Operational Instruction Manual
Single-Phase
Digital Combined Meter

Please read through the manual before installment and operation
Chapter 1. Technical parameters
--1
Single-Phase Digital Combined Meter
1.1 Measuring range
1.1.1 Voltage: Direct measurement:AC 0~600V
Accessory device:AC 0~9999KV(PT */ 100V)
1.1.2 Current:Direct measurement:AC 0~10A
Accessory device:AC 0~9999A(CT */ 5A)
1.1.3 Ffrequency:45~65Hz
1.1.4 Active Power:0~9999KW,Reacitve Power 0~9999KVar
1.1.5 Power Factor:0 000C~0 500C~1 000~0 000L~0 500L
1.2 Accuracy rating :±0 5 FS±1 digit
1.3 Sampling rate: about 1 times/s
1.4 Measuring display mode: RMS measurement, four-digit LED nixietube display
1.5 Display resolution: Max. display resolution 0.001A,0.1V,0.01Hz
1.6 Input circuit consumption: current<0.5VA,voltage<1VA
1.7 Auxiliary power supply: AC 220V,50/60Hz Can customize other values
1.8 Auxiliary supply consumption:< 3VA
1.9 Overflow indication: Displaying character”HHHH”
1.10 Alarm Output: Higher and lower limit alarm output by two groups of reply, contact
rating is AC250V/2A DC30V/2A
1.11 Transmitting output: can be set freely as DC 0~10mA 0~20mA or 4~20mA,
accuracy rating is ±0.5 % FS,electrical isolation between the signal input and
auxiliary power supply
1.12 Transmitting output load resistance 500
1.13 Communication interface RS485 serial communication applying MODBUS_RTU
communication protocol
1.14 Operational environment: free of corrosive gas with temperature of -10~50°C ,
and humidity 85%RH
:
.....
.
、
:
:
:
、
:,
()
≤Ω
Note: communication output, alarm output, transmitting output are additional functions.Note: communication output, alarm output, transmitting output are additional functions.

Chapter 2. Installment and connection
--2
A
V
Hz
SET
A
V
SET
Hz
120×120Square
96×96Square
80×80Square
72×72Square
48×48Square
120 120
96 96
80 80
7272
4848
110 110
90 90
74 74
66 66
44 44
83
83
83
83
73
112112
92 92
76 76
68 68
45 45
21. Shape and cutout hole dimension(unit mm):
Shape
Panel dimension Case dimension
Cutout hole dimension
WHW WHHD
2.2 Method of installation
Choose the corresponding hole cutout dimension from the table above , make
a hole in the installation screen, insert the instruments into the hole, place the
four clamping pieces into the clamping holder and push and tighten them by hand.
2.3 Wiring instructions
2.3.1 Terminal arrangement and function declaration of instrument(please accord
to the one of instrument case)
Auxiliary power supply (POWER) AC 220V,50/60Hz(Can customize other values)
Electrical quantity signal input(INPUT) : U* andI * represent live wire terminal
of AC voltage input signal and inlet wire terminal of AC current input signal.When
the voltage is higher than the rated input voltage of the product,you should consider
of using PT and installing fuse of 1A at the voltage input port; while the current is
higher than rated input current of the product, you should consider of using the
exterior CT
:

--3
Chapter 3. Programming and usage
3.1 Panel description
SET
Voltage display screen
Current display screen
Other Parameters
display screen
Set key
Shift key
Up key
Down key
3.2 Key function
Set key Press this key 2s to enter the programmable mode Under the
programmable mode it is used to save and return to the menu
Shift key Under the programmable mode it is used to left shift the cursor
one digit,and quit the programmable mode and return to the measuring
value display interface.
Down key: under the programmable mode,it is used for degression of parameter
value or enter the next menu.
Up key:under the programmable mode,it is used for progressive increase of
parameter value or enter the previous menu.
:
,.
:,
;
SET
2.3.2 Typical connection
L
N
UU*II*
L
N
UU*II*
L
N
UU*II*
Voltage≤600V,input directly
Current≤5A,input directly
Voltage≤600V,input directly
Current 5A,input via CT
>
Voltage 600V,input via PT>
Current 5A,input via CT>

