Fuji Electric Micro-Controller X Socket type User manual

Digital temperature controller
Micro-Controller X
Socket type
Operation Manual
Type: PXF4
INP-TN5A4117-E


1
Safety Instructions
Please read the safety instructions throughly before using the equipment. The safety instructions must be observed
by every user to prevent accidents. Failure to comply with the instructions contained in this manual may reduce the
safety of the equipment.
The safety instructions are classied into “Warning” and “Caution” according to the following interpretations:
Mishandling may lead to serious injury or death.
Mishandling may result in personal injury or damage to the
property.

2
WARNING
Installation and wiring
This equipment is intended to be used under the following conditions.
Ambient temperature -10 to 50°C
Operating humidity 90%RH or less (Non condensation)
Installation category II According to IEC 61010-1
Pollution degree 2
Recommended fuse 250 V AC, 0.1 A, T (Time-Lag) (100 to 240 V AC),
400 V DC/AC, 1 A, T (Time-Lag) (24 V DC/AC)
Usage environment Indoor use
For 24 V DC/AC power supply model, if the equipment is connected to the Safety Extra Low Voltage (SELV)
circuit, a basic insulation* must be provided between the SELV circuit and the power input terminals. Otherwise,
the power input terminals must be connect to Extra Low Voltage (ELV) circuit so as to prevent the electric shock.
About safety standard
Please observe the following instructions to meet the requirements of safety standard. Failure to observe these
instructions violates safety standards. (This product is not a safety equipment.)
Install a recommended fuse, which is specied in the instruction manual, between the external main power
(mains circuit) and this equipment.
If accessible Safety Extra Low Voltage (SELV) circuits are to be connected to Signal input terminal, SSR
Drive output terminal or Current output terminal, ensure to provide a basic insulation* between the SELV
circuits and these terminals (For example, use transformer which has a basic insulation* or higher degree of
insulation).
Whole this equipment must be mounted in an enclosure in order to prevent the electric shock and spread of
re.
Be sure to install an appropriate external protective circuit to prevent excessive temperature rise etc.
When performing wiring work, be sure to turn the power off and to wear protection gloves or safety glasses,
to prevent an electric shock.
Do not use this equipment for the measurement of circuits which falls under measurement categories II, III,
or IV.
Do not use this equipment for measurement of signals to which a voltage over
30 VRMS or over 60 V DC is applied.
* The basic insulation requires a clearance at least 1.5 mm and a creepage of at least 3.0 mm. If such
insulation is not provided, the UL61010 and EN61010 safety compliance may become invalid.

3
If the voltage exceeds 50 V DC (which is called as hazardous voltage), install a basic insulation between all
terminals and the ground, and supplementary insulation on the digital outputs.
Note that the insulation class for this equipment is as follows. Before installing, please conrm that the insulation
class for equipment meets usage requirements.
Basic insulation
(1500 V AC)
Functional
insulation (500 V AC)
No insulation
Power supply (100 to 240 V AC) Internal circuit
Power supply (24 V DC/AC)
Control output 1 (relay contact) Process value input
Alarm output 1 and 2 (relay contact) Control output 1 (SSR drive, current)
In case where damage or problems with this equipment may lead to serious accidents, install appropriate external
protective circuits.
As this equipment has no power switch or fuse, install them separately as needed.
If you install a fuse, be sure to place it between the main power switch and this equipment. (Main power switch:
double-pole breaker, fuse rating: 250V, 1A)
A power switch or a circuit breaker should be installed within the power supply facility.
A power switch or a circuit breaker should be properly installed within easy reach of an operator.
A power switch or a circuit breaker should be identied as the one for this product.
Electrical wiring must be made by the qualied personnel only and in accordance with your local and national
standards.
For power supply wiring, use a wire equivalent equal to 600 V vinyl insulated wire or higher level.
To prevent damage and failure of the equipment, provide the rated power voltage.
To prevent shock and equipment failure, do not turn the power ON until all wiring is complete.
Before turning on power, conrm that clearance space has been secured to prevent shock or re.
Do not touch the terminal while the machine is on. Doing so risks shock or equipment errors.
Never disassemble, convert, modify or repair this equipment. Doing so risks abnormal operation, shock or re.
If any failure occurs, please contact the manufacturer and return the product.
Output relay is the part has a limited life. When output relay contact comes to the end of its life, it might remain
on-state, or off-state. For safety, use a protective circuit outside.
The factory default setting of this equipment is as follows. Change the setting as necessary so as the equipment to
meet your application. Please note that the improper settings may result in overheat or unexpected damage. For
the details of operation, refer to this manual.
• Control output 1: heating control
• Alarm output 1 to 2 (optional): No function
Symbols on the instrument
: Read this instruction manual thoroughly before using the product, and usethe product safely.
Maintenance
When installing or removing the equipment, turn the power OFF. Otherwise, shock, operational errors or failures
may be caused.
Periodic maintenance is recommended for continuous and safe use of this equipment.
Some parts installed on this equipment have a limited life and/or may deteriorate with age.
The warranty period for this unit (including accessories) is three years after the date of manufacture, if the
product is used properly.

