Siemens CDC-4 User manual

SiemensSiemens
SiemensSiemens
Siemens IndustryIndustry
IndustryIndustry
Industry,,
,,
,Inc.Inc.
Inc.Inc.
Inc.
BuildingBuilding
BuildingBuilding
Building
TT
TT
Tecec
ecec
echnologies Dihnologies Di
hnologies Dihnologies Di
hnologies Divisionvision
visionvision
vision
P/N 315-034200-9
INTRODUCTION The Model CDC-4 from Siemens Industry, Inc., is a card that
allows conventional detectors to be used on the FireFinder-XLS
system. It provides four Class A or Class B conventional detec-
tion zones. Each zone can support two-wire photoelectric or
ionization compatible smoke detectors and an unlimited number
of normally open circuit closure devices. The module also
supports Siemens Fire Safety flame and beam detectors.The
relay base, remote lamp and audible base may also be used with
the CDC-4.The CDC-4 uses one network address on the
FireFinder-XLS system. It has diagnostic LED indicators showing
module status and the status of each zone.
OPERATION Activation of any device on the circuit initiates a zone alarm and
causes any previously programmed functions to operate. Any
circuit in an alarm or trouble condition is displayed on the PMI/
PMI-2/PMI-3.
The CDC-4 is designed to function in a local degrade mode
during failure of the FireFinder-XLS main processor or during
the loss of the system communication network. While in the
degrade mode, the CDC-4 can report both alarm and trouble
conditions and can activate local outputs on other modules
within the same enclosure.
The maximum zone alarm current can be set to either 175mA
or 100mA and is set in pairs for zones 1/2 and 3/4. When a
compatible detector is selected in the Zeus Programming Tool,
the maximum zone alarm current is automatically set by the
CDC-4. Detectors requiring the 100mA zone current limit (see
table on page 11) cannot be used on the same zone pair as
detectors requiring the 175mA zone current limit (see table on
pages 7-11).
CDC-4 zones may be configured either as alarm-causing or
supervisory-causing, if allowed by the local Authority Having
Jurisdiciton.
Do not use shorting devices on circuits with accessories on them.The shorting
devices will lower the zone voltage to a point where the accessories will not operate.
Figure 1
CDC-4 Conventional
Detector Card
Conventional Detector Card
Installation Instructions
Model CDC-4

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-92
Any or all of the CDC-4 circuits may be programmed to operate with Alarm Verifica-
tion. This allows the automatic verification of alarm conditions caused by smoke
detectors in order to prevent nuisance alarms. For further information, refer to the
FireFinder-XLS Manual, P/N 315-033744.
When upgrading the firmware in the CDC-4, be sure to check the PC board version.
Version 2.0 and above firmware are only compatible with PC board P/N 580-034888.
If version 2.0 or above firmware is uploaded into the older version of the CDC-4, the
PMI/PMI-2/PMI-3 displays “ROM SW Version Error”. The PC board revision number is
printed on the back of the CDC-4 board.
Controls and Indicators The front panel of the CDC-4 contains one reset switch, sixteen LEDs, and three
HNET address switches as shown in Figure 1.
A reset switch is located on the top of the front panel. Pushing the reset switch re-
initializes the CDC-4 operation (similar to a cold boot).
The LEDs follow the reset switch and their functions are defined as follows:
POWER (Green) Normally ON. When illuminated, indi-
cates that power for the CDC-4 is applied
to the card.
CARD FAIL (Yellow) Normally OFF. When illuminated, indi-
cates that the card microprocessor has
failed.
HNET FAIL (Yellow) Normally OFF. When illuminated, indi-
cates that the HNET communication with
the CDC-4 has terminated and the card
goes into degrade mode (applicable only
when card resides in the HNET network).
GND FAULT (Yellow) Normally OFF. When illuminated, indi-
cates that the CDC-4 has detected either
a negative or positive ground fault.
ZONE 1 ALARM (Red) Normally OFF. When illuminated indi-
cates that an alarm condition has been
detected in Zone 1. It will stay on
continuously until the system is reset.
ZONE 1 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
that a trouble condition has been de-
tected in Zone 1. It will stay on continu-
ously until the condition is cleared.
ZONE 1 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-
cates that there is a break in the Class A
wiring in Zone 1.
ZONE 2 ALARM (Red) Normally OFF. When illuminated indi-
cates that an alarm condition has been
detected in Zone 2. It will stay on
continuously until the system is reset.

