Shark 200 User manual

Doc# E149703 V.1.11 QS - 1
Shark® 200 Meter Quickstart
Shark® 200 Meter Quickstart Guide
CAUTION! Installation of the Shark® 200 meter must be performed only by qualified personnel who fol-
low standard safety precautions during all procedures. Those personnel should have appropriate training
and experience with high voltage devices. Appropriate safety gloves, safety glasses and protective cloth-
ing are recommended.
During normal operation of the Shark® meter, dangerous voltages flow through many parts of the unit, includ-
ing: Terminals and any connected CTs (Current Transformers) and PTs (Potential Transformers), all I/O Modules
and their circuits. All Primary and Secondary circuits can, at times, produce lethal voltages and currents. Avoid
contact with any current-carrying surfaces.
Do not use the meter or any I/O device for primary protection or in an energy-limiting capacity. The meter can
only be used as secondary protection.
IMPORTANT! Refer to your meter’s Installation and Operation Manual for additional safety warnings before
performing installation, wiring, or maintenance of your meter. See the link to the manual, below.
NOTE: This Quickstart Guide gives basic installation, wiring, and programming instructions.For additional meter oper-
ation and programming information, refer to your meter’s Installation and Operation Manual and the Communicator
PQATM, MeterManagerPQATM, and EnergyPQA.comTM Software User Manual on EIG’s website:
User Manual:
https://www.electroind.com/products/shark-200-power-and-energy-meter/
From the webpage, click Technical Documents>User Manual.
Software Manual:
https://www.electroind.com/products/communicatorpqa-power-monitoring-software/
From the webpage, click Technical Documents>User Manual.
CommunicatorPQATM Setup Software:
https://www.electroind.com/products/communicatorpqa-power-monitoring-software/
From the webpage, click Download ComPQA Pro. To get a Professional license for the software, email sales@elec-
troind.com or call 516-334-0870.
All EIG’s metering and software products’ literature can be accessed from:
https://www.electroind.com/power-metering-products/
For software and metering integration, EIG’s Technical Support Engineers are available on an hourly or daily basis to
help with typical commissioning assistance, which includes:
• Verifying meter installation and wiring.
• Verifying proper system integration.
• Working with 3rd parties to ensure cross compatibility.
• Advising users on best practices for optimal implementation.
You can reach Technical Support from 8 a.m. to 8 p.m. EST, Monday-Friday, at 516-334-0870.

Doc# E149703 V.1.11 QS - 2
Shark® 200 Meter Quickstart
Mechanical Installation
Electrical Installation: Select diagram for your application.
NOTE: Other wiring configurations are available. See the Shark 200 meter User Manual (see page QS-
1 for the download link).
WYE direct, 3
phase, 4 wire
Delta direct, 3
phase, 3 wire
NOTE: Do not overtighten nuts. The maximum installation torque is 0.4 Newton-Meter.
WYE with PTs,
3 phase, 4 wire
Delta with PTs, 3
phase, 3 wire

Doc# E149703 V.1.11 QS - 3
Shark® 200 Meter Quickstart
Program Settings Using the Faceplate Buttons:
(MENU, ENTER, DOWN ARROW, RIGHT ARROW)
See the figure on the right for the location of the
faceplate buttons.
Access Configuration Mode:
1.Push the MENU button - you will see
the display on the right; rSt will be
blinking.
2.Press the DOWN ARROW once.
CFG (Configuration) moves to the
top of the display.
3.Press the ENTER button. You will
see the Configuration menu, shown
on the right.
4.Press the DOWN ARROW and then press the ENTER button. You will see the CT
numerator setting screen (Ct-n). The current CT numerator is shown in the second
line. To change the setting, press the DOWN ARROW until the value you want is
displayed. Then press the RIGHT ARROW to move to the next digit. Repeat until
the setting is done.
5.Press the ENTER button to go to the CT denominator screen (CT-d). This setting is
display only - it can’t be changed.
6.Press the ENTER button to go to the CT Scaling setting screen (CT-S). The current
Scaling is shown in the second line. Press the DOWN ARROW to choose another
value. You can choose 1, 10, or 100.
7.Press the ENTER button to go to the PT numerator setting screen (Pt-n).The current
PT numerator is shown in the second line. To change the setting, press the DOWN
ARROW until the value you want is displayed. Then press the RIGHT ARROW to
move to the next digit. Repeat until the setting is done.
8.Press the ENTER button to go to the PT-denominator screen (Pt-d). The current
PT denominator is shown in the second line. To change the setting, press the DOWN
ARROW until the value you want is displayed. Then press the RIGHT ARROW to
move to the next digit. Repeat until the setting is done.
9.Press the ENTER button to go to the PT Scaling setting screen (PT-S). The current
Scaling is shown in the second line. Press the DOWN ARROW to choose another
value. You can choose 1, 10, 100, or 1000.
NOTE: See example CT and PT settings on page QS-5.