4
Caution
Installation
Please avoid installing in the following locations.
• Locations in which the ambient temperature falls outside the range of –10 to 50 °C when equipment is in use.
• Locations with rapid temperature changes, leading to dew condensation
• Locations with corrosive gases (especially sulde gas, ammonia, etc.) or ammable gases.
• Locations with vibration or shock directly. (Vibration and shock may cause output relay malfunction.)
• Locations in contact with water, oil, chemicals, steam or hot water. (If the equipment gets wet, there is a risk of
electric shock or re, so have it inspected by Fuji distributor.)
• Locations with high concentrations of atmospheric dust, salt or iron particles.
• Locations with large inductive interference, resulting in static electricity, magnetic elds or noise
• Locations in direct sunlight.
• Locations that build up heat from radiant heat sources, etc.
Recommended site conditions
• A place where the ambient humidity during operaion is between 45 to 85% RH.
About EMC standard
This equipment is a class A , for industrial locations, equipment. Do not use this equipment in domestic
establishment, such as residential areas, or it may cause radio interference. If you use this equipment in
domestic locations, take adequate measures on the outside of the equipment to reduce radio interference.
Under the requirement of EMC standard, the maximum length of external cable including a sensor to be
connected to this equipment is 30 m. Do not connect the sensor longer than 30 m.
Panel mounting
Insert the controller unit into the panel cutout from the front, and then put the mounting bracket from the rear.
The mounting bracket should be pushed in until the controller is securely xed to the panel. If there is a slight
gap remaining, gently tighten the two screws until the gap disappears. (Make sure not to over tighten the screws,
as doing so may result in the mounting bracket separating from the stopper.)
The front of this equipment is waterproof in compliance with NEMA-4X standards (IP66- equivalent). To effect
waterproof, the included packing is shall be attached between the controller and the panel according to the
guidelines below. (Incorrect attachment may cause the equipment to lose its waterproof capabilities.)
(1) As shown in Fig. 1, insert to the panel after attaching the packing to the equipment case.
(2) As shown in Fig. 2, tighten the screws of the mouthing bracket so that no gaps can remain between the
equipment face, the packing and the panels. Once nished, conrm that there are no changes in shape such
as displaced or improperly-tted packing, etc. as shown in Fig. 3
< Attachment on vertical surface (Horizontal attachment) >
Mounting
bracket
Packing
Case
(Good)
Case
Fig. 3
Case
(Bad)
Fig. 2Fig. 1
PanelPanel Screw
UnitUnit
Front
Packing
If the panel does not have enough strength, gaps may develop between the packing and the panel to lose
waterproong capabilities.
In order to aid heat dissipation, do not block the sides of the equipment.

