165 [6.50]
172 [2.83]
186 [7.32]
DIN rail
(35mm wide)
50 [1.97]
3.5 [0.14]5 [0.20]
(4 [.16])
2-4.3 [.17] dia
4 [.16] deep

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 6 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
SNSR.EXC+
SNSR.EXC–
FE
PWR–
PWR+
1
2
4
5
3
POWER SUPPLY (IN)
SENCOR EXCITATION
(IN)
SNSR.EXC+
SNSR.EXC–
FE
PWR–
PWR+
1
2
4
5
3
POWER SUPPLY (OUT)
SENCOR EXCITATION
(OUT)
1
2
4
3OUTPUT Y0
Y0
NC
NC
+
24V
1
2
4
3OUTPUT Y1F
YF
NC
NC
+2
4V
•
•
•
•
•
MECHATROLINK-III
CONNECTOR
MECHATROLINK-III
CONNECTOR
*1
*1
*1. The network cable can be connected to either one.
USB Connector
CONFIGURATION
CONNECTOR
MOUNTING REQUIREMENTS unit: mm [inch]
175 (6.89)
2−M4

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 7 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MECHATROLINK-III COMMUNICATION
Transmission cycle: 125 µsec., 250 µsec., 500 µsec., 1 – 64 msec. (with 1 msec. increments)
Communication cycle: 125 µsec. through 64 msec.
Applicable prole: Standard I/O profile (cyclic communication)
Event-driven communication acquiring ID profile (event-driven communication)
Transmission bytes: 16 bytes
Station address: 03H through EFH (set with rotary switches)
Cyclic communication: Available
Event-driven communication: Available
Slave monitoring: None
MECHATROLINK-III RELATED COMMANDS
Commands available with this unit are the following.
PROFILE COMMAND CODE FUNCTION
Common command NOP 00H No operation command
ID_RD 03H Read ID command
CONFIG 04H Setup device command
ALM_RD 05H Read alarm or warning command
ALM_CLR 06H Clear alarm or warning command
CONNECT 0EH Establish connection command
DISCONNECT 0FH Release connection command
Standard I/O profile DATA_RWA 20H Transmit I/O data
• NOP (00H)
Does nothing except sending back current status
BYTE COMMAND RESPONSE REMARKS
0 NOP (00H) NOP (00H) No operation command
1 00H 00H Not used
2 CMD_CTRL CMD_STAT Refer to CMD_CTRL/CMD_STAT.
3
≥ 4 00H 00H Reserve
• ID_RD (03H)
Reads the product ID.
BYTE COMMAND RESPONSE REMARKS
0 ID_RD (03H) ID_RD (03H) Read ID command
1 00H 00H Not used
2 CMD_CTRL CMD_STAT Refer to CMD_CTRL/CMD_STAT.
3
4 ID_CODE ID_CODE Refer to ID_CODE
5 OFFSET OFFSET OFFSET: designates the place to read data
6 SIZE SIZE SIZE: specify the size of data to read
7
≥ 8 00H ID Product’s ID
• CONFIG (04H)
No parameter to set for this unit. Immediately response with completion.
BYTE COMMAND RESPONSE REMARKS
0 CONFIG (04H) CONFIG (04H) Setup device command
1 00H 00H Not used
2 CMD_CTRL CMD_STAT Refer to CMD_CTRL/CMD_STAT.
3
4 00H 00H Recalculation of parameters and set up. Other than 00H is
not supported.
≥ 5 00H 00H Reserve

