Installation Instructions
Model XLS-MLE6(R)-ADPT
Adapter Kit
SiemensSiemens
SiemensSiemens
Siemens IndustryIndustry
IndustryIndustry
Industry,,
,,
,Inc.Inc.
Inc.Inc.
Inc.
BuildingBuilding
BuildingBuilding
Building
TT
TT
Tecec
ecec
echnologies Dihnologies Di
hnologies Dihnologies Di
hnologies Divisionvision
visionvision
vision
A6V10328630_en--_b
INTRODUCTION Use the Model XLS-MLE6(R)-ADPT Adapter Kit from Siemens Industry, Inc., to
upgrade existing MXL Systems installed in Model MLE-6(R) backboxes to FireFinder-
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular Systems.The XLS-MLE6(R)-
ADPT Adapter Kit consists of an adapter plate, inner door and outer door.The XLS-
MLE6-ADPT (S54430-C9-A1) inner and outer doors are black; the XLS-MLE6R-ADPT
(S54430-C9-A2) inner door is black and outer door is red.The XLS-MLE6-ADPT and
the XLS-MLE6R-ADPT are identical in all other ways and will be referred to in the
remainder of this document as XLS-MLE6-ADPT.
The adapter plate installs over the existing studs in an MLE-6(R) backbox with the
#1/4 x 20 hex flange nuts supplied and provides studs on which to mount three
CAB-MP mounting plates (P/N 500-633012) and two PTB power termination boards
(P/N 500-033390).
The outer door consists of the door frame and three removable panels. Each remov-
able panel is secured to the door with #10-32 nuts. The removable panels may be
clear (OD-LP), blank (OD-BP/-R), or vented (OD-GP/-R) depending on the application.
The OD-BP-R and OD-GP-R panels are red. The outer door is attached to the backbox
by hinge pins and secured to the backbox by a keyed latch.
The inner door has three openings in it for the installation of an operator interface and
other modules. There are eight threaded studs around each opening on the inner
door. These threaded studs allow equipment installation on the door. The equipment
is secured by #10-32 nuts. The inner door is permanently hinged right, is attached to
the backbox by screws, and is secured to the backbox by a swell-action latch.
The XLS-MLE6(R)-ADPT is for indoor use only in dry environments.
With this conversion, the maximum battery set that can be used in the backbox is 33
AH (model BTX-1). If larger batteries are required, use either a BB-55 or CAB-BATT
battery box.
When converting an MXL to an XLS/Desigo Fire Safety Modular/Cerberus PRO
Modular system, it may be necessary to use the XLS-EXT-CABLE-PKG (S54430-K1-
A1).This kit includes a 58 inch 60-pin Data Bus cable, a 58 inch 6-pin CAN Bus cable
and a 20 inch 12AWG ground wire.
To convert an MLE-6(R) backbox from an MXL System to an XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular component system, you must first disassemble the
MXL and then assemble the XLS/Desigo Fire Safety Modular/Cerberus PRO Modular.
This two-part procedure is described in detail on page 2.
Siemens Industry, Inc.
Building Technologies Division
A6V10328630_en--_b2
DISASSEMBLY OF MXL SYSTEM
Remove all system power, first battery and then AC.
1. Remove and discard the outer door and the hardware used to secure it in
place.
2. Disconnect and remove the modules from the inner door.
3. Remove all modules from the backbox, making sure to mark all wires.
4. Remove the MPS power supply and batteries from the backbox. Save the
mounting hardware for later use.
ASSEMBLY OF XLS/DESIGO FIRE SAFETY MODULAR/CERBERUS PRO MODULAR SYSTEM
The three parts of the XLS-MLE6-ADPT are installed separately. The adapter plate is
installed first, followed by the inner door and then the outer door.
Adapter Plate The XLS-MLE6-ADPT adapter plate has 18 holes in it that fit over the studs in the
MLE-6 backbox in only one way.
1. Place the XLS-MLE6-ADPT over the studs in the backbox and secure it in
place with the six #1-4 x 20 hex flange locknuts supplied in the locations
marked “A” shown in Figure 1.
MLE-6
BACKBOX
XLS-MLE6(R)-ADPT
ADAPTER PLATE
“A”
“A”
GROUND LUG
(THIS LUG IS FOR
GROUNDING THE
AC INPUT)
REMOVE GROUND
LUG BEFORE
MOUNTING THE PTB.
AFTER INSTALLING
THE PTB, BE SURE
TO REINSTALL THE
GROUND LUG.
“A”
“A” “A”
“A”
“B” “B”
“B”
“B”
“B”
“B”
“B” “B”
“B” “B”
“B” “B”
“C”
“C”
“D”
BATTERY BATTERY
Figure 1
Installing the XLS-MLE6-ADPT Adapter Plate in the MLE-6 Backbox
Siemens Industry, Inc.