5
Do not block the air vents on the top and bottom of the case.
Wiring
For thermocouple input, use the designated compensation lead; for RTD input, use wires with small lead wire
resistance and without any resistance difference among the three wires.
To avoid noise conductor effects, input signal wires should be separated from electric power lines or load lines.
Input signal wire and output signal wire should be separated each other. And both should be shield wire.
If there is a lot of noise from the power source, adding an insulation transducer and using a noise lter is
recommended. Always attach a noise lter to a panel that is grounded securely, and keep the wiring between
the noise lter output side and the measuring equipment power terminal wiring to a minimum length. Please do
not attach fuses and switches, etc. to the noise lter output wiring; otherwise the lter’s effectiveness will be
decreased.
Twisting the power wires is effective when connecting the wires. (The shorter the pitch of the twist, the more
effective the connection is against noise.)
Operation preparation time is required for the contact output when power is turned on. If using it as a signal to an
external interlock circuit, please couple it with a delayed relay.
Concerning the output relay, connecting the maximum rated load will shorten the product’s life; so please attach
an auxiliary relay. If the output operation frequency is high, selecting a SSR drive output type is recommended.
[Proportionate cycles] Relay output: 30 seconds or more, SSR drive output:
1 second or more
When inductive loads such as magnetic opening/closing equipment, etc. as relay output equipment are connected,
use of a surge absorber is recommended in order to protect the contacts against opening/closing surges and to
ensure long-term use.
Recommended specication for the surge absorber
Voltage Nominal varistor voltage
100V 240V
200V 470V
Attachment position: between the relay control output contacts.
Operation
The alarm function does not work properly when an error takes place unless the settings are made correctly.
Always verify its setting before operation.
If the input wiring breaks, the display will read “UUUU” or “LLLL”. When replacing the sensor, always turn the
power OFF.
Others
Please do not wipe the equipment with organic solvents such as alcohol or benzene, etc. If wiping is necessary,
use a neutral cleaning agent.
Do not use mobile phones near this equipment (within 50 cm). Otherwise a malfunction may result.
Trouble may occur if the equipment is used near a radio, TV, or wireless device.
This equipment should be treated as an industrial waste when it is disposed of.

6
Contents
Safety Instructions ................................................................................................................... 1
WARNING .................................................................................................................................................. 2
Installation and wiring ..............................................................................................................................2
Maintenance ............................................................................................................................................3
Caution ......................................................................................................................................................4
Installation............................................................................................................................................... 4
Panel mounting ........................................................................................................................................ 4
Wiring ..................................................................................................................................................... 5
Operation ................................................................................................................................................ 5
Others .....................................................................................................................................................5
For Proper Use ........................................................................................................................ 8
Model Specications................................................................................................................ 9
1 Part names and functions ................................................................................................ 10
1-1 Operation keys..................................................................................................................................... 10
1-2 Indicators ............................................................................................................................................. 11
1-3 Digital characters ................................................................................................................................. 12
2 Basic Operation ............................................................................................................... 13
2-1 Basic operation .................................................................................................................................... 13
2-2 Changing SV (Set value) ..................................................................................................................... 14
2-3 Parameters List.................................................................................................................................... 15
Operation Mode ..................................................................................................................................... 15
1st block parameter ................................................................................................................................ 15
2nd block parameter ...............................................................................................................................16
3rd block parameter ................................................................................................................................18
2-4 Temperature control functions ............................................................................................................. 19
2-5 Communication function ...................................................................................................................... 19
3 Parameter functions and setting procedure ..................................................................... 20
3-1 1st block parameter ............................................................................................................................. 20
[MANU] Manual mode selection (001) .................................................................................................... 20
[Stby] Standby setting (002) .................................................................................................................... 21
[PRoG] Ramp soak control (004) .............................................................................................................22
[LACH] Alarm latch cancel (005) ............................................................................................................ 24
[At] Auto-tuning (006) ............................................................................................................................ 25
[tM1] [tM2] Timer 1 display (007), Timer 2 display (008) .......................................................................... 27
[AL1] [A1-L] [A1-H] Alarm 1 settings (010, 011, 012) .............................................................................. 28
[AL2] [A2-L] [A2-H] Alarm 2 settings (013, 014, 015) .............................................................................. 28
[LoC] Key lock (019) ............................................................................................................................. 29