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 8 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
• ALM_RD (05H)
Reads alarm or warning
BYTE COMMAND RESPONSE REMARKS
0 ALM_RD (05H) ALM_RD (05H) Read alarm or warning command
1 00H 00H Not used
2 CMD_CTRL CMD_STAT Refer to CMD_CTRL/CMD_STAT.
3
4 0000H 0000H Read current alarm or warning.
12 points max. (2 bytes in 8th to 31st byte)
Other than 0000H is not available.
5
6 0000H 0000H 0
7
≥ 8 00H 00H 0
• ALM_CLR (06H)
Clears alarm or warning
BYTE COMMAND RESPONSE REMARKS
0 ALM_CLR (06H) ALM_CLR (06H) Clear alarm or warning command
1 00H 00H Not used
2 CMD_CTRL CMD_STAT Refer to CMD_CTRL/CMD_STAT.
3
4 0000H 0000H Clear current alarm or warning. Other than 0000H is not
available.
5
≥ 6 00H 00H Reserve
• CONNECT (0EH)
Starts communication with master station.
BYTE COMMAND RESPONSE REMARKS
0 CONNECT (0EH) CONNECT (0EH) Establish connection command
1 00H 00H Not used
2 CMD_CTRL CMD_STAT Refer to CMD_CTRL/CMD_STAT.
3
4 30H 30H MECHATROLINK application layer: 30H
5 00H 00H Communication mode: Asynchronous, single transmission,
subcommand disabled
6 COM_TIME COM_TIME Communication cycle: Multiple of transmission cycle.
E.g. Transmission cycle: 0.5 msec., communication cycle: 2
msec. Set 4 (=2/0.5)
7 30H or 01H 30H or 01H Profile type
30H: Standard I/O profile
01H: Event-driven communication acquiring ID profile
≥ 8 00H 00H Reserve
• DISCONNECT (0FH)
Stops communication with master station.
BYTE COMMAND RESPONSE REMARKS
0 DISCONNECT (0FH) DISCONNECT (0FH) Release connection command
≥ 1 00H 00H Reserve

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 9 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
• DATA_RWA (20H)
Transmits I/O data to master station. Data allocation is following.
Data size is 16 bytes.
BYTE COMMAND RESPONSE REMARKS
0 DATA_RWA (20H) DATA_RWA (20H) Transmit I/O data
1 00H 00H Not used
2 CMD_CTRL CMD_STAT Refer to CMD_CTRL/CMD_STAT.
3
4 CH0 OUT LO CH0 IN LO CHx OUT: Output data: See ‘Output Data’ of ‘I/O DATA’
CHx IN: Input data: See ‘Input Data’ of ‘I/O DATA’
5 CH0 OUT HI CH0 IN HI
6 CH1 OUT LO CH1 IN LO
7 CH1 OUT HI CH1 IN HI
8 CH2 OUT LO CH2 IN LO
9 CH2 OUT HI CH2 IN HI
10 CH3 OUT LO CH3 IN LO
11 CH3 OUT HI CH3 IN HI
12 00H 00H Not used
13 00H 00H Not used
14 00H 00H Not used
15 00H 00H Not used
[ I/O DATA ]
• Input data
Input data to be sent from the slave to the master are set in the response.
CH0 IN LO CH0 data low 8 bits Bit 0 through 7 of the data, which reads back the output data, are set
CH0 IN HI CH0 data high 8 bits Bit 8 through 15 of the data, which reads back the output data, are set
CH1 IN LO CH1 data low 8 bits Bit 16 through 23 of the data, which reads back the output data, are set
CH1 IN HI CH1 data high 8 bits Bit 24 through 31 of the data, which reads back the output data, are set
CH2 IN LO CH2 data low 8 bits Not used
CH2 IN HI CH2 data high 8 bits Not used
CH3 IN LO CH3 data low 8 bits Not used
CH3 IN HI CH3 data high 8 bits Not used
• Output data
Output data to be sent from the master to the slave are set in the command. Unused with input module.
CH0 OUT LO CH0 data low 8 bits Bit 0 through 7 of output data are set
CH0 OUT HI CH0 data high 8 bits Bit 8 through 15 of output data are set
CH1 OUT LO CH1 data low 8 bits Bit 16 through 23 of output data are set
CH1 OUT HI CH1 data high 8 bits Bit 24 through 31 of output data are set
CH2 OUT LO CH2 data low 8 bits Not used
CH2 OUT HI CH2 data high 8 bits Not used
CH3 OUT LO CH3 data low 8 bits Not used
CH3 OUT HI CH3 data high 8 bits Not used

