Simplex 2120 Use and care manual

B!!Simplex
2120 Multiplex
Communicating Device
Transponder (CDT)
Technical Reference
0 1992 Simplex Time Recorder Co.
MUX2-21-106 (575-278)
All specifications and other information shown were current as of publication, and are subject to change without notice.
Ed 9 92
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

CAUTION
ELECTRICAL HAZARD
Disconnect electrical power when making any internal
adjustments or repairs. Installation and servicing
should be performed by qualified Simplex Representa-
tives.
batteries FIRST and AC power last. When connectmg
power to this system, connect AC power FIRST and
WARNING
This equipment generates, uses, and can radiate radio
frequency energy and if not installed and used in
accordance with the instructions manual, may cause
interference to radio communications. It has been
tested and found to comply with the limits for a Class A
computing device pursuant to Subpart J of Part 15 of
FCC Rules, which are designed to provide reasonable
protection against such interference when operated in
a commercial environment. Operation of this
equipment in a residential area is likely to cause
interference in which case the user at his own expense
will be required to take whatever measures may be
required to correct the interference.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

TABLE OF CONTENTS
INTRODUCTION ....................................................................................................................................................... 1
CDT PANEL INSTALLATION ..................................................................................................................................... 3
CDT PANEL JUMPER PLACEMENT AND SWITCH SETTINGS ............................................................................ .6
CDT PERIPHERAL SWITCH SETTINGS.. ............................................................................................................... 9
CDT CHECKOUT.. ............................................................................................................................................. 10
.....
LIST OF FIGURES
Figure No. Title Page
1 A 2120 System With CDT ................................................................................................................ 1
2 A Communicating Device Transponder ........................................................................................... 1
3 MAPNET II@Block Diagram ....... ..................................................................................................... 2
4 CDT Board To 2120 Communications Line Connections.. .............................................................. .4
5 CDT Power Supply Terminal Connections ....................................................................................... 5
6 CDT Panel Jumper And Switch Locations ....................................................................................... 6
7 CDT Monitor And Control Point Locations In Memory ..................................................................... 9
8 CDT Power Supply Terminal Connections ..................................................................................... 10
9 CDT Power Supply Terminal Connections For 12 Volt Power Option.. .......................................... 11
10 CDT Board To 2120 Communications Line Connections ............................................................... 11
11 Power Supply ................................................................................................................................. 12
12 CDT Termination TB2 .................................................................................................................... 15
13 CDT Termination TBl .................................................................................................................... 16
i
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

INTRODUCTION
The communicating device transponder (CDT) is a 2120 system component that is connected to the BMUX via
a 2120 communications channel (see Figure 1).
El
ET
A 2120 System with CDT
FIGURE 1
The CDT mounts in a 2-, 4-, or 6-unit backbox (see Figure 2). Each CDT has two transponder addresses used
to identify its location in the 2120 system (you only select the lower address via switches). Each CDT also has
monitor and control points.
A Communicating Device Transponder
FIGURE 2
1
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

The 2120 CDT allows use of addressable devices to provide individual reporting. So, if an addressable smoke
detector senses smoke, its activation will result in a report that specifically identifies the location of that detector.
Look at Figure 3. You can see that all addressable devices are connected to the CDT panel via a twisted, shielded
wire pair called MAPNET II@.
PS = Addressable Pull Station
ASD = Addressable Smoke Detector
IAM = Interface Addressable Module
ZAM = Zone Addressable Module
Up to 128 Devices Per MAPNET II@
MAPNET II@Block Diagram
FIGURE 3
As Figure 3 shows, there are four basic types of addressable devices:
l
Addressable smoke detectors (ASDs), requiring only the MAPNET II@wire pair for both data and power.
l
Addressable pull stations (APSs), requiring only the MAPNET II@wire pair for both data and power.
l
lnferface addressable modules (IAMs), requiring only the MAPNET II@wire pair for both data and power.
IAMs interface a single conventional device - such as a pull station or smoke detector - to a CDT.
l
Zone addressable modules (ZAMs), requiring the MAPNET II@wire pair for data, a pair for power and a
pair to connect the external monitor or control device wiring. A monitor ZAM interfaces a zone of
conventional alarm-initiating devices to the CDT. A control ZAM interfaces a single controlled device to
the CDT. A signal ZAM interfaces a zone of indicating devices to the CDT (signal ZAMs may require a
fourth wire pair for audio or phone riser input).
Since addressable devices have unique locations, each device’s address must be proper/y set. The address for
each device on a MAPNET II@MUST be set when you install the device.
This technical reference provides installation instructions for the CDT panel. Instructions for setting panel and device
switch settings are provided in this document.
2
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