7
3-2 2nd block parameter ............................................................................................................................ 30
[P] Proportional band (030) ..................................................................................................................... 30
[i] Integral time (031) ............................................................................................................................. 30
[d] Derivative time (032) ........................................................................................................................ 30
[HyS] Hysteresis range for ON/OFF control (033) ..................................................................................... 32
[bAL] Output convergence value (036) .................................................................................................... 34
[AR] Anti-reset windup (037) ..................................................................................................................35
[CtRL] Control algorithm (038) ............................................................................................................... 36
[SLFb] PV (Process variable) stable range (039) ....................................................................................... 39
[oNoF] Hysteresis mode (040) ................................................................................................................. 40
[tC] Cycle time of control output 1 (041) .................................................................................................. 41
[P-N2] Input signal code (043) ................................................................................................................ 42
[P-SL] Lower limit of measuring range (044) ............................................................................................ 43
[P-SU] Upper limit of measuring range (045) ............................................................................................ 43
[P-dP] Decimal point position (046) .........................................................................................................45
[PVOF] PV offset (048) .......................................................................................................................... 46
[SVOF] SV shift (050) ............................................................................................................................ 47
[P-dF] Time constant of input lter (050).................................................................................................. 48
[ALM1] [ALM2] Alarm type 1, 2 (051, 052) ............................................................................................ 49
[StAt] Status display of ramp soak (054) .................................................................................................. 51
[PtN] Ramp soak execution pattern (055) ................................................................................................. 52
[SV-1] to [SV-8] 1st target SV to 8th target SV (056 to 077) ....................................................................... 53
[tM1R] to [tM8R] 1st ramp time to 8th ramp time (057 to 078) .................................................................. 53
[tM1S] to [tM8S] 1st soak time to 8th soak time (058 to 079) .....................................................................53
[Mod] Ramp soak mode (080) ................................................................................................................. 55
3-3 3rd block parameter ............................................................................................................................. 57
[P-N1] Control action (090) .................................................................................................................... 57
[SV-L] SV (Set value) lower limiter (091) ................................................................................................ 58
[SV-H] SV (Set value) upper limiter (092) ................................................................................................ 58
[dLY1] [dLY2] Delay time 1, 2 (093, 094) ................................................................................................ 59
[A1Hy] [A2Hy] Alarm 1, 2 hysteresis (098, 099) ...................................................................................... 59
[A1oP] [A2oP] Alarm 1, 2 options (101, 102) ........................................................................................... 61
[PLC1] [PHC1] OUT1 Upper/Lower Limits (104, 105) ............................................................................. 62
[PCUt] Output limit types (108)............................................................................................................... 63
[oUt1] Output value (MV) display (109) .................................................................................................. 64
[RCJ] RCJ (Cold junction compensation) setting (111) .............................................................................. 65
[AdJ0] User-denable zero adjustment (113) ............................................................................................ 66
[AdJS] User-denable span adjustment (114) ............................................................................................ 66
[dSP1] to [dP14] Parameter mask (126 to 139) .......................................................................................... 68
[UKy1] [UKy2] [UKy3] USER key assignment (143, 144, 145) ................................................................. 70
[FLo1] MV1 during FALT (146) ..............................................................................................................71
[dSPt] PV/SV display OFF (148) ............................................................................................................. 72
4 Troubleshooting ............................................................................................................... 73

