manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Network Hardware
  8. •
  9. Siemens FastConnect RJ45 Plug 90 User manual

Siemens FastConnect RJ45 Plug 90 User manual

Assembly Instructions for SIMATIC NET Industrial Ethernet FastConnect RJ45 Plug 90 6GK1901-1BB20-2A..
Copyright © 2014 Siemens AG
1. Use the green knife cassette
6GK1901-1GB01 (5.1 mm knife
clearance) in the stripping tool.
If your stripping tool was supplied with a
yellow knife cassette, the cutting depth must
be adjusted with the middle socket-head
screw after fitting the new cassette!
2. Take the stripping tool in your right hand.
3. Measure the cable length against the
measuring template. Use your left index
finger as the limit stop.
4. Insert the cable into the stripping tool.
Your left index finger is the limit stop.
5. Tighten the stripping tool fully.
6. To strip the insulation, turn the tool in the
direction of the arrow
- approx. 4 times for PVC insulation,
- approx, 8 times for PUR insulation.
7. Keeping the stripping tool closed, pull it
off the end of the cable along with the
jacket and remnants of the shield.
8. If the white filler is not removed with the
insulation, remove it and the transparent
protective foil with your hand.
9. Cut off the dummy cores.
10. Spread out the wires according to the
color markings on the contact elements
of the FC RJ45 plug.
11. Open the holder cover until it latches
and push in the wires according to their
color coding* as far as the limit stop in
the holder cover
12. Push the cable into position as shown in
the picture (see arrows). Press down
the contact elements as far as the limit
stop to contact the wires.
13. Close the cover and turn the locking
mechanism in the direction of the arrow
as far as possible with your hand.
14. Insert a 2.5 mm screwdriver into the
hole in the locking mechanism and turn
it as far as the limit stop.
15. The connector is correctly locked when
the opening of the locking mechanism
is pointing to the side and the surfaces
are flush with the surface of the
connector.
16. If there is little space, release the
connector catch with a screwdriver (2.5
mm blade width).
Notes:
Replace the knife cassette if the cut edges
become ragged or after approx.·
1500 operations on cables with PVC
outer jackets·
150 operations on cables with PUR
outer jackets
The piercing contacts of the FC RJ45 plug
can be released and recontacted up to 10
times. Cable ends that have already been
pierced must not be used again but must be
cut off.
Don’t pull while unlocking the plug.
To create a crossover cable, combine the
wires in the connector at one end according
to the following scheme:
Connect white with yellow
Connect blue with orange.
You will find information on network structures in the SIMATIC NET Industrial Ethernet Networking Manual
green
5
18
90o
38mm
Montageanleitung für SIMATIC NET Industrial Ethernet FastConnect RJ45 Plug 180 6GK1901-1BB20-2A..
SIMATIC NET
Produktinformation
Product Information Stand / Dated / 01/2014
Montageanleitung für / Assembly Instructions for
SIMATIC NET Industrial Ethernet
FastConnect RJ45 Plug 90 6GK1901-1BB20-2A..
Konfektionieren von/Assembling the 6GK1901-1BB10-2A.. an/with
IE FC TP Standard Cable GP 2x2 6XV1 840-2AH10
IE FC TP Flexible Cable GP 2x2 6XV1 870-2B
IE FC TP Trailing Cable GP 2x2 6XV1 870-2D
IE FC TP Trailing Cable 2x2 6XV1 840-3AH10
IE TP Torsion Cable GP 2x2 6XV1 870-2F
IE FC TP Marine Cable 2x2 6XV1 840-4AH10
IE FC TP Food Cable 2x2 6XV1 871-2L
IE FC TP Festoon Cable GP 2x2 6XV1 871-2S
IE FC TP FRNC Cable GP 6XV1 871-2F
IE FC TP Standard Cable 6XV1840-2AU10
Nachfolgend finden Sie Informationen in deutscher Sprache. Die aktuellen Hinweise finden Sie auf folgender
Internetseite: http://support.automation.siemens.com "Produktsupport".
You will find information below in English. You will find the latest information on the following Internet page:
http://support.automation.siemens.com "Product Support".
A5E0328643
A
5E00328643-3
© SIEMENS AG 2014
Ä