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 10 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
CMD_CTRL
CMD_CTRL command area is following.
BIT FUNCTION REMARKS
0 – 2 Reserve Not used
3 ALM_CLR 0: Clear alarm/warning disabled
1: Clear alarm/warning triggered
4 – 5 Reserve Not used
6 – 7 CMD_ID Not used in the standard I/O command profile
8 – 15 Reserve Not used
CMD_STAT
CMD_STAT response area is following.
BIT FUNCTION REMARKS
0 D_ALM Not used
1 D_WAR Not used
2 CMDRDY 1: Command reception enabled
0: Other
3 ALM_CLR_CMP 1: Completion of execution of ALM_CLR
0: Other
ALM_CLR_CMP can be canceled by setting ‘0’ for ALM_CLR in CMD_CTRL command
area.
4 – 5 Reserve Not used
6 – 7 RCMD_ID Not used in the standard I/O command profile
8 – 11 CMD_ALM Warning 0: Normal, 1: Invalid data
Alarm 8: Unsupported command received, 9: Invalid data, A: Command execu-
tion condition error, B: Subcommand combination error, C: Phase error
12 – 15 COMM_ALM Warning 0: Normal, 1: FCS error, 2: Command data not received, 3: Synchronous
frame not received
Alarm 8: FCS error, 9: Command data not received, A: Synchronous frame not
received, B: Synchronization time interval error, C: WDT error

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 11 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
ID_CODE
ID_CODE is following.
ID_CODE NAME SIZE
(BYTES) SUPPORT VALUE
(HEXADECIMAL) REMARKS
01H Vendor ID Code 4 Yes 0x00000021 M-SYSTEM CO., LTD.
02H Device Code 4 Yes 0x00000403 R7I4DML3-DC32A-B
03H Device Version 4Ye s Firmware version E.g. 1.00 -> 0x0064
04H Device Definition File version 4 Yes 0x00001000
05H Extended Address Setting 4Yes 0x00000001
06H Serial No. 32 Yes Unit serial
number
E.g. AB123456 -> 0x32314241
0x36353433
0x00000000
0x00000000
0x00000000
0x00000000
0x00000000
0x00000000
10H Profile Type 1 4Yes 0x00000030 Standard I/O profile
11H Profile Version 1 4Ye s 0x00000100
12H Profile Type 2 4Yes 0x000000FF Indicates the unit does not support
13H Profile Version 2 4Ye s 0x00000000
14H Profile Type 3 4Yes 0x000000FF Indicates the unit does not support
15H Profile Version 3 4Ye s 0x00000000
16H Min. Transmission Cycle 4Yes 0x000030D4 125 µsec.
17H Max. Transmission Cycle 4Yes 0x0061A800 64 msec.
18H Increments of Transmission
Cycle
4Yes 0x00000001 Available to 31.25, 62.5, 125, 250, 500 [µsec.]
& 1 – 64 [msec.] (1 msec. increments)
19H Min. Communication Cycle 4 Yes 0x000030D4 125 µsec.
1AH Max. Communication Cycle 4 Yes 0x0061A800 64 msec.
1BH Transmission Bytes 4 Yes 0x00000002 16 Bytes
1CH Transmission Bytes
(Current Setting)
4Yes 0x00000002 16 Bytes
1DH Profile Type
(Current Selection)
4Yes 0x00000001 /
0x00000030
Event-driven communication / Cyclic com-
munication
20H Supported Communication
Mode
4Yes 0x00000003 Event-driven communication / Cyclic com-
munication
21H MAC Address 4 No ----
30H List of Supported Main Com-
mands
32 Yes 0x0000C079
0x00000001
0x00000000
0x00000000
0x00000000
0x00000000
0x00000000
0x00000000
ALM_CLR, ALM_RD, CONFIG, ID_RD,
NOP, DISCONNECT, CONNECT,
DATA_RWA
38H List of Supported Sub Com-
mands
32 No ----
40H List of Common Parameters 32 No ----
80H Main Device Name 32 Ye s 0x34463752
0x334C4D48
0x442D442D
0x32334341
0x00000041
0x00000000
0x00000000
0x00000000
“R7I4DML3-DC32A-B”
90H Sub Device 1 Name 4 No ----
98H Sub Device 1 Version 32 No ----
A0H Sub Device 2 Name 4 No ----
A8H Sub Device 2 Version 32 No ----
B0H Sub Device 3 Name 4 No ----
B8H Sub Device 3 Version 32 No ----