Doc# E149703 V.1.11 QS - 4
Shark® 200 Meter Quickstart
10.Press the ENTER button to go to the Connection setting screen (Cnct). The current
setting is shown in the second line. Press the DOWN ARROW to choose another
value. You can choose 3 EL (element) WYE, 2 Ct del (Delta), or 2.5 EL WYE.
11.Press the ENTER button to go to the meter Address setting screen (Adr). The
meter’s current address is shown in the second line. To change the setting, press
the DOWN ARROW until the value you want is displayed. Then press the RIGHT
ARROW to move to the next digit. Repeat until the setting is done. Valid address-
es are from 001 through 247. IMPORTANT! If you are using the Ethernet
option (INP100S) do not change any settings - leave the address as 001.**
12.Press the ENTER button to go to the meter Baud Rate setting screen (bAUd). The
meter’s current Baud Rate is shown in the second line. Press the DOWN ARROW
to choose another Baud Rate. You can choose 9600 (choose this for RS485
connection), 19.2 (19200), 38.4 (38400) or 57.6 (57600). IMPORTANT! If you
are using the Ethernet option, do not change any settings - leave the Baud Rate
as 57.6.**
13.Press the ENTER button to go to the meter Protocol setting screen (Prot). The
meter’s current Protocol is shown in the second and third lines. Press the DOWN
ARROW to choose another communication Protocol. You can choose Mod rtU
(Modbus RTU; choose this for RS485 connection), Mod ASCI (Modbus ASCII),
or dnp (DNP 3.0). IMPORTANT! If you are using the Ethernet option, do not
change any settings - leave the protocol as Mod rtU.**
14.Press the ENTER button to go to the Scroll setting screen (SCrL). The current
setting is shown in the second line. Press the DOWN ARROW to choose another
setting. You can choose YES (the meter readings will scroll on the display) or no
(the meter readings will not scroll on the display).
15.Press the MENU button twice. You will see the Store Settings screen (Stor ALL?)
The default setting is YES. To save the settings you’ve made, press the ENTER
button. You will see the confirmation screen (Stor ALL done) and then the meter
resets.
NOTE: If you do not want to save your settings, press the RIGHT ARROW. YES
changes to no. Press the ENTER button.
**The Shark® 200 meter’s Ethernet communication settings are the default settings of
Address 1, Baud Rate 57.6 and Protocol Mod rtU. See the Shark® 200/200T Meter Installation and
Operation Manual (see page QS-1 for the download link) for additional configuration instructions for
the Shark® 200 meter’s Ethernet port

Doc# E149703 V.1.11 QS - 5
Shark® 200 Meter Quickstart
Example CT Settings:
200/5 Amps: set the Ct-n value as 200, Ct-S value as 1.
800/5Amps: set the Ct-n value as 800, Ct-S value as 1.
2000/5 Amps: set the Ct-n value as 2000, Ct-S value as 1
10,000/5 Amps: set the Ct-n value as 1000, Ct-S value as 10.
Example PT Settings:
14400/120 Volts: set the Pt-n value as 1440, Pt-d value as 120, Pt-S value as 10.
138000/69 Volts: set the Pt-n value as 1380, Pt-d value as 69, Pt-S value as 100.
345000/115 Volts: set the Pt-n value as 3450, Pt-d value as 115, Pt-S value as 100.
345000/69 Volts: set the Pt-n value as 0345, Pt-d value as 69, Pt-S value as 1000.
For additional programming instructions for the faceplate buttons, see Chapter 6 in the Shark® 200/
200T Meter Installation and Operation Manual.
Connect to the Meter through the
RS485 Port:
The Shark® 200 meter has a stan-
dard RS485 port that makes connec-
tion between the meter and a laptop
PC very simple.The Shark® 200
meter’s RS485 port uses standard 2-
wire, half duplex architecture.
Factory Initial Default Settings: When the Shark® 200 is powered up, for 10 seconds you can
connect to the meter using the Factory Default Settings (even if the Device Profile has been changed).
After 10 seconds, the Device Profile reverts to the actual Device Profile in use. This is one way you can
always connect to the meter. The Factory Initial Default Settings are:
Device Address:1
Baud Rate:57600
Protocol:Modbus RTU

