Model: SF-104S-2 Digital Temperature Controller
Features of Function
Super-thin,water-proof, with outer high-voltage parts,easy&convenient to fix the compressor of one HP.
Temperature Display/ Temperature Control/Evap.Fan Control/Value Storing/ Self Testing
Specifications
1. Output of the outside sealed transformer:AC12V(one transformer matched with one temp. controller)
2. Temperature sensor: NTC, 2m(L)
3. Range of temperature displayed :-45~150℃Accuracy:±1℃
4. Range of set temperature: -45~99℃Factory default :4℃
5. Dimension:77(Length)×35(Width)×30(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
6. Temperature of the operating environment:-10~60℃
Relative Humidity:20%~90%(Non-condensing)
7. Relay output contact capacity:
Compressor : N.O. 30A/250VAC
Evap.Fan : N.O.30A/250VAC
Front Panel Operation
1. Set temperature(compressor stop temperature) adjustment:
Press “SET”button, the set temperature is displayed.
Press “▲”or“▼”button to modify and store the displayed value. Press “SET”button to exit the adjustment
and display the cold room temperature.
If no more button is pressed within 6 seconds, the cold room temperature will be displayed.
(Set temperature adjustment range: parameter E1~E2)
2. Refrigeration LED: During refrigeration, the LED is on; When the cold room temp. is constant, the LED is off;
During the delay start, the LED flashes.
3. Defrost LED: during defrosting , the LED is on; When the cold-room temp. is constant, the LED if off; During
the delay start, the LED flashes.
4. Manually start / stop defrost: pressing “SET”& “Defrost”buttons simultaneously for 6 seconds can start or
stop defrost.
5. Parameter setup
Press “SET”button and hold for 6 seconds to enter the parameter setup mode while E1 flashes.
Press again “SET”button to select sequentially from the parameters : E2,E3,E4,E5,E1.
Press “▲”or“▼”button, the value of parameter will be displayed and can be modified and stored.
If no more button is pressed within 6 seconds, it will return to normal operation mode.