‘.
CDT PANEL INSTALLATION
The CDT panel is shipped with cabinet drawings for use during installation. Information on reading cabinet drawings
can be found in the
2120 Multiplex System Installation
manual (MUX2-21-003).
DOCUMENTS YOU WILL NEED DURING THE INSTALLATION
l
System interconnect drawings for the communications channels, any audio and telephone risers, and all
powering.
~
l
CDT equipment cabinet drawings showing component locations and external connections.
l
M-2120~CDT wiring diagrams.
Note:
CDT cabinet drawings refer you to M-2120-CDT wiring diagrams. These wiring diagrams:
l
Tell you how the MAPNET II@and power line (if required) are connected to addressable devices.
AND
l
Tell you how conventional devices are connected to ZAMs and IAMs.
Consult your Simplex Representative if you do not receive the proper system documentation.
INSTALLATION PRECAUTIONS
A. Use twisted, shielded pair for all MAPNET II@lines.
B. Each CDT equipment cabinet should be connected to building ground via a single, unbroken conductor
(12AWG wire, typical). Conduit ground is not sufficient.
C. MAKE NO CONNECTIONS TO CDTs WITH POWER APPLIED.
D. Before applying power to CDT equipment:
l
Verify that power connections have been terminated at the proper terminals.
l
Verify that all wiring is free of grounds.
E. Apply power to equipment ONLY in the presence of a qualified Simplex Technical Representative (TR) and
in the following sequence:
l
Apply AC power first.
l
Apply battery power last.
F. NEVER APPLY OR DISCONNECT CDT EQUIPMENT POWER BY USING AN INTERCONNECT PLUG.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

c
INSTALLATION SUMMARY
The following is a set of recommended procedures to follow during CDT installation. Before you begin wiring:
l
Ensure that all system interconnection and wiring diagrams for your system are provided.
l
All backboxes (cabinets) and the associated equipment should be properly installed and grounded via
a single, unbroken conductor (12AWG, typical). Conduit ground is NOT sufficient.
Mounting
1. Install the CDT’s backbox using the information in the section entitled “Backboxes” in the
2120 Multiplex
System Installation
manual. Use the transponder number on the CDT equipment shipping carton to help you
find the cabinet’s proper location.
2. Install the CDT (and other equipment, if applicable) into the backbox.
Data and Power Connections
3. Connect the 2120 communications channel to the CDT (Figure 4). Use the system data interconnect drawing
and the appropriate CDT cabinet drawing to determine proper connections.
TBl
SHIELD
5 0
4 0
3 0
L
2 0
10
-
-
-
-
-
-
INCOMING 2120
COMMUNICATION
LINE
OUTGOING 2120
COMMUNICATION
LINE
CDT Board to 2120 Communications Line Connections
FIGURE 4
4
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

4. (If required) Connect the power line to the CDT (Figure 5). Use the system power interconnect drawing and the
appropriate CDT cabinet drawing to determine required connections. DO NOT APPLY POWER.
FACTORY
WIRED TO
NEARBY POWER AVAILABLE
TRANSPONDER FOR ADDITIONAL UNITS
-‘e R B R B R B d
TBl
666666
000000
12 1110 9 6 7 6 5 4 3 2 1 BACKPLATE
CONNECTED
TO CDT FOR
TROUBLE
REPORTS
+- +
- c- +- +
--
---
26VDC ZBVDC 26VDC 26VDC 26VDC
-
CDT POWER SUPPLY
562-464; 562462
THROUGH 562-466
(GROUND
SCREW)
NOTES:
R = RED
B = BLACK
CDT Power Supply Terminal Connections
FIGURE 5
5. Leave the MAPNET II@disconnected from the CDT panel.
Preliminary Checkout by Simplex TR
6. The TR will verify that all data, audio/telephone, and power line connections have been properly made. Then,
with power connected, the TR will verify the operation of the system’s basic components. When the TR has
completed his preliminary checkout, power down all equipment.
MAPNEl@ and Addressable Device Installation
7. If the addressable devices on the MAPNET II’ have not yet been installed, do so now.
8. Connect the MAPNET II@lines to the CDT cabinet’s contractor terminal block (shown in the cabinet drawing) and
peripheral devices (using the M-2120-CDT wiring diagrams).
Final Checkout by Simplex TR
9. Installation should now be complete. You should again contact your local TR for final checkout.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