nderungen vorbehalten
Subject to change
Montageanleitung für SIMATIC NET Industrial Ethernet FastConnect RJ45 Plug 180 6GK1901-1BB20-2A..
Wir haben den Inhalt der Druckschrift auf Über-einstimmung mit dem
beschriebenen Werkzeug geprüft. Dennoch können Abweichungen
nicht ausgeschlossen werden, so daß wir für die vollständige
Übereinstimmung keine Gewähr übernehmen. Die Angaben in der
Druckschrift werden jedoch regelmäßig überprüft. Notwendige
Korrekturen sind in den nachfolgenden Auflagen enthalten. Für
Verbesserungsvorschläge sind wir dankbar.
Technische Änderungen vorbehalten.
Weitergabe sowie Vervielfältigung dieser Unterlage, Verwertung und
Mitteilung ihres Inhalts nicht gestattet, soweit nicht ausdrücklich
zugestanden. Zuwiderhandlungen verpflichten zu Schadenersatz. Alle
Rechte vorbehalten, insbesondere für den Fall der Patenterteilung
oder GM-Eintragung.
Copyright © Siemens AG 2014
A
ll Rights Reserved
Wichtiger Hinweis
Wir weisen darauf hin, daß der Inhalt dieser Betriebsanleitung nicht Teil einer früheren oder bestehenden Vereinbarung, Zusage oder eines
Rechtsverhältnisses ist oder diese abändern soll. Sämtliche Verpflichtungen von Siemens ergeben sich aus dem jeweiligen Kaufvertrag, der
auch die vollständige und allein gültige Gewährleistungsregel enthält. Diese vertraglichen Gewährleistungsbestimmungen werden durch die
Ausführungen dieser Betriebsanleitung weder erweitert noch beschränkt.
Wir weisen außerdem darauf hin, daß aus Gründen der Übersichtlichkeit in dieser Betriebsanleitung nicht jede nur erdenkliche
Problemstellung im Zusammenhang mit dem Einsatz dieses Werkzeugs beschrieben werden kann. Sollten Sie weitere Informationen
benötigen oder sollten besondere Probleme auftreten, die in der Betriebsanleitung nicht ausführlich genug behandelt werden, können Sie die
erforderliche Auskunft über die örtliche Siemens-Niederlassung anfordern.
WARNUNG !
Das in der Anleitung beschriebene Werkzeug ist nur für das Abisolieren der SIMATIC NET Industrial
Ethernet FastConnect Leitungen bestimmt. Bei anderweitiger Verwendung kann es zu Unfällen oder zur
Zerstörung von Werkzeug und Leitung kommen.
Das Werkzeug darf auf keinen Fall an Leitungen die unter Spannung stehen benutzt werden.
Weitere Informationen zum Netzaufbau finden Sie im SIMATIC NET Industrial Ethernet Netzhandbuch
Anforderung an die Qualifikation des Personals
Qualifiziertes Personal im Sinne dieser Betriebsanleitung bzw. der Warnhinweise sind Personen, die mit Aufstellung,
Montage, Inbetriebsetzung und Betrieb dieses Produktes vertraut sind und über die ihrer Tätigkeit entsprechenden
Qualifikation verfügen und in erster Hilfe geschult sind.
_________________________________________________________________________________
We have checked the contents of this manual for agreement with this
tool described. Since deviations cannot be precluded entirely, we
cannot guarantee full agreement. However, the data in this manual
are reviewed regularly and any necessary corrections included in
subsequent editions.Suggestions for improvement are welcome.
Technical data subject to change.
The reproduction, transmission or use of this document or its contents
is not permitted without express written authority. Offenders will be
liable for damages. All rights, including rights created by patent grant
or registration of a utility or design, are reserved.
Copyright © Siemens AG 2014
A
ll Rights Reserved
Note
We would point out that the contents of this product documentation shall not become a part of or modify any prior or existing agreement,
commitment or legal relationship. The Purchase Agreement contains the complete and exclusive obligations of Siemens. Any statements
contained in this documentation do not create new warranties or restrict the existing warranty.
We would further point out that, for reasons of clarity, these operating instructions cannot deal with every possible problem arising from the
use of this device. Should you require further information or if any special problems arise which are not sufficiently dealt with in the operating