Building Technologies Division
A6V10328630_en--_b3
2. Three CAB-MPs can be mounted on the XLS-MLE6-ADPT using the studs
marked “B” in Figure 1.
3. Install the required CC-5/CC-2 system cardcage(s), PSC-12 power supply,
optional PSX-12 power supply extender and PTB power termination board
after careful consideration of NEC Article 760 for separation of power
limited and non-powered limited wiring. Use the hardware provided with
those modules to mount them to the CAB-MP mounting plate. Refer to the
CC-5/CC-2 Installation Instructions, P/N 315-033035, the PSC-12 Installation
Instructions, P/N 315-033060, and the PSX-12 Installation Instructions, P/N
315-034120.
4. There is room on the bottom of the XLS-MLE6-ADPT to mount up to two
PTBs on the studs marked “C” and “D” in Figure 1. Refer to the PTB
Installation Instructions, P/N 315-034877. The stud marked “D” is a lug for
grounding the AC input. Remove the ground lug before mounting the PTB.
After installing the PTB, be sure to reinstall the ground lug.
5. There is room in the bottom of the enclosure for a battery set of up to 33 AH.
6. System cards can be installed in the CC-5/CC-2 cardcage(s), as required.
Install the Inner Door Install the inner door by following the steps listed below.
1. Place two of the eight #8-32x5/16 screws provided in the top and bottom
holes on the right-hand side of the backbox.
2. Tighten the screws just a few turns leaving a 1/8-inch gap between the
head of the screws and the backbox.
3. Slide the inner door into position under the screws.
4. Make certain the flange at the left-hand top of the inner door is seated in
the slot in the backbox and the swell action latches located near the top and
bottom of the inner door are seated in their respective holes in the backbox.
(Refer to Figure 2.) Press the latches down to secure them in place, adjust-
ing the door as needed so that it seats securely in the enclosure.
Siemens Industry, Inc.
Building Technologies Division
A6V10328630_en--_b4
INNER
DOOR
SWELL
ACTION
LATCH
HOLE
FOR
LATCH
MLE-6
BACKBOX
SLOT
FLANGE
SWELL
ACTION
LATCH
HOLE
FOR
LATCH
MLE-6
BACKBOX
#8-32x5/16
SCREWS
(QTY. 8)
LOCATION OF
OPTIONAL
HTSW-1
TAMPER
SWITCH
Figure 2
Installing the Inner Door
5. Insert the remaining six screws in the six holes on the right side of the
backbox to secure the inner door. Tighten all eight of the screws.
6. Install a FCM2041-U2/-U3 on the inner door. Refer to the PMI Installation
Instructions, P/N 315-033070, the FCM2041-U2 Installation Instructions,
Document ID A6V11231623, or the FCM2041-U3 Installation Instructions,
Document ID A6V11231630, for further information.
7. Install door-mounted modules (FCM-6, LCM-8, SCM-8), as needed, for
system operation.
8. Insert blank plates, as needed, in unused spaces on door and secure with
#10-32 nuts. (Refer to Table 1 and Figure 3.)
1ELBAT
SETALPROODRENNI
LEDOMNOITPIRCSEDGNITNUOM
PM-DI,6-MCFroftekcarb/etalpgnitnuoM
.MCBdna8-MCS,8-MCL
deruce
S.roodnisdutsnostnuoM
.stun23-01owthtiw
PS-DIehtsaezisemasehttresniknalB
.tekcarb/etalpgnitnuomPM-DI
deruc
eS.roodnisdutsnostnuoM
.stun23-01owthtiw
nacsPS-DIrosPM-DIruofotpU
.worenonodellatsnieb
PF-DI.etalpknalbwo
rlluFderuceS.roodnisdutsnostnuoM
.stun23-01thgiehtiw
MCB.etalpknalbroodrennIderuceS.roodnisdutsnostnuoM
.st
un23-01thgiehtiw
Siemens Industry, Inc.
Building Technologies Division
A6V10328630_en--_b5
Models LVM and FMT, one module width each, mount to the inner door. No other
modules (PSC-12/PSX-12/CC-5/CC-2) may be located behind these modules.
BACK OF
INNER DOOR
ID-FP
ID-MP
ID-SP
Figure 3
Inner Door and Plates
Install the Outer Door 1. Insert the hinge pins on the outer door in the hinges on the backbox.
2. Install clear, blank, or vented removable panel(s) as required and secure
with #10-32 nuts. (Refer to Table 2 and Figure 4.)
3. Place the XLS system label, P/N 575-234411, Desigo Fire Safety Modular
sytem label, P/N A5Q00075144, or Cerberus PRO Modular system label, P/
N A5Q00075194, on the inside of the outer door.
2ELBAT
SETALPROODRETUO
LEDOMNOITPIRCSEDGNITNUOM
PL-DOesurof-etalPsneLraelC
fonoitacidnilausivnehw
.deriuqersi
noitarepometsys
.roodnisdutsnostnuoM
.stun23-01thgiehtiwderuceS
R-/PB-DOnehwesurof-etalPknalB
metsysehtfon
oitacidnilausiv
daednehwro,deriuqertonsi