8
For Proper Use
Conrmation of model
code
Please conrm that the model delivered matches your order.
“Model Specications” (see page 9)
Installation and Mounting External dimensions
• Panel cutout
• Panel mounting dimensions
“4 Installation and Mounting” (instruction manual)
Wiring Terminal connection diagram
“5 Wiring” (instruction manual)
Power ON
Before starting operation, wait for at least 30 minutes for the PXF to warm up.
Basic settings and
operation
Basic operations (see page 13)
Changing SV (Set value) (see page 14)
Parameters List (see page 15 to 18)
Temperature control functions (see page 19)
Advanced Usage Setting of input sensor and input range (see page 42 to 44)
Selecting control method (see page 36)
Controlling through auto-tuning (see page 25)
Setting parameter automatically
• Fuzzy control (see page 37)
• Self tuning control (see page 37)
Operation
Error Indications Display during equipment error
“4 Troubleshooting” (see page 73)

9
Model Specications
Specification
45678
PXF
2U -
9 10 11 12 13
Note
Note1
Digit
<Front panel size W×H>
48×48mm
<Input signal>
Universal input
Universal input (PXV/PXW/PXZ)
<Control output>
Relay contact (SPDT)
SSR drive output
Current output
<Terminal form>
Socket type
<Revision code>
<Alarm output>
None
2 points
<Power supply voltage>
100 to 240V AC
24 V AC/DC
―
4
U
Y
0
0
2
V
B
4
G
B
C
E
A
N
4
5
6
7
8
9
10
11
12
13
0Y 04
Note1) Input terminal assignment is same as RTD input of PXV/PXW/PXZ

10
1 Part names and functions
This section describes the names and functions of each part of the front panel. The front panel has the PV and SV
displays, the status indicator lamps, and the setting keys, etc. Their functions are explained below. Please read and
understand them before using the PXF.
For details about the setting of parameters, see Chapter 2 and Chapter 3.
Operation keys Indicator
PXF4
USERkey
SEL key
LEFT key
DOWN key
UP key
1-1 Operation keys
USER key
• Press to switch between SV and MV during the PV/SV display (operation mode).
• Press to return to the operation mode from the parameter setup mode.
• Press and hold the USER key to start the assigned function during the PV/SV display (operation mode). (No
function is allocated at the factory.)
SEL key
• Press to enter the parameter setup mode from the operation mode or standby.
• Press to nish selecting and save change.
LEFT key
• Press to move the digit when you editing the numerals.
UP/DOWN key
• Press to change the SV during the PV/SV display.
• Press to switch the parameters during the parameter selection mode.
• Press to change the parameter value during the parameter editing mode.
USER+UP keys, USER+DOWN keys
• By pressing and holding the USER key and the UP/DOWN key during the PV/SV display, you can start the
assigned function.
In the factory default setting, the USER + UP key allows you to switch between run/standby, and the USER +
DOWN key to switch between start/stop of auto-tuning.
See page 70 for how to change the setting of these keys.

11
Indicators
1-2 Indicators
(1) Process variable (PV)
Indicates the process variable. In the parameter setup mode, the parameter name is displayed.
(2) OUT1 indicator
Lights during control output is ON.
(3) EV1, EV2 indicators
Lights during digital output 1 to 2 are ON.
(4) STBY indicator
Lights when the stanby is set to ON. (see page 21)
(5) MANU indicator
Lights during manual mode. (see page 20)
(6) °C/˚F indicator
Shows the temperature unit under use.
(7) A, % indicator
Indicates the unit applied to the value on SV screen during the parameter selection mode and parameter editing
mode.
(8) Set Value (SV) / Manipulated variable (MV)
Shows the setpoint or the manipulated variable. During the parameter editing mode, the parameter setpoint is
displayed.
(9) MV indicator
Lights when the MV is displayed.
(10) Screen No.
Shows screen No. when in parameter setting.
(11) AT indicator
Lights during auto tuning. (see page 25)
(12) RUN/HOLD/END indicators
Lights during ramp soak operation. (see page 22)
(13) KEYLOCK indicator
Lights when the keylock is on. (see page 29)

12
Part names and functions
1-3 Digital characters
The following tables provide correspondence between digital characters used for the display of the controller and
alphanumerical characters. (See the following table for details.)
Digital character Alphabet Digital character Numer
A 1
B 2
C 3
D 4
E 5
F 6
G 7
H 8
I 9
J 0
K
L
M
N
O
P
―Q
R
S
T
U
V
W
X
Y
―Z