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-93
ZONE 2 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
that a trouble condition has been de-
tected in Zone 2. It will stay on continu-
ously until the condition is cleared.
ZONE 2 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-
cates that there is a break in the Class A
wiring in Zone 2.
ZONE 3 ALARM (Red) Normally OFF. When illuminated indi-
cates that an alarm condition has been
detected in Zone 3. It will stay on
continuously until the system is reset.
ZONE 3 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
that a trouble condition has been de-
tected in Zone 3. It will stay on continu-
ously until the condition is cleared.
ZONE 3 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-
cates that there is a break in the Class A
wiring in Zone 3.
ZONE 4 ALARM (Red) Normally OFF. When illuminated indi-
cates that an alarm condition has been
detected in Zone 4. It will stay on
continuously until the system is reset.
ZONE 4 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
that a trouble condition has been de-
tected in Zone 4. It will stay on continu-
ously until the condition is cleared.
ZONE 4 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-
cates that there is a break in the Class A
wiring in Zone 4.
Three rotary dial switches at the bottom of the front panel are used to set the HNET
network address of the CDC-4.
PRE-INSTALLATION The network address switches must be set prior to inserting the card into the CC-5
(refer to Figure 1):
Network Address Switches: Set the three-digit HNET network address for the
CDC-4 using the three rotary dial address switches located near the bottom of the
front panel. (Refer to Figure 1 for the location of the switches.) The address for the
CDC-4 must be the same as the address selected for it in the Zeus Programming
Tool. To set the address, turn the pointers on each of the three dials to the numbers
for the selected address. For example, if the address is 123, set the pointer for the
HUNDREDS dial to “1”, set the pointer for theTENS dials to “2”, and set the pointer
for the the ONES dial to “3”. The range of allowable addresses is from 001 to 251
(leading zeros must be used).
HNET
HUNDREDS
TENS
ONES

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-94
WIRING
Remove all system power before installation, first battery, then AC. (To power up,
connect the AC first, then the battery.)
All device field wiring to the CDC-4 is connected to the terminal blocks of the CC-5
card cage slot in which it is installed.
To Connect the External Wiring:
1. Loosen the screw of the
terminal by turning it counter-
clockwise.
2. Insert the wire into the side of
the terminal block
3. Tighten the screw of the
terminal block by turning it
clockwise.
Connect +24V from PSC-12 to terminal
17 and -24V from PSC-12 to terminal 18
of the slot in the CC-5 where the CDC
will be installed using 12-18 AWG (Refer
to Fig.2).
Refer to Figure 3. All circuits are power
limited to NFPA 70 per NEC 760. Each
detector or group of detectors must use
a two-wire circuit of at least 18 AWG,
thermoplastic fixture wire, enclosed in
conduit. If permitted by local building
codes, 18 AWG limited energy, shielded
cable without conduit may also be used.
The CDC-4 may be connected to existing
device loops that have a 3.9K or 4.7K
end-of-line resistor (1/4W, 5%) or a 50uF,
50V end-of-line capacitor installed. Always use a 50uF, 50V end-of-line capacitor for
new installations and whenever practical in existing detector loops for all detector
models except the Siemens PBA-1191, which requires a 4.7K end-of-line resistor, as
shown in Figure 3.
Total circuit resistance must not exceed 70 ohms—40 ohms if accessories (relay/
audible bases) are used.
Each detector zone can be wired Class A or Class B individually.
The screw terminals can accommodate one 12 -18 AWG or two 16-18 AWG.
All unused zones must be terminated with a 50uF capacitor (Terminals 1 and 4 for
Zone 1,Terminals 5 and 8 for Zone 2,Terminals 9 and 12 for Zone 3, andTerminals 13
and 16 for Zone 4).
12345678
910111213141516
LINE+ (OUT)
LINE+ (OUT)
LINE+ (OUT)
LINE+ (OUT)
LINE- (OUT)
LINE- (OUT)
LINE- (OUT)
LINE- (OUT)
LINE- (
RETURN)
LINE- (RETURN)
LINE- (RETURN)
LINE- (RETURN)
LINE+ (RETURN)
LINE+ (RETURN)
LINE+ (RETURN)
LINE+ (RETURN)
24V+
24V–
ZONE 1
ZONE 3
TO 24VDC FROM PSC-12
ZONE 2
ZONE 4
ONE SLOT OF CC-5 FOR CDC-4
17 18 19 20 21 22 23 24
Figure 2
Wiring 24V Power Lines