.deriuqersinoitcetorptnorf
.roodnisdutsnostnuoM
.stun23-01thgiehtiwderuceS
R-/PG-DOnehwesurof-etalPllirG
.deriuqersilenapdetnev
.roodnisdutsnostnuoM
.stun23-01thgiehtiwde
ruceS
Siemens Industry, Inc.
Building Technologies Division
A6V10328630_en--_b6
CAB3 OUTER DOOR
OD-LP
OD-GP/-R
OD-BP/-R
Figure 4
Outer Door and Plates
4. A ground wire comes installed on the inside of the outer door. (Refer to
Figure 5.) Bring the free end of the ground wire through the opening at the
top left-hand side of the inner door and secure it in place on an unused
stud in the backbox with a #10-32 hex nut (user supplied).
Siemens Industry, Inc.
Building Technologies Division
A6V10328630_en--_b7
MLE-6
BACKBOX
GROUND WIRE
WIRE: 12AWG
UNUSED STUD FOR
GROUND WIRE
INNER
DOOR
OUTER
DOOR
USER SUPPLIED
#10-32 HEX NUT
Figure 5
Ground Wire Installation
5. Close the outer door and secure with the key latch.
WIRING In compliance with NEC Article 760, all power limited fire protective signaling
conductors must be separated a minimum of ¼ inch from all of the following wiring
located within a control panel:
• electric light
•power
• Class 1 or non-power limited fire protective signaling conductors
To meet these requirements, the following guidelines must be observed when
installing modules and wiring to this control panel.
Siemens Industry, Inc.
Building Technologies Division
A6V10328630_en--_b8
When installing power limited field wiring, the installer must comply with NEC article
760, which states:
The fire alarm power-limited circuits are installed using Types FPL, FPLR, FPLP or
permitted substitute cable, provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in. (6.35 mm) or by a noncon-
ductive sleeve or nonconductive barrier from all other conductors.
If energy limited cable or equivalent is not used within the enclosure, then the following
guidelines do not apply. In that case,be sure to follow standard wiring practices.
Wiring Entering Enclosure Non-Power Limited Wiring
Wiring entering the enclosure from the bottom and right side of the backbox is
considered non-power limited wiring. Wiring must be in the shortest route and must
not overlap any other wiring.
Power Limited Wiring
Wiring entering the enclosure from the top and the left side of the backbox is
considered power limited. Wiring must be in the shortest route and must not overlap
any other wiring.
Use the existing lances in the backbox to dress the wires as needed to maintain
separation of power limited and non-power limited wiring.
Use the existing lances on the adapter plate to dress the wires as needed to main-
tain separation of power limited and non-power limited wiring.
Install Wiring The primary mains input must have a separate or dedicated circuit breaker. Wire in
accordance with local codes and Article 760 of NEC.
1. Remove the knockouts in the backbox for the entry of field wiring.
2. Pull all field wiring into the backbox. Do not dress the wiring until the
location of all the equipment is known.
3. Install the wiring from the external power source to the approximate
location of the power supply.
Siemens Industry, Inc.
Building Technologies Division
A6V10328630_en--_b9
Cyber security disclaimer
Siemens products and solutions provide security functions to ensure the secure operation of building comfort,
fire safety, security management and physical security systems. The security functions on these products and
solutions are important components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is
customized to individual security needs. Such a security concept may result in additional site-specific preventive
action to ensure that the building comfort, fire safety, security management or physical security system for your
site are operated in a secure manner. These measures may include, but are not limited to, separating networks,
physically protecting system components, user awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact your Siemens sales or
project department. We strongly recommend customers to follow our security advisories, which provide infor-
mation on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada, Ltd.
1577 North Service Road East
Oakville, Ontario
L6H 0H6 Canada
Document ID A6V10328630_en--_b