13
2 Basic Operation
2-1 Basic operation
The below gure illustrates the mode transition and the key operations.
Power ON
Operation Mode
approx.
1 second
To switch between SV and MV
Press .
MV
SV
To change the setpoint
● Press or to change the value.
● Press to move to the next digit.
● Press to move to the next digit.
< Parameter selection mode > < Parameter editing mode >
2nd block parameter
1st block
parameter
3rd block
parameter
approx.
3 seconds
approx.
5 seconds
The parameter setpoint starts blinking.
Press or to change the value.
To change the digit, use .
Press to resist the changed value.

14
Basic Operation
2-2 Changing SV (Set value)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
The SV is a target value for control.
SV must be within the range between [SV-L] (lower limit) and [SV-H] (upper limit) which belong to Pid
parameter.
Related parameters:
SV (Set value) lower limiter [SV-L], SV (Set value) upper limiter [SV-H] (see page 58)
[Setting example] Changing the SV from 250°C to 1195°C –––––––––––––––––––
Display Operating procedure
1. 1. Check that the PV/SV display is shown.
2. Press , or keys to change SV to “1195”.
The change become effective immediately.

15
Parameters List
2-3 Parameters List
The following explains each channel parameter.
The range of the parameters in the shaded area indicates the industrial values.
When you change the PV input lower limit (P-SL), PV input upper limit (P-SU), or decimal place position (P-dP),
recongure all the industrial values.
Power-cycle the controller after you change the setpoint of the parameters of which No. column is shaded in gray.
Operation Mode
Parameter
symbol Parameter name Setting range Factory default
setting
Parameter
mask DSP
PV
Process Value ― ― ―
SV Set value Within the limit of 0 to 100% of FS
0 (°C)
―
MV Manipulated Variable (%) -5.0 to 105.0 (%)
-5.0
DSP14-
32768
1st block parameter
No Display Parameter
symbol Parameter name Setting range Factory
default setting
Parameter
mask DSP
Reference
page
1
MANU
Manual mode selection oFF, oN oFF DSP13-32
20
2 Stby Standby setting oFF, oN oFF DSP1-1
21
4 PRoG Ramp soak control oFF, RUN, HLd oFF DSP1-2
22
5 LACH Alarm latch cancel oFF, RSt oFF DSP1-4
24
6 At Auto-tuning oFF, oN, L-oN oFF DSP1-8
25
7 tM-1 Timer 1 display ― ― DSP1-16
27
8 tM-2 Timer 2 display ― ― DSP1-32
10 AL1 Set value of alarm 1
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
10 (°C)
DSP1-128
28
11 A1-L Lower limit value of alarm 1
Absolute value alarm: 0 to 100%FS,
Deviation alarm: -100 to 100%FS
10 (°C)
DSP2-1
12 A1-H Upper limit value of alarm 1
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
10 (°C)
DSP2-2
13 AL2 Set value of alarm 2
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
10 (°C)
DSP2-4
14 A2-L Lower limit value of alarm 2
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
10 (°C)
DSP2-8
15 A2-H Upper limit value of alarm 2
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
10 (°C)
DSP2-16
19 LoC Key lock 0 to 5 0 DSP3-1
29