R7I4DML3-DC32A
EM-8008-C Rev.1 P. 12 / 12
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
I/O DATA DESCRIPTION
■DISCRETE OUTPUT MODULE
015
Output 0
Output 1
Output 2
Output 3
Output 15
0: OFF 1: ON
Output 7
Output 8
Output 16
Output 17
Output 18
Output 19
Output 31
Output 23
Output 24
■DISCRETE OUTPUT
■STATUS
0
15
Output 0 Output 16 (Overcurrent/overheat; disconnection)
Output 1 Output 17 (Overcurrent/overheat; disconnection)
Output 2 Output 18 (Overcurrent/overheat; disconnection)
Output 3 Output 19 (Overcurrent/overheat; disconnection)
Output 7 Output 23 (Overcurrent/overheat; disconnection)
Output 8 Output 24 (Overcurrent/overheat; disconnection)
Output 4 Output 20 (Overcurrent/overheat; disconnection)
Output 5 Output 21 (Overcurrent/overheat; disconnection)
Output 6 Output 22 (Overcurrent/overheat; disconnection)
Output 11 Output 27 (Overcurrent/overheat; disconnection)
Output 12 Output 28 (Overcurrent/overheat; disconnection)
Output 9 Output 25 (Overcurrent/overheat; disconnection)
Output 10 Output 26 (Overcurrent/overheat; disconnection)
Output 14 Output 30 (Overcurrent/overheat; disconnection)
Output 15 Output 31 (Overcurrent/overheat; disconnection)
Output 13 Output 29 (Overcurrent/overheat; disconnection)
0 : Normal
1 : Detected the overcurrent/overheat and disconnection
Note: Status is disabled with option code /D1 (without wire breakdown detection).
When overcurrent or overheat is detected on each channel of discrete output while the output is ON, the status bit correspond-
ing to the output turns “1” and is latched*. Then the discrete output is also latched to OFF.
To reset the latched bit and discrete output, set this output to OFF from the host PC/PLC or turn off and on the power supply
to the unit.
When disconnection (open load) is detected while output is OFF, the corresponding status bit turns “1” but is not latched.
* The status bit turns “0” if the load is opened in the state overcurrent or overheat is detected. However, the discrete output of the
unit remains latched. Be sure to remove the cause of error and reset the latched output by setting the output to OFF or turning
off/on the power supply.
Table of contents
Other MG I/O System manuals
Popular I/O System manuals by other brands

Allen-Bradley
Allen-Bradley Compact 5000 Series user manual

ICP DAS USA
ICP DAS USA P8R8-DIO quick start guide

Allen-Bradley
Allen-Bradley ArmorBlock-LP 1792-IB16LP installation instructions

Extron electronics
Extron electronics TLP VIM user guide

National Instruments
National Instruments NI PXI-665 Series CALIBRATION PROCEDURE

ETAS
ETAS ES930.1 user guide

Measurement Computing
Measurement Computing USB-3103 user guide

SeaLevel
SeaLevel SeaRAQ 6510 user manual

EverFocus
EverFocus External I/O Box quick start guide

WAGO
WAGO I/O-SYSTEM 750 manual

Advantech
Advantech B+B SmartWorx Zlinx ZZ24D-NA-SR quick start guide

Future Desion Controls
Future Desion Controls FDC-VR18 quick start guide