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-95
9 10 11 12 13 14 15 16
ZONE 3 ZONE 4
_
_
_++
+
EOLR
4.7K, 1/4W
P/N 140-820188
PBA-1191
ABCDEF
DO NOT
USE
LINE+
LINE-
+
EOL
50uF, 50V
P/N 100-115588
1 2 3 4 5 6 7 8
NC NC
ZONE 1
CLASS A** ZONE
2
CLASS B
LINE+ (OUT)
LINE- (OUT)
LINE+ (RETURN)
LINE- (RETURN)
LINE+
LINE-
EOL
50uF, 50V
P/N 100-115588
+
EOL
50uF, 50V
P/N 100-115588
+
IN CANADA,
MOUNT USING
MODEL EL-33
*** *
**OPERATES IN FULL CONFORMANCE WITH STYLE 6 (ULC DCLA)
***OPERATES IN FULL CONFORMANCE WITH STYLE 4 (ULC DCLB)
*
Figure 3
CDC-4 Detector Zones
NOTES:
1. All circuits can be Class A or
Class B.
2. All circuits are power limited
to NFPA 70 per NEC 760.
3. All circuits are supervised.
4. Refer to the UL Compatible
Two-Wire Detector List for
the maximum number of
detectors per zone.
5. Do not mix smoke detectors
with the PBA-1191.
6. Do not mix different
manufacturer’s smoke
detectors on the same zone.
7. Max resistance: 70 ohms/
circuit, 40 ohms/circuit if
accessories (relay/audible
bases) are used.
8. Do not use shorting devices
on circuits with accessories
on them.
9. Only one device accessory
per circuit is guaranteed to
activate on the CDC-4.
10. When mixing different
model detectors on a zone,
do not install more detectors
than the smallest number
shown in the “Number of
Detectors Per Zone” column
of the compatibility table.
For example, if installing
Siemens PE-11 and PE-3
detectors on the same zone,
do not install more than
fifteen detectors on that
zone. When configuring the
zone in Zeus, enter the
model name of the detector
with the smallest number
(PE-3 in this example).
11. Positive and negative ground
fault detected at <20K ohms
for terminals 1-16.

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-96
INSTALLATION The CDC-4 plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin
DIN connectors and can occupy any slot in the card cage. (Refer to Figure 4.)
Insert the CDC-4 card into the card guides rightside up
(lettering on the front panel is legible).
Slide the card in until the card edge connectors contact
the receptacles on the motherboard.
Verify that the DIN connectors of the card and the card-
cage aligned properly. The card can only plug in one
direction to the card cage, if it does not align, DO NOT
FORCE the card.
Place thumbs on the front panel adjacent to the captive
screws and gently apply even pressure on the card until
the connectors seat in the receptacles on the
motherboard. Secure with the captive screws.
Power up the system and verify that the CDC-4 power
LED turns ON.
INITIATING DEVICES Refer to the UL Compatible Two-Wire Detector List for the number of detectors that
may be used on a CDC-4 zone.
Refer to Figure 3 for initiating device wiring. All circuits are power limited to NFPA 70
per NEC 760. Each detector or group of detectors must use a two-wire circuit of at
least 18 AWG, thermoplastic fixture wire, enclosed in conduit. If permitted by local
building codes, 18 AWG limited energy, shielded cable without conduit may also be
used.
Total circuit resistance must not exceed 70 ohms—40 ohms if accessories (relay/
audible bases) are used.
If the smoke detector has an alarm verification function, the circuit must not be
programmed for alarm verification.
See NFPA 72 Standard for the number of normally open contact devices allowed.
See UL Compatible Two-Wire Detectors for the list of compatible devices.
For specific wiring and installation information, read the instructions provided with
each device.
Figure 4
Installing The CDC-4

