3.Enter the meter’s new IP address in the Host field and click Connect. The Device Status screen
opens, confirming the connection.
4.Click OK. CommunicatorPQATM software’s Main screen opens.
Configuration Steps:
5.Click the Profile button in the tool bar. You will see the
Shark 100B Profile screen, shown on the right.
6.Click the Scaling tab and select settings based on your
application. The entry fields are as follows:
CT Numerator - enter the value you want to use.
CT Denominator (display only - can’t be changed).
CT Multiplier - select from 1, 10 and 100.
CT Fullscale (Calculated automatically)
PT Numerator - enter the value you want to use.
PT Denominator - enter the value you want to use.
PT Multiplier - select from 1, 10, 100, and 1000.
PT Fullscale (Calculated automatically)
System Wiring: select from 3 Element Wye, 2.5 Element
Wye, or 2 CT Delta.
Phases Displayed: select from A, AB, or ABC.
NOTE: Voltage Full Scale = PT Numerator x PT Multiplier; Current Full Scale = CT Numerator x CT
Multiplier
IMPORTANT! Specify Primary and Secondary Voltage in Full Scale (NOT Ratios).
Example CT Settings:
200/5 Amps: set the Ct-n value as 200, Ct-S value as 1.
800/5Amps: set the Ct-n value as 800, Ct-S value as 1.
2000/5 Amps: set the Ct-n value as 2000, Ct-S value as 1
10,000/5 Amps: set the Ct-n value as 1000, Ct-S value as 10.
Example PT Settings:
14400/120 Volts: set the Pt-n value as 1440, Pt-d value as 120, Pt-S value as 10.
138000/69 Volts: set the Pt-n value as 1380, Pt-d value as 69, Pt-S value as 100.
345000/115 Volts: set the Pt-n value as 3450, Pt-d value as 115, Pt-S value as 100.
345000/69 Volts: set the Pt-n value as 345, Pt-d value as 69, Pt-S value as 1000.
Update Device:
7.Click the Update button to send the new settings to the meter.
NOTE: For additional wiring options, programming screens, and instructions on using the Shark®
100BT’s BACnet®*, refer to the Shark® 100/100T/100B Meter Installation and Operation Manual and
the CommunicatorPQATM, MeterManagerPQATM, and EnergyPQA.comTM Software User Manual on the
enclosed CD.