--4
(Display value)
SET
SET SET
SET
SET SET
SET
SET SET
SET
SET
SET
SET
SET
SET
3.4 Menu framework
Press
2S
(
)
multiplying power of voltage
transformer 1~9999:
(
:)
multiplying power of current
transformer 1~9999
(:)RS485 communication address 1~247
()Communication baud rate
(:
:, : , )
1st channel relay alarm fuction settings
OFF off AH high alarm AL: low alarm
(:.)1st channel relay alarm value setting 0 150 0~%
(:
:, , )
Analog quantity output fuction settings
OFF off 4 20:4 20mA 0 20 0 20mA-- -:-
(
)
Analog quantity output value settings,
20mA corresponds to the full range,
range: 0~150.0%, the default 100%
()1st relay alarm object selection
()Analog quantity output object selection
SET
Press When the parameters were modified

--5
3.5 Menu significations
Under the programmable mode, four menu setting items including of signal
input, communication, switching value output annlog quantity output.Signal
input code: ;communication code: ;switching value output code: ;
annlog quantity output: .
,
0001 0002 0003
0004
0001, 0002
0003, 0004
1 9999~
1 9999~
1 247~
1200, 2400
4800, 9600
OFF
AH
AL
0 150 0~.%
OFF
AH
AL
Menu Parameter Description
Signal input code: ;Communication code: ;
Switching value output code: ;
Annlog quantity output: .
0001 0002
0003
0004
Set multiplying power of voltage transformer:PT
(Primary value/second value of voltage transformer)
for example PT=10KV/100V=100:
Set multiplying power of current transformer:CT
(Primary value/second value of current transformer)
for example CT=300A/50A=60:
RS485 communication address 1~247:
Communication baud rate
1st channel relay alarm fuction settings
OFF off AH high alarm AL:low alarm
:
::,,
1st channel relay alarm value setting 0 150 0:.~%
1st channel relay alarm object selection
U:voltage I current F frequency
P:active power H:power Factor
:
,: , : ,
,
2nd channel relay alarm fuction settings
OFF off AH high alarm AL low alarm
:
::,,:
,, , ,UIFPH

0 150 0~.%
OFF
020
420
-
-
UIFPH,, , ,
0 150 0~.%
2nd channel relay alarm object selection
U:voltage I current F frequency
P:active power H:power Factor
:
,: , : ,
,
2nd channel relay alarm value setting 0 150 0:.~%
Analog quantity output fuction settings
OFF off 4 20:4 20mA 0 20 0 20mA
:
:, ,-- -:-
Analog quantity output value settings,
20mA corresponds to the full scale,
range: 0~150.0%, the default 100%
Analog quantity output object selection
U:voltage I current F frequency
P:active power H:power Factor
:
,: , : ,
,
,, , ,UIFPH
--6
3.6 Programming operation examples
The measuring range of instruments has been set as the same parameters
provided by users at the factory. Users should check if the input network, voltage/
current measuring range and transformer multiplying power are consistent with
the actual input again before use.
SET SET SET
SETSETSET
SET SET
SET
SET
SET
SET
Example 1 The factory default parameter is AC 5A( ) If the current transformer
is 100A 5A should modify the CT multiplying power as 20(100/5)
:CT 1
/
=;
,
Press
2S
Display
value
Display
value
Display
value

--7
Example 1 The factory default parameter is AC 5A( ) If the current transformer
is 1000A 5A should modify the CT multiplying power as 200(1000/5)
:CT 1
/
=;
,
SET SET SET
SETSETSET
SET SET
SET
SET
SET
SET
Display
value
Display
value
Display
value Press
2S
Chapter 4.Cautions
4.1 Please confirm if the power supply, input signal and each terminal wiring of
the meter are correct and reliable before applying the power.
4.2 The instrument must be preheated for 15 minutes to guarantee the precision
of measurement.
4.3 The instrument should not be rapped, knocked and vibrate excessively and
its using environment should meet the technical requirements.
4.4 The meter has been calibrated according to the measuring range required
by the customer upon order. The user should check once again if the measuring
range of the meter is fit with the specifications of the transformer and set the
measuring range again if not.
Chapter 5. Packing and Storage
The instrument and accessories with packing should keep storage conditions
cool and dry and free of wet and corrosive gas with temperature not more than
70°Cand not less than -40°C,and relative humidity≤85%RH.