CT, PT Ratios and System Hookup
Settings: Enter the following settings:
CT Numerator (enter value you want),
Denominator (display only), Multiplier (1,
10, or 100), CT Fullscale (Calculated auto-
matically)
PT Numerator (enter value you want),
Denominator (enter value you want),
Multiplier (1, 10, 100, or 1000), PT Fullscale
(Calculated automatically)
System Wiring: select from 3 Element Wye,
2.5 Element Wye, or 2 CT Delta.
NOTE: Voltage Full Scale = PT Numerator x PT Multiplier
Current Full Scale = CT Numerator x CT
Multiplier
IMPORTANT! Specify Primary and Secondary Voltage in Full Scale (NOT Ratios).
Example CT Settings:
200/5 Amps: Set Ct-n value as 200, Ct-S value as 1.
800/5 Amps: Set Ct-n value as 800, Ct-S value as 1.
2,000/5 Amps: Set Ct-n value as 2000, Ct-S value as 1.
10,000/5 Amps: Set Ct-n value as 1000, Ct-S value as 10.
Example PT Settings:
14,400/120 Volts: Set Pt-n value as 1440, Pt-d value as 120, Pt-S value as 10.
138,000/69 Volts: Set Pt-n value as 1380, Pt-d value as 69, Pt-S value as 100.
345,000/115 Volts: Set Pt-n value as 3450, Pt-d value as 115, Pt-S value as 100.
345,000/69 Volts Set Pt-n value as 345, Pt-d value as 69, Pt-S value as 1000.
Update Device:
8.When changes are complete, click the Update button to send a new profile to the Shark 200T meter.
9.Click Cancel to Exit the profile (or) click other tabs to update other screens.
10.Use Communicator EXT to communicate with the device and perform required tasks.
NOTE: For further details and additional programming screens (Password, Limits, Energy and Dis-
play), refer to the Shark User’s Manual & Communicator EXT 3.0 Software Manual on the enclosed CD.