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-97
ELECTRICAL RATINGS
stiucriCgnitaitinI
)ybdnats(egnaregatloV CDV8.22-7.12
tnerruCyrosivrep
uSxamenozrepAm4
tnerruCmralAxamenozrepAm571xamenozrepAm001
ylppuSrewoP
tnerruCenalPkcaBV420
tnerruCV42lan
imreTwercS
yrosivrepuS xamenozrepAm8+Am011 yrosivrepuS xamenozrepAm8+Am011
mralA xamenozrepAm023+Am011 mralA xamenozrepAm082+Am011
tnerruCenalPkcaBV2.6xamAm051
tnerruCybdnatSV42
yrosivrepuS xamenozrepAm8+Am051 yrosiv
repuS xamenozrepAm8+Am051
mralA xamenozrepAm023+Am051 mralA xamenozrepAm082+Am051

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-98
rerutcafunaMrotceteD ledoM rotceteDLU reifitnedI esaB ledoM esaBLU reifitnedI forebmuN srotceteD enoZreP
detsiLCLU
stcudorPriA slortnoCdna N-W2-WRN-W2-WR002-18654002-1865406N
stcudorPriA slortnoCdna P-W2-WRP-W2-WR002-18654002-18
65403N
rerutcafunaMrotceteD ledoM rotceteDLU reifitnedI esaB ledoM esaBLU reifitnedI forebmuN srotceteD enoZreP
detsiLCL
U
snemeiS 2911-FD2911-FD0911-BFD0911-BFD4Y
snemeiS 3-ID H3-ID 3A-ID H3A-ID
3-ID H3-ID 3A-ID H3A-ID
S3-BDS3-BD03030303
Y
Y
Y
Y
s
nemeiS 3B-ID H3B-ID 3B-ID H3B-ID I3-DAI3-DA0303 Y
Y
snemeiS A4-IDA4-IDST4-BD FT4-BD ST4-BD FT4-BD 0303 Y
snemeiS 6-ID6-IDST
4-BD FT4-BD ST4-BD FT4-BD 0303 Y
snemeiS 531-P3-TD531-P3-TDS3-BDS3-BDdetimilnUY
snemeiS 11-TD11-TD11-BD TPDA/wS3-BD 11-
BD S3-BD 0303 Y
snemeiS 121IH121IHE11-BD 11-BD E11-BD 11-BD 0303 Y
Y
snemeiS 121HO121HOE11-BD 11-BD E11-BD 11-BD 0303 Y
Y
sne
meiS 121PO121POE11-BD 11-BD E11-BD 11-BD 0303 Y
Y
snemeiS 1911-ABP1911-ABP1911-BBP1911-BBP1Y
snemeiS 3-EP T3-EP 3-EP T3-EP S3-BDS3-BD5151 Y
Y
snemeiS 3-EP T3-EP 3-EP T3-EP PLI3-DAPLI3-DA5151 Y
Y
snemeiS 11-EP11-EP11-BD P11-DA RP11-DA
11-BD P11-DA RP11-DA
030303
Y
snemeiS T11-EPT11-EP11-BD TPDA/wS3-BD 11-BD S3-BD 0303 Y
UL COMPATIBLE TWO-WIRE DETECTORS
The detectors listed in the following tables are compatible with the CDC-4 (UL
identifier CDC).The CDC-4 and all Siemens detectors shown below are ULC listed.
Contact the manufacturer for listing information on models other than Siemens.

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-99
rerutcafunaMrotceteD ledoM rotceteDLU reifitnedI esaB ledoM esaBLU reifitnedI forebmuN srotceteD enoZreP
detsiLCLU
ollopA 051-00055
ot 351-00055
051-00055
ot 351-00055
002-18654 022-18654 722-18654 032-18654 132-18654 232-18654
002-18654 022-18654 722-18654 032-18654 132-18654 232-18654
060604040406
N
ollopA 052-00055052-00055002-18654 022
-18654 722-18654 032-18654 132-18654 232-18654
002-18654 022-18654 722-18654 032-18654 132-18654 232-18654
06060
4040406
N
ollopA 053-00055053-00055002-18654 022-18654 722-18654 032-18654 132-18654 232-18654
002-18654 022-1865
4722-18654 032-18654 132-18654 232-18654
030352525203
N
ollopA 083-00055083-00055002-18654 022-18654 722-18654 03
2-18654 132-18654 232-18654
002-18654 022-18654 722-18654 032-18654 132-18654 232-18654
020251515102
N
rerutcafunaMrotceteD ledoM rotceteDLU reifitnedI esaB ledoM esaBLU reifitnedI forebmuN srotceteD enoZreP
detsiLCLU
sdrawdE B0526 B0526 B0526
100 100 100
100-B9426 100-B1526 A100-B1526
100 100 100
555555
Y
Y
Y
sdrawdE B9626 B9626 B9626 B9
626
100 100 100 100
100-B9426 100-B1526 A100-B1526 300-B1526
100 100 100 100
5
5
5
5
Y
Y
Y
Y
sdrawdE B0726 B0726 B0726 B0726
100 10
0100 100
100-B9426 100-B1526 A100-B1526 300-B1526
100 100 100 100
5
5
5
5
Y
Y
Y
Y