Other Siemens Indoor Fireplace manuals

Siemens LGA41.153A27 User manual

Siemens

Siemens LGA41.153A27 User manual

Siemens LFL1.148 User manual

Siemens

Siemens LFL1.148 User manual

Popular Indoor Fireplace manuals by other brands

Canvas HANOVER 064-4016-8 Assembly instructions

Canvas

Canvas HANOVER 064-4016-8 Assembly instructions

Heatilator SC60 owner's manual

Heatilator

Heatilator SC60 owner's manual

Montigo DelRay DRL3613NI-2 Installation & maintenance manual

Montigo

Montigo DelRay DRL3613NI-2 Installation & maintenance manual

Home Decorators Collection EDENFIELD 365-302-121 Use and care guide

Home Decorators Collection

Home Decorators Collection EDENFIELD 365-302-121 Use and care guide

Regency Horizon HZ42E-NG Owners & installation manual

Regency

Regency Horizon HZ42E-NG Owners & installation manual

Kozy-World EF4901 Installation instructions and homeowner's manual

Kozy-World

Kozy-World EF4901 Installation instructions and homeowner's manual

Home Decorators Collection SP6977 quick start guide

Home Decorators Collection

Home Decorators Collection SP6977 quick start guide

Dimplex Opti-V PGF10 instructions

Dimplex

Dimplex Opti-V PGF10 instructions

Logaire Christchurch Operation manual

Logaire

Logaire Christchurch Operation manual

Dimplex X1B Black user manual

Dimplex

Dimplex X1B Black user manual

Majestic fireplaces Arch Screen Door Kit GABS4S0 installation instructions

Majestic fireplaces

Majestic fireplaces Arch Screen Door Kit GABS4S0 installation instructions

Charlton & Jenrick INFINITY 880 BF owner's manual

Charlton & Jenrick

Charlton & Jenrick INFINITY 880 BF owner's manual

Dimplex Figaro FGA15 user manual

Dimplex

Dimplex Figaro FGA15 user manual

Element4 SUMMUM 100 Series installation manual

Element4

Element4 SUMMUM 100 Series installation manual

Quadra-Fire 3100-I installation manual

Quadra-Fire

Quadra-Fire 3100-I installation manual

Hearth & Home MEZZO48 installation instructions

Hearth & Home

Hearth & Home MEZZO48 installation instructions

Martin MPL PENINSULA 53D9042 Installation and maintenance manual

Martin

Martin MPL PENINSULA 53D9042 Installation and maintenance manual

FMI (V)B42 OWNER'S OPERATION AND INSTALLATION MANUAL

FMI

FMI (V)B42 OWNER'S OPERATION AND INSTALLATION MANUAL