CDT PANEL JUMPER PLACEMENT AND
SWITCH SETTINGS
The CDT panel (Figure 6) contains three switch packages (SW1 through SW3), a pushbutton switch (SW4) that
resets the CDT’s microprocessor when pressed, and six jumpers (JWl through JW6).
JUMPERS JUMPERS
CDT Panel Jumper and Switch Locations
FIGURE 6
SW1 is used to set the CDT’s transponder address and communications baud rate. Set switches SWl-1 and
SW1 -2 as follows:
BAUD RATE SWl-1 SWl-2
9600 OFF OFF
4800 ON ON
2400
OFF ON
1200 ON OFF
Switches SW1 -3 through SW1 -8 specify the transponder address (one less than the transponder number).
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

SWITCH NUMBER BINARY WEIGHT
SW1 -8 32
SW1 -7 16
SW1 -6 8
SW1 -5 4
SW1 -4 2
SW1 -3 1
FOR SWl, SW2, AND SW3:
OPEN SWITCH = LOGICAL 1 = OFF
CLOSED SWITCH = LOGICAL 0 = ON
Add the binary weight of the OFF switches to obtain the address. Two examples are provided below.
BINARY WEIGHT SW1 SWITCH ADDRESS 34 ADDRESS 51
32 8 OFF OFF
16 7 ON OFF
8 6 ON ON
4 5 ON ON
2 4 OFF OFF
1 3
ON
OFF
Note:
Any CDT requires two consecutive transponder addresses, even though we set only the lower address
via switches.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

‘SW2 is used to tell the CDT how many monitor points are present (from zero to 128 possible monitor devices).
Switches SW3-1 through SW3-7 are used to tell the CDT how many control points are present (from zero to 64
possible control devices).
Switch SW3-8 is used to indicate whether the MAPNET II@is single line or McCulloh loop. Set SW3-8 ONto indicate
McCulloh loop; set SW3-8 OFF to indicate single line.
CAUTION:
At least one switch on either SW2 or SW3 must be OFF or the CDT panel will not operate.
Jumpers JWl through JW6 are set as indicated below.
JW7 and JWZ are IN, and are not normally field-alterable.
JW3 is IN for local mode operation.
JW4 is OUT, and is not normally field-alterable.
JW5 is IN when 2120 communications occur via RS232C interface, and OUT for normal communications.
JW6 is OUT when 2120 communications occur via RS232C interface and IN for normal communications.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

The addresses for all CDT monitor devices are set in the same way.
The addresses for all CDT control devices are set in the same way.
Note:
Control ZAM Addressing begins with device number 128 and ends with device number 65 (64 possible
control devices per CDT panel). This numbering scheme exists because of the way in which the CDT panel’s
internal memory is laid out. Thus, the first control device on a MAPNET II@ - as far as addressing is
concerned - will “occupy” the 128th position in CDT memory, the second control device will “occupy” the
727th position in CDT memory, etc.
If you look at Figure 7 below, you can see that monitor point addressing begins at the “bottom” of CDT
memory, while control point addressing begins at the “top” of CDT memory.
ADDRESS
1 2 3 4
116 117 118 119
ETC.
ETC.
t
12345678
16 17 18 19 20 21 22 23
1 2345678
8 9 10 11 12 13 14 15
12345678
0 1 2 3 4 5 6 7
~-POINT #
--ADDRESS
-POINT #
-ADDRESS
CDT Monitor and Control Point Locations in Memory
FIGURE 7
9
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