instructions, please contact your local Siemens representative.
WARNING ! The tool and plug-in connector described in the manual must only be used in conjunction with SIMATIC
NET Industrial Ethernet FastConnect cables. If used elsewhere, accidents may occur or tools, connector
and cable may be irreparably damaged.
The tool and plug-in connector must not be used on live cables under any circumstances.
CL/CSA-Rating The units are intended for communication circuits operating at 175 mA or less
and a maximum 56.5 V dc, ringing voltage not to exceed 150 Vrms or for data circuits operating
at 30 V ac, 42 V dc, 100 mA.
For more detailed information on setting up networks, refer to the SIMATIC NET Industrial Ethernet
Network Manual
Personnel qualification requirements
Qualified personnel as referred to in the operating instructions or in the warning notes are defined as persons
who are familiar with the installation, assembly, startup and operation of this product and who possess the
relevant qualifications for their work and have a First Aid qualification.
Montageanleitung für SIMATIC NET Industrial Ethernet FastConnect RJ45 Plug 180 6GK1901-1BB20-2A..
1. Verwenden Sie im Abisolierwerkzeug die
grüne Messerkassette 6GK1901-1GB01
(5,1 mm Messerabstand)!
Bei Abisolierwerkzeugen, die mit gelber
Messerkassette ausgeliefert wurden, ist
nach dem Austausch der Messerkassette
mit der mittleren Imbusschraube die
Schnitttiefe zu justieren!
2. Nehmen Sie das Abisolierwerkzeug in die
rechte Hand.
3. Messen Sie die Leitungslänge durch
Anlegen der Leitung an die
Maßschablone ab.
Benutzen Sie den Zeigefinger der linken
Hand als Anschlag.
4. Legen Sie die Leitung in das
Abisolierwerkzeug ein. Der Zeigefinger
der linken Hand bildet den Anschlag.
5. Spannen Sie das Abisolierwerkzeug bis
zum Anschlag.
6. Drehen Sie das Abisolierwerkzeug zum
Abisolieren der Leitung bei
-PVC-Isolierung ca. 4 mal, bei
-PUR-Isolierung ca. 8 mal
in Pfeilrichtung.
7. Ziehen Sie das Abisolierwerkzeug im
geschlossenen Zustand mit den Mantel-
und Schirmresten vom Leitungsende ab.
8. Falls beim Abisolieren die weiße
Füllmasse nicht mit abgezogen wurde,
entfernen Sie diese ebenso wie die
transparente Schutzfolie durch Abziehen
von Hand.
9. Schneiden Sie die Blindader ab.
10. Fächern Sie die Adern gemäß den
Farbmarkierungen auf den Kontaktier-
elementen des FC RJ45 Plugs auf.
11. Öffnen Sie die Aufnahmeklappe, bis
diese einrastet. Führen Sie die Adern
bis zum Anschlag in die Kontaktier-
elemente des FC RJ45 Plug ein
12. Schieben Sie das Kabel in Position wie
im Bild dargestellt (siehe Pfeile).
Drücken Sie die Kontaktierelemente bis
zum Anschlag hinunter.
13. Schließen Sie den Deckel und drehen
Sie das Verschlussstück in Pfeilrichtung
soweit, wie dies von Hand möglich ist.
14. Stecken Sie einen Schraubendreher
2,5 mm durch die Bohrung im
Verschlussstück und drehen Sie bis
zum Anschlag weiter.
15. Der Stecker ist korrekt verriegelt, wenn
die Öffnung des Verschlussstücks zur
Seite gerichtet ist und die Seitenflächen
plan mit dem Stecker verlaufen.
16. Entriegeln Sie den Stecker bei
beengten Einbauverhältnissen mit einen
Schraubenzieher (2,5 mm
Klingenbreite).
Hinweise:
Erneuern Sie die Messerkassette bei
unsauberen Schnittergebnissen bzw. nach
ca.
1500 Arbeitsgängen bei Leitungen mit
PVC Außenmantel
150 Arbeitsgängen bei Leitungen mit
PUR Außenmantel
Die Schneidklemm-Kontakte des FC RJ45
Plug können bis zu 10 Mal gelöst und neu
kontaktiert werden.
Kontaktierte Leitungsenden dürfen nicht
nochmals kontaktiert werden sondern
müssen abgeschnitten werden.
Entriegeln Sie den Stecker nicht unter Zug.
Für die Herstellung eines Verbindungs-
kabels mit gekreuzten Adern kombinieren
Sie an einem Kabelende die Adern mit den
Farbmarkierungen im Stecker nach
folgendem Schema:
weiß mit gelb verbinden
blau mit orange verbinden.
Weitere Hinweise zum Netzaufbau finden Sie im SIMATIC NET Industrial Ethernet Netzhandbuch
5
18
grün
90o
38 mm