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-910
rerutcafunaMrotceteD ledoM rotceteDLU reifitnedI esaB ledoM esaBLU reifitnedI forebmuN srotceteD enoZreP
detsiLCLU
langiSortcelE )LSE( C02401SA/NA/N07N
langiSortcelE )LSE( RC02411SA/NA/N07N
langiSortcelE )LSE( TRC02411SA/NA/N07N
langiSortc
elE )LSE( TC02401SA/NA/N07N
langiSortcelE )LSE( C52401SA/NA/N07N
langiSortcelE )LSE( RC52411SA/NA/N07N
langiSortcelE )LSE( TRC5
2411SA/NA/N07N
langiSortcelE )LSE( TC52401SA/NA/N07N
langiSortcelE )LSE( C924A01SA/NA/N53N
langiSortcelE )LSE( TC924A01SA/NA/N53N
l
angiSortcelE )LSE( TFA/C115A01SA/NA/N53N
langiSortcelE )LSE( TFA/C815A01SA/NA/N53N
langiSortcelE )LSE( TXB/B125 )FFO1wS/
w( A01SA/NA/N53N
langiSortcelE )LSE( TXRC125 )FFO1wS/w( A11SA/NA/N53N
langiSortcelE )LSE( TXB/B825 )FFO1wS/w( A01SA/NA/N53N
l
angiSortcelE )LSE( TXRC825 )FFO1wS/w( A11SA/NA/N53N
langiSortcelE )LSE( U11601SU10600S07N
langiSortcelE )LSE( DU11601SU1060
0S07N
langiSortcelE )LSE( DU11601S01U90600S07N
langiSortcelE )LSE( TU11601SU10600S07N
langiSortcelE )LSE( 21601SU10600S07N
langi
SortcelE )LSE( DU21601SU10600S07N
langiSortcelE )LSE( DU21601S01U90600S07N
langiSortcelE )LSE( 5U31601SU10600S07N

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-911
rerutcafunaMrotceteD ledoM rotceteDLU reifitnedI esaB ledoM esaBLU reifitnedI forebmuN srotceteD enoZreP
detsiLCLU
ikihcoH 531-DCD3-DH022-4SN 022-6SN 3-BH0202 N
ikihcoH 531-DCD3-DH422-4SN 422-6SN 5-BH0202 N
ikihcoH 091-DCD3-DH022-4SN 0
22-6SN 3-BH0202 N
ikihcoH 091-DCD3-DH422-4SN 422-6SN 5-BH0202 N
ikihcoH F42-HIS3-DHD22-SH 22M-ABY 3-BH 3-BH 0202 Y
Y
ikihco
HF42-HIS3-DH422-BSH35-BH02Y
ikihcoH F42-HIS3-DHR422-CSH37-BH02Y
ikihcoH F42-HIS3-DHD422-SH 422M-ABY 5-BH 5-BH 0202 Y
Y
ikihc
oH 42-JIS3-DH022-4SN 022-6SN 3-BH5151 Y
Y
ikihcoH 42-JIS3-DH422-4SN 422-6SN 5-BH5151 Y
Y
ikihcoH F42-KLS HF42-KLS 3-DHD22-S
H22M-ABY 3-BH 3-BH 0202 Y
Y
ikihcoH F42-KLS HF42-KLS 3-DHD422-SH 422M-ABY 5-BH 5-BH 0202 Y
Y
ikihcoH F42-KLS HF42-KLS 3-D
H422-BSH35-BH0202 Y
N
ikihcoH F42-KLS LF42-KLS 3-DHR422-CSH37-BH0202 N
N
ikihcoH LF42-KLS3-DH2-BSH N2-BSH 05-BH0202 N
N
ikihc
oH H42-RLS V42-RLS 3-DH022-4SN 022-6SN 3-BH0202 N
N
ikihcoH H42-RLS V42-RLS 3-DH422-4SN 422-6SN 5-BH0202 N
N
ikihcoH 538-R
LS W538-RLS 3-DH022-4SN 022-6SN 3-BH5151 N
N
ikihcoH 538-RLS W538-RLS 3-DH422-4SN 422-6SN 5-BH5151 N
N
ikihcoH H538-RLS WH
538-RLS 5-DH422-4SN 422-6SN 5-BH5151 N
N
ikihcoH H538-RLS WH538-RLS 5-DH022-4SN 022-6SN W022-6SN
3-BH515151
N
N
N