CDT CHECKOUT
CAUTION:
These procedures must be performed in the presence of (or by) a Simplex Technical Representative.
Do not apply power to equipment unless the TR is present.
CDT checkout is broken up into preliminary checkout and final checkout.
CDT PRELIMINARY CHECKOUT
CAUTION:
ENSURE THAT ALL POWER IS OFF BEFORE PROCEEDING.
Note 1:
To simplify preliminary CDT checkout, group CDTs according to the power source. Check out all CDTs
associated with the same supply and then proceed to the next group of CDTs.
Note 2:
Perform Steps 1 through 7 for CDT cabinets containing a CDT power supply board (P/N 562-464).
1. Verify that 120VAC is properly terminated at TB2 of the power supply as shown in Figure 8.
FACTORY
WIRED TO
NEARBY
TRANSPONDER
POWER AVAILABLE
FOR ADDITIONAL UNITS
--+-+-+
U-U
28VDC 2BVDC 28VOC
CONNECTED
TO CDT FOR
TROUBLE
REPORTS
- +- +- +
u-L-J
2BVDC 28VDc 28VDC
BACKPLATE
CDT POWER SUPPLY
562464; 562482
THROUGH 562-488
(GROUND
SCREW)
NOTES:
R = RED
B = BLACK
CDT Power Supply Terminal Connections
FIGURE 8
Note:
If any contractor wiring is connected to TBl of the power supply, proceed to Step 2. If no contractor
wiring is connected to TBl , proceed to Step 4.
2. Disconnect the ground wire connected to TB2-3 of the supply. Then, use your VOM to check for shorts to
ground on any contractor wiring connected at TBl
Requirement:
VOM indicates no shorts between each wire and ground. If this requirement is not met for all
contractor wiring connected at TBl , then troubleshoot and repair the wiring fault.
3. Check for shorts between each ‘I+” (red) and ‘I-” (black) contractor-installed wire connected at TBl on the
power supply.
Requirement:
VOM indicates no “+ ” to “ - ” shorts. If this requirement is not met for each “+ ” and “ - ” wire
connected at TBl , then check the outgoing wiring for “ + ” to “ - ” shorts. Repair the wiring as necessary.
4. Perform Steps 5 through 7 only if the CDT power supply is provided with the 12 volt power option (P/Ns 562-
483, -484, -487, and -488).
10
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Note:
If any contractor wiring is connected to TB3 of the power supply, proceed to Step 5. If no contractor
wiring is connected to TB3, proceed to Step 7.
5. Use your VOM to check for shorts to ground on any contractor wiring connected at TB3 as shown in Figure 9.
POWER AVAILABLE
FOR ADDITIONAL UNITS
67654321
Gddd
12VDC 12VDC 12VDC 12VDC
CDT Power Supply Terminal Connections
for 12 Volt Power Option
FIGURE 9
Requirement:
VOM indicates no shorts between each wire and ground. If this requirement is not met for all
wiring connected at TB3, then troubleshoot and repair the wiring fault.
6. Check for shorts between each “+” (red) and “-I’ (black) contractor-installed wire connected at TB3 of the
supply.
Requirement:
VOM indicates no “ + ” to “ - ” shorts. If this requirement is not met for each ‘I+” and “--I’ wire
connected at TB3, then check the outgoing wiring for “+ )(to ‘I-” shorts.
7. Reconnect the ground wire removed in Step 2.
8. Locate the CDT panel board (P/N 562-562).
9. Verify that the incoming and outgoing 2120 communications lines are connected to the CDT at TBl as shown
in Figure 10.
INCOMING 2120
COMMUNICATION
CDT Board to 2120 Communications Line Connections
FIGURE 10
11
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Note:
Once you have checked out all of the equipment powered by the CDT power supply, proceed to Step
10.
10. Check each CDT panel’s jumper placement and switch settings as described in the section, CDT Panel Jumper
Placement and Switch Settings, of this publication.
11. Apply power to the CDT power supply by:
l
Applying AC power first.
l
Connecting the batteries last.
12. Set your VOM to the GODCV scale. Connect it across the red (+ ) and black (0 volts) battery connectors.
13. If VOM displays 27 volts, proceed to Step 14. Otherwise, perform the ET/CDT Battery Adjustment procedure.
ET/CDT Battery Adjustment Procedure
Caution:
To be performed by Simplex personnel only.
Note:
The protective cardboard cover over the power supply must be removed to access components.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
0.
P.
Q.
Ft.
S.
Locate R2, Pl, R15, R6, and R21 (Figure 11).
Remove the batteries first and then AC power.
Disconnect connector Pl
Reconnect AC power only.
Adjust R15 fully clockwise.
Connect the VOM across the RED (+) and BLACK (0 volts) battery connections.
Adjust R6 until VOM reads about 26 volts.
Connect the VOM across the left side of R2 (+) and the BLACK battery connector (0 volts).
SLOWLY adjust R15. At some point, the voltage reading on the VOM will SUDDENLY DROP from about
33 volts to approximately 10 volts. This is the TRIP POINT. Stop at this point.
Now, SLOWLY adjust R6 clockwise until the
VOM reading trips back to about 33 volts.
Stop at this point.
Connect the VOM as in Step 6 above. The VOM
should read about 28 volts.
Readjust R6 until the VOM reads about 27
Connect the VOM across TBl-1 (+) and
TBl-2 (-).
Adjust R21 until the VOM reads 28 volts.
Remove AC power.
Reconnect the Pl connector.
Re-apply AC power.
Reconnect the batteries.
Replace the protective cardboard cover
over the power supply.
Power Supply
FIGURE 11
12
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

