RETROFITTING TO AN EXISTING SIDDONS COILED TANK
This new Electronic Split heat pump model has improved features over the previous mechanical heat pump.
New features include:
* Electronic tank sensor probe replacing the mechanical Klixon tank thermostat for regulating the on/off
function of the heat pump
* Electronic tank sensor probe replacing the mechanical Klixon tank thermostat for regulating the over
temperature function of the compressor; this can be reset by turning power to the heat pump on/off.
* Electronic tank sensor probe for activating the de-ice function; on older units from 2005, this will replace
the mechanical Klixon evaporator thermostat for regulating the de-ice function
* Pressure switches
* LED display unit that provides diagnostic information and monitoring of key operating parameters (refer
Section IV). Note, the LED display unit can be placed under the heat pump lid on top of the electrical
wiring post or placed onto a wall using the sensor extension lead provided with the heat pump)
REFRIGERANT: This Electronic Split heat pump is charged with 1.5KG of R134A refrigerant, whereas the
older style Mechanical Split heat pump is charged with 1.5kg of R417a refrigerant.
CONNECTING THE NEW HEAT PUMP
* Locate the heat pump at least 75mm clear of a wall on the air inlet side and at least 1m clear of a wall or
fence on the air outlet side.
* Ensure all refrigerant is purged from the existing system.
* Connect the existing refrigeration lines to the new refrigeration lines supplied with new electronic heat
pump by brazing them together.
* Ensure the new heat pump and tank and connected with no refrigerant leakage.
* Evacuate the air from the refrigeration lines and the 40m condenser coil wrapped around the tank.
* Fully open both refrigeration valves on the heat pump to charge the whole system.
* Mark the technical label on the tank, deleting reference to R417a refrigerant charge and write in R134a.
* The digital controller can be placed inside the heat pump box on top of the terminal block after the heat
pump has been set, clock and timer (if required) or it can be fixed onto a wall by using the extension lead
provided. Make sure the digital controller is protected from the weather.
* Fit the drain plug and connect a plastic hose to take the condensate water from the evaporator away to a
drain from underneath the heat pump. Angle the heat pump slightly towards the drain plug to enable the
condensate water to flow easily towards the drain plug. Periodically check the drain plug for any blockages.
* If the heat pump is mounted on a wall or on top of a roof, make sure the heat pump’s feet are mounted on
top of rubber pads to prevent vibration from being transmitted.
* It is fine to connect the heat pump to off-peak power but keep in mind the heat pump will operate about
25% more efficiently with a 10 degree rise in the ambient air temperature.
* We recommend installing a pool pump timer set between 12:00pm and 5.00pm if connecting to a
continuous tariff to ensure one operating cycle at the warmest time of day for greater efficiency.
CONNECTING THE SENSOR PROBE TO THE TANK
You will need to fit the tank water temperature sensor probe against the storage tank wall, underneath the
insulating foam and seal with silicone. Here are the key installation points:
* Make a small hole with a screwdriver hard against the storage tank 50-75mm long to fit the probe tightly
* Push the sensor probe in right to the end of the hole
* Seal the hole with silicone to ensure the probe gets a good reading from the tank wall, unaffected by the air
* Secure the sensor probe lead so it cannot fall out of position
* Fine tuning adjustment to the probe cut off/on settings can be made if necessary (refer Section IV)