Other Siemens Network Hardware manuals

Siemens SIMATIC PN/CAN LINK User manual

Siemens

Siemens SIMATIC PN/CAN LINK User manual

Siemens NK8000 MP.4.60 Parts list manual

Siemens

Siemens NK8000 MP.4.60 Parts list manual

Siemens SIMATIC NET SCALANCE X-100 Series User manual

Siemens

Siemens SIMATIC NET SCALANCE X-100 Series User manual

Siemens SIMATIC NET RUGGEDCOM RX1536 User manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RX1536 User manual

Siemens PROFIBUS DP-V1 User manual

Siemens

Siemens PROFIBUS DP-V1 User manual

Siemens SIMATIC NET RUGGEDCOM APE Instruction sheet

Siemens

Siemens SIMATIC NET RUGGEDCOM APE Instruction sheet

Siemens SIRIUS 3RA2130 User manual

Siemens

Siemens SIRIUS 3RA2130 User manual

Siemens Rider 11, Rider 13 H,Rider 11 Bio Instruction manual

Siemens

Siemens Rider 11, Rider 13 H,Rider 11 Bio Instruction manual

Siemens RUGGEDCOM MX5000RE Technical Document

Siemens

Siemens RUGGEDCOM MX5000RE Technical Document

Siemens SIMATIC NET PROFIBUS OBT User manual

Siemens

Siemens SIMATIC NET PROFIBUS OBT User manual

Siemens SIMATIC NET User manual

Siemens

Siemens SIMATIC NET User manual

Siemens RUGGEDCOM WIN5237 User manual

Siemens

Siemens RUGGEDCOM WIN5237 User manual

Siemens SIMATIC NET SCALANCE W M766 Series User manual

Siemens

Siemens SIMATIC NET SCALANCE W M766 Series User manual

Siemens WTT662 Series User manual

Siemens

Siemens WTT662 Series User manual

Siemens SICAM SGU 7XV5676 User manual

Siemens

Siemens SICAM SGU 7XV5676 User manual

Siemens SCALANCE S615 User manual

Siemens

Siemens SCALANCE S615 User manual

Siemens SCALANCE W788C-2 User manual

Siemens

Siemens SCALANCE W788C-2 User manual

Siemens SIVACON 8PS BD01 Series User manual

Siemens

Siemens SIVACON 8PS BD01 Series User manual

Siemens SINUMERIK 840Di sl Parts list manual

Siemens

Siemens SINUMERIK 840Di sl Parts list manual

Siemens SIMATIC NET User manual

Siemens

Siemens SIMATIC NET User manual

Siemens 2000592-001 User manual

Siemens

Siemens 2000592-001 User manual

Siemens RUGGEDCOM WIN5149 User manual

Siemens

Siemens RUGGEDCOM WIN5149 User manual

Siemens SIMATIC NET SCALANCE W774-1 User manual

Siemens

Siemens SIMATIC NET SCALANCE W774-1 User manual

Siemens SIMATIC IPC427E User manual

Siemens

Siemens SIMATIC IPC427E User manual

Popular Network Hardware manuals by other brands

Honeywell FUSION STREAMER user guide

Honeywell

Honeywell FUSION STREAMER user guide

Advantech B+B SMARTWORX ESWGP512 4SFP T user manual

Advantech

Advantech B+B SMARTWORX ESWGP512 4SFP T user manual

Avaya G700 Quick start for hardware installation

Avaya

Avaya G700 Quick start for hardware installation

Huawei Lampsite RHUB3908 Maintenance Guide

Huawei

Huawei Lampsite RHUB3908 Maintenance Guide

Paradyne COMSPHERE 6700 Series user guide

Paradyne

Paradyne COMSPHERE 6700 Series user guide

Lenze E84AZESM Series Mounting instructions

Lenze

Lenze E84AZESM Series Mounting instructions

LumenRadio W-BACnet manual

LumenRadio

LumenRadio W-BACnet manual

NetApp AFF A250 manual

NetApp

NetApp AFF A250 manual

AVYCON AVR-HN516P16A quick start guide

AVYCON

AVYCON AVR-HN516P16A quick start guide

NI PXIe-4303 USER GUIDE AND SPECIFICATIONS

NI

NI PXIe-4303 USER GUIDE AND SPECIFICATIONS

NCast Telepresenter M4 Reference manual

NCast

NCast Telepresenter M4 Reference manual

National Instruments NI-9206 Getting started

National Instruments

National Instruments NI-9206 Getting started

Valcom VIP-812A quick start guide

Valcom

Valcom VIP-812A quick start guide

Dialogic DM/IP481-2T1-PCI-100BT Quick install card

Dialogic

Dialogic DM/IP481-2T1-PCI-100BT Quick install card

Allied Telesis AT-TRAY1 Specifications

Allied Telesis

Allied Telesis AT-TRAY1 Specifications

Monacor DN-1218P operating instructions

Monacor

Monacor DN-1218P operating instructions

Vivotek ND8401 user manual

Vivotek

Vivotek ND8401 user manual

HMS Networks Anybus Wireless Bolt LTE Startup guide

HMS Networks

HMS Networks Anybus Wireless Bolt LTE Startup guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.