14. Leave the power applied to this power supply and proceed to the next CDT.
15. (New 2120 installations only) Once you have checked out all CDTs in the system and all other 2120 equipment,
perform the BMUX checkout procedures in the 2120 Multiplex System Checkout Procedures manual (MUX2-
21-004).
Note:
When you finally power-up the BMUX, each CDT that comes up will report a LOCAL LOOP COMM FAIL
error message. Ignore the message for the time being; it will clear once the CDT’s MAPNET II@lines are
installed.
15. When you have completed preliminary checkout of all CDTs, remove power from them in the following
sequence:
l
Disconnect batteries first.
l
Disconnect AC last.
CDT FINAL CHECKOUT
CAUTION:
NOTIFY BUILDING PERSONNEL AND APPROPRIATE AUTHORITIES (FIRE AND POLlCf
DEPARTMENTS, ETC.) BEFORE PROCEEDING.
A. Identification of Contractor Wiring Errors
1. Before the contractor applies power to any CDTs, verify that the MAPNET II@communications lines are properly
terminated on each CDT using Figure A or B as appropriate from the M-2120-CDT wiring diagrams, or by using
Figures 12 and 13.
2. The contractor should now apply power to each system component by:
l
Applying AC power first.
l
Connecting batteries last.
3. (New 2120 installations only) Allow two minutes for the BMUX to initialize.
Note 1:
You will need the CMS file covering each CDT to locate devices reported in Step 4.
Note
2: Each CDT uses two transponder addresses; addressable devices are reported on either of the CDT
addresses.
4. Identify all CDT monitor and control device troubles. Remember: The BMUX reports CDT device troubles per
addressable device, so the ‘CDT trouble reports you receive will refer directly to specific MAPNET II@devices.
Use the first three digits of the device’s point number to determine the location of the associated CDT panel.
Note:
If you get either a LOCAL LOOP COMM FAIL or LOCAL LOOP MCCULLOH trouble report from a CDT, then
the MAPNET II@lines associated with the reported CDT are disconnected from the panel, their polarity is
reversed, or fuse Fl on the CDT panel is open.
5. If there is a string of devices on the same MAPNET II@that has troubles, look for:
0 Open wiring at a branch circuit junction box.
l
Open wiring in the branch circuit itself.
l
MAPNET II@wire pairs reversed at a branch circuit junction box.
13
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

6. Locate other troubled devices and:
l
Check device addressing using the CMS file.
l
Check device wiring.
If the wiring and~address check out properly, replace the troubled device.
Note:
If two or more devices have the same address setting, then there will be one or more troubles associated
with the devices which have duplicate switch settings. Use half-splitting to isolate the improperly
addressed devices.
B. CDT Functional Checkout
Activate all CDT peripherals and verify that the proper reports are received at the BMUX. Use SMPL operating
commands to operate CDT control or signal ZAMs. If DEVICES DO NOT REPORT, CHECK SW2 AND SW3
SETTINGS ON CDT PANEL.
14
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

-+ 24vdc
-+ 24vdc
-+ 24vdc
-+ 24vdc
-0vdc
-0vdc
-0vdc
-0vdc
EOL
CDT
TERMINAT ION
TB2
- NOT USED b I
- NOT USED m 47k
- NOT USED
-SIG SIL--l I
.DET FIST
-BROWN-OUTIOVERVOL
-EARTH TROUBLE
-SIGNAL TROUBLE
-LOW BATTERY TROUB
_ RE
.TA
‘LE
SISl
&GE
‘OR
CDT Termination TB2
FIGURE 12
15
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

1
CDT ;
TERMINATION’ 1
TBI ;
1
*
COMMON
RTS ( not used 1
XMIT
RCV
CTS (
not used 1
.DCD ( not used 1
DC COMM (-1
DC COMM (-1
DC COMM (+I
DC COMM (+I * NOTE:
DC COMM (SH)
DC COMM (SH) Terminate M
MAPNET@ GND shield at
.MAPNET@(A)
Or
,MAPNET@(B) CDT power
,MAPNET@A&B (-1 (not at T
.MAPNET%&B (-1
APNET@
ov
suPPlY
Bl-5)
CDT Termination TBl
FIGURE 13
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Other manuals for 2120
8
Table of contents
Other Simplex Marine Radio manuals
Popular Marine Radio manuals by other brands

Simons Voss Technologies
Simons Voss Technologies TRA.FP.INF2 user manual

Garmin
Garmin GTX 23 ES installation manual

Raisecom
Raisecom iTN8600-I Product description

Raymarine
Raymarine Ray101E Owner's handbook

EcoxGear
EcoxGear SOUNDEXTREME SEI-SEMRNGGE user guide

West Marine
West Marine VHF155 owner's manual