16
Basic Operation
2nd block parameter
No Display Parameter
symbol Parameter name Setting range Factory
default setting
Parameter
mask DSP
Reference
page
30 P Proportional band 0.0 to 999.0 (%) 5.0 DSP3-2
30
31 i Integral time 0 to 3200 (sec) 240 DSP3-4
32 d Derivative time 0.0 to 999.9 (sec) 60.0 DSP3-8
33 HyS Hysteresis range for ON/
OFF control 0 to 50%FS 1 (°C) DSP3-16
32
36 bAL Output convergence value -100.0 to 100.0 (%) 0.0 DSP3-128
34
37 AR Anti-reset windup 0 to 100%FS 400 (°C) DSP4-1
35
38 CtRL Control algorithm
oNoF, Pid, FUZY, SELF, Pid2
Pid DSP4-2
36
39 SLFb PV (Process variable) stable
range 0 to 100%FS 8 (°C) DSP4-4
39
40 oNoF Hysteresis mode oN, oFF oN DSP4-8
40
41 tC
Cycle time of control output 1
1 to 150 (sec)
Relay: 30
DSP4-16
41
SSR: 2
Current: 1
43 P-N2 Input signal code
JPt (Resistance bulb (RTD) JPt100)
Pt (Resistance bulb (RTD) Pt100)
J (Thermocouple J)
K (Thermocouple K)
R (Thermocouple R)
b (Thermocouple B)
S (Thermocouple S)
t (Thermocouple T)
E (Thermocouple E)
L (Thermocouple L)
N (Thermocouple N)
PL-2 (Thermocouple PL-II)
W (Thermocouple W)
0-5V (DC voltage 0 to 5V DC)
1-5V (DC voltage 1 to 5V DC)
0-10 (DC voltage 0 to 10V DC)
2-10 (DC voltage 2 to 10V DC)
0-20 (Direct current 0 to 20mA)
4-20 (Direct current 4 to 20mA)
U (Thermocouple U)
MV (MV)
K DSP4-64
42
44 P-SL Lower limit of measuring
range -1999 to 9999 0 (°C) DSP4-128
43
45 P-SU Upper limit of measuring
range -1999 to 9999 400 (°C) DSP5-1
46 P-dP Decimal point position 0 to 3 0 DSP5-2
45
48 PVOF PV offset -10.00 to 10.00%FS 0 (°C) DSP5-8
46
49 SVOF SV shift -50.00 to 50.00%FS 0 (°C) DSP5-16
47
50 P-dF Time constant of input lter 0.0 to 120.0 (sec) 5.0 DSP5-32
48
51 ALM1 Alarm type 1 0 to 31 0 DSP5-64
49
52 ALM2 Alarm type 2 0 to 31 0 DSP5-128
54 StAt Status display of ramp soak ― ― DSP6-2
51
55 PtN
Ramp soak execution pattern
1 to 3 1 DSP6-4
52

17
Parameters List
No Display Parameter
symbol Parameter name Setting range Factory
default setting
Parameter
mask DSP
Reference
page
56 SV-1 1st target SV SV lower limit (SV-L) to
SV upper limit (SV-H) %FS 0 (°C) DSP6-8
53
57 tM1R 1st ramp time 0.00 to 99.59 0:00 DSP6-16
58 tM1S 1st soak time 0.00 to 99.59 0:00 DSP6-32
59 SV-2 2nd target SV SV lower limit (SV-L) to
SV upper limit (SV-H) %FS 0 (°C) DSP6-64
60 tM2R 2nd ramp time 0.00 to 99.59 0:00 DSP6-128
61 tM2S 2nd soak time 0.00 to 99.59 0:00 DSP7-1
62 SV-3 3rd target SV SV lower limit (SV-L) to
SV upper limit (SV-H) %FS 0 (°C) DSP7-2
63 tM3R 3rd ramp time 0.00 to 99.59
0:00
DSP7-4
64 tM3S 3rd soak time 0.00 to 99.59
0:00
DSP7-8
65 SV-4 4th target SV SV lower limit (SV-L) to
SV upper limit (SV-H) %FS 0 (°C) DSP7-16
66 tM4R 4th ramp time 0.00 to 99.59
0:00
DSP7-32
67 tM4S 4th soak time 0.00 to 99.59
0:00
DSP7-64
68 SV-5 5th target SV SV lower limit (SV-L) to
SV upper limit (SV-H) %FS 0 (°C) DSP7-128
69 tM5R 5th ramp time 0.00 to 99.59
0:00
DSP8-1
70 tM5S 5th soak time 0.00 to 99.59
0:00
DSP8-2
71 SV-6 6th target SV SV lower limit (SV-L) to
SV upper limit (SV-H) %FS 0 (°C) DSP8-4
72 tM6R 6th ramp time 0.00 to 99.59
0:00
DSP8-8
73 tM6S 6th soak time 0.00 to 99.59
0:00
DSP8-16
74 SV-7 7th target SV SV lower limit (SV-L) to
SV upper limit (SV-H) %FS 0 (°C) DSP8-32
75 tM7R 7th ramp time 0.00 to 99.59
0:00
DSP8-64
76 tM7S 7th soak time 0.00 to 99.59
0:00
DSP8-128
77 SV-8 8th target SV SV lower limit (SV-L) to
SV upper limit (SV-H) %FS 0 (°C) DSP9-1
78 tM8R 8th ramp time 0.00 to 99.59
0:00
DSP9-2
79 tM8S 8th soak time 0.00 to 99.59
0:00
DSP9-4
80 Mod Ramp soak mode 0 to 15
0
DSP9-8
55