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-912
esohthtiwsrotcetedesehtximtonoD.sledomgniwollofehtrofAm001otdetsujdasitimiltnerrucenoZ htiwelbitapmoce
rasrotcetedesehT.)4dna3senoZro2dna1senoZ(riapenozemasehtnoevobadetsil gniriwehtneewtebecnatsiserenileh
T.888430-085N/PdraobCPhtiwrehgihdna0.2noisivererawmrif .smho03deecxetontsumsecivedgnitrohsynadna4-CDCe
htraenslanimret
rerutcafunaMrotceteD ledoM rotceteDLU reifitnedI esaB ledoM esaBLU reifitnedI forebmuN srotceteD enoZreP
detsiLCLU
rosneSmetsyS )KRB( 1511A dnaPL011B PL611B A52Y
rosneSmetsyS )KRB( 0041A A/NA/N03Y
rosneSmetsyS )KRB( 1541A B1
04B,104B B604Bdna A52Y
rosneSmetsyS )KRB( *HD1541A 004HDA 52N
rosneSmetsyS )KRB( 1512A dnaPL011B PL611B A52Y
rosneSmetsyS )KRB( T0032A A/NA/N52N
rosneSmetsyS )KRB( 0042A A/NA/N52Y
rosneSmetsyS )KRB( HT0042A A/NA/N52Y
rosneSmetsyS )KRB( 1542A B104B,104B B604Bdn
aA52Y
rosneSmetsyS )KRB( *1542A 004HDA 52Y
rosneSmetsyS )KRB( HT1542A B104B,104B B604Bdna A52N
rosneSmetsyS )KRB( 1545A dna104B B1
04B A52N
rosneSmetsyS )KRB( *I004HD
HD1541( )004HD/w
AA/NA/N52N
rosneSmetsyS )KRB( *P004HD
HD1542( )004HD/w
AA/NA/N52N
.gnisuoh004HDhtiw1542ehtsiP004HDledoM.gnisuoh004HDhtiwHD1541ehtsiI004HDledoM*
rerutcafunaMrotceteD ledoM rotceteDLU reifitnedI esaB ledoM esaBLU reifitnedI forebmuN srotceteD enoZreP
detsiLCLU
rosneSmetsyS )KRB( TA0042A A/NA/N1N
rosneSmetsyS )KRB( TIA0042A A/NA/N1N

Siemens Industry, Inc.
Building Technologies Division
P/N 315-034200-913
CYBER SECURITY DISCLAIMER
Siemens products and solutions provide security functions to ensure the secure
operation of building comfort, fire safety, security management and physical security
systems. The security functions on these products and solutions are important
components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of-the-
art security concept that is customized to individual security needs. Such a security
concept may result in additional site-specific preventive action to ensure that the
building comfort, fire safety, security management or physical security system for
your site are operated in a secure manner. These measures may include, but are not
limited to, separating networks, physically protecting system components, user
awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact
your Siemens sales or project department. We strongly recommend customers to
follow our security advisories, which provide information on the latest security
threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada, Ltd.
1577 North Service Road East
Oakville, Ontario
L6H 0H6 Canada
P/N 315-034200-9Document ID A6V10239127
Table of contents
Other Siemens PCI Card manuals