Doc# E149703 V.1.11 QS - 6
Shark® 200 Meter Quickstart
Follow these steps to connect to the meter via RS485:
1. Connect the meter to the PC, using an RS485 cable. EIG offers a RS485 to USB connector, which can
be ordered from EIG’s website: https://www.electroind.com/product/rs485-to-usb-communication-
-converter/.
2. Open CommunicatorPQATM software (see page QS-1 for the download link).
3. Click Connect in the Icon Bar.
4. You will see the Connect screen. Make sure
your settings match the ones shown on the right
(use pull-down menus).
5. Click Connect. The Device Status screen confirms
the connection. Click OK to close the Device Status
screen.
6. Click the Profile button on the Icon bar.
7.The Device Profile screen opens. The Tree menu on the left side of the screen lets you choose setting
screens. Click on a plus sign to view the settings screen
options.

Doc# E149703 V.1.11 QS - 7
Shark® 200 Meter Quickstart
Program CT, PT Ratios
1. This is the first Device Profile screen. To
return to this screen from another set-
tings screen, click General Settings>CT,
PT Ratios and System Hookup.
2. These are the settings:
a. CT Numerator (enter value you want),
Denominator (display only), Multiplier
(1, 10, or 100), CT Fullscale (Calculated
automatically)
b. PT Numerator (enter value you want),
Denominator (enter value you want),
Multiplier (1, 10, 100, or 1000), PT Fulls-
cale (Calculated automatically)
NOTE: Voltage Full Scale = PT Numerator x
PT Multiplier
Current Full Scale = CT Numerator x CT Multiplier
IMPORTANT! Specify Primary and Secondary Voltage in Full Scale (NOT Ratios).
NOTE: You can also enter the Ratios for CT/PT Numerator and Denominator and click the Update CT/
Update PT buttons to let the software calculate the Numerator, Denominator, and Multiplier for you.
You can then empty the Ratio fields and click the Update Ratio buttons to confirm the calculated set-
tings: you will see the same ratios you initially entered.
See Chapter 8 in the software manual for additional screen settings instructions (see page QS-1; alter-
natively, you can click Help>Contents from the CommunicatorPQATM software’s Main screen).
Program Communications:
1. Click General Settings>Communications.
2. The settings shown on the screen are the
default settings for the meter’s IrDA (COM1
and RS485 (COM2) ports. You can change the
settings, if necessary for your application.

Doc# E149703 V.1.11 QS - 8
Shark® 200 Meter Quickstart
Program Meter Time: The meter is preset to Eastern time. To change the meter time:
1. From the Main screen’s Title bar, click Tools>Set Device Time.
2. You can either enter the time in the Time fields, or click Use
PC Time to set the time using your PC’s time.
3. Click Send.
NOTE: The meter offers multiple Time Synchronization meth-
ods. See Chapter 8, Section 8.1.2 in the software manual (see
page QS-1; alternatively, you can click Help>Contents from the
Main screen to open the manual) for instructions on setting up
Time Sync for the meter.
Program Meter Name:
To enter a name/ID for the meter:
1. From the Device Profile screen, click
General Settings>System Settings.
2. Input a new meter designation into the
field. Note that it is important to name
each meter individually, since the meter
name is used to name the log databases
when logs are downloaded.
See Chapter 8 in the software manual
for an explanation of the other settings
in this screen.
IMPORTANT! When you have made
changes to the meter’s Device Profile, click
Load Profile at the bottom of the Device Pro-
file screen to send the new settings to the
meter. The meter will reboot and then you can reconnect to it. Note that you can also click Save Profile
to save your changes without sending them to the meter.
Shark® is a registered trademark of Electro Industries/GaugeTech. CommunicatorPQATM, MeterManagerPQATM, and Ener-
gyPQA.comTM are trademarks of Electro Industries/GaugeTech.
https://electroind.com/
Table of contents
Other Shark Measuring Instrument manuals