18
Basic Operation
3rd block parameter
No Display Parameter
symbol Parameter name Setting range Factory
default setting
Parameter
mask DSP
Reference
page
90 P-N1 Control action 0 to 3
0
DSP9-16
57
91 SV-L SV (Set value) lower limiter 0 to 100%FS 0 (°C) DSP9-32
58
92 SV-H SV (Set value) upper limiter 0 to 100%FS 400 (°C) DSP9-64
93 dLY1 Delay time 1 0 to 9999 (sec) 0 DSP9-128
59
94 dLY2 Delay time 2 0 to 9999 (sec) 0 DSP10-1
98 A1Hy Alarm 1 hysteresis 0 to 50%FS 1 (°C) DSP10-16
59
99 A2Hy Alarm 2 hysteresis 0 to 50%FS 1 (°C) DSP10-32
101
A1oP Alarm 1 options 000 to 111 000 DSP10-128
61
102
A2oP Alarm 2 options 000 to 111 000 DSP11-1
104
PLC1 Lower limit for output 1 -5.0 to 105.0 (%) -5.0 DSP11-4
62
105
PHC1 Upper limit for output 1 -5.0 to 105.0 (%) 105.0 DSP11-8
108
PCUt Output limit types 0 to 3 0 DSP11-64
63
109
oUt1 Output value (MV) display ― ― DSP11-128
64
111
RCJ RCJ (Cold junction
compensation) setting oN, oFF oN DSP12-2
65
112
GAiN PV gradient 0.001 to 2.000 1.000 DSP12-4
―
113
AdJ0 User-denable zero
adjustment -50 to 50%FS 0 (°C) DSP12-8
66
114
AdJS User-denable span
adjustment -50 to 50%FS 0 (°C) DSP12-16
126
dSP1
Parameter mask ― Depends on
the model DSP14-128
68
127
dSP2
…
138
dP13
139
dP14
143
UKy1 USER key 0 to 6 0 DSP14-8
70
144
UKy2 USER key + UP key 0 to 6 1 DSP14-16
145
UKy3 USER key + DOWN key 0 to 6 5 DSP14-32
146
FLo1 MV1 during FALT -5.0 to 105.0 (%) -5.0 DSP14-64
71
148
dSPt PV/SV display OFF 0 to 8 0 DSP14-256
72
This manual suits for next models
1
Table of contents
Other Fuji Electric Temperature Controllers manuals

Fuji Electric
Fuji Electric PXG5 User manual

Fuji Electric
Fuji Electric PUMCE User manual

Fuji Electric
Fuji Electric PXR3 Series User manual

Fuji Electric
Fuji Electric PUM Series User manual

Fuji Electric
Fuji Electric PXH Series User manual

Fuji Electric
Fuji Electric PXZ Series User manual

Fuji Electric
Fuji Electric PXR3 Series User manual

Fuji Electric
Fuji Electric PXF4 User manual

Fuji Electric
Fuji Electric PUMCL User manual

Fuji Electric
Fuji Electric PXE4 User manual