AERASGARD®KLQ-CO2 ⁄ KCO2
including mounting flange
AERASGARD®ALQ-CO2 ⁄ ACO2
Duct and on-wall air quality and CO2 sensors respectively measuring
transducers (VOC), self-calibrating, with active output
APPLICATION:
These self-calibrating microprocessor-controlled CO2and mixed gas measuring instruments are used for
the detection of air quality and ⁄ or CO2content in air within a range of 0 ppm to 2000 ppm CO2. Measuring
signals are converted into standard signals of 0 –10 V. Optional, this device can be supplied with switching
output, with 9-point LED indication, or with a combination of various output variants.
The CO2content of air is determined by a NDIR sensor. Self-calibration of the CO2measurement takes place
in cycles of ca. 7 days. In order to ensure this function, the device must be exposed to fresh air (CO2content
300...400ppm) at least once every 7 days.
The air quality detection range is calibrated for standard applications such as air quality monitoring in resi-
dential and conference rooms. The lifetime of the chemical mixed gas sensor used for this purpose is limited.
It depends on type and concentration of pollutant gases. When device-specific parameters are observed,
the expected lifetime is at least 36 months.
TECHNICAL DATA:
Power supply: ...................................................24V AC ⁄ DC
CARBON DIOXIDE:
CO2 sensor:........................................................optical sensor (NDIR), non-dispersive infrared technology
Measuring range, CO2:...............................0… 2,000 ppm CO2
Output, CO2:......................................................0-10V
Measuring accuracy, CO2:........................± 30ppm, ± 5% of final value
Pressure dependence: ...............................± 1.6% ⁄ kPa (referred to standard pressure)
Long-term stability:.......................................± 1% of final value per year
Gas exchange:..................................................by diffusion
AIR QUALITY:
Air quality sensor:..........................................VOC sensor (metal oxide)
(VOC = volatile organic compounds)
Measuring range, air quality: ..................0 …100 % (mixed gas pollution referred to calibrating gas)
Output, air quality: .........................................0 -10V (0V= clean air, 10V = polluted air)
Measuring accuracy, air quality:
...........± 20 % of final value (referred to calibrating gas)
Warm-up period: ............................................ca. 1 hour
Ambient temperature:................................0…+50°C
Electrical connection: ..................................0.14 -1.5 mm2via screw terminals on circuit board
Enclosure:...........................................................plastic, material polyamide, 30% glass-globe-reinforced,
with quick-locking screws colour pure white (similar RAL 9010)
Dimensions:.......................................................108 x 72.5 x 70mm
Cable union: .......................................................M16, including strain relief
Protective tube: ..............................................metal, Ø 20 mm, KCO2⁄ KLQ-CO2: nominal length NL= 190mm;
ACO2⁄ ALQ-CO2: nominal length NL=103mm
Process connection: ....................................by mounting flange, plastic, (included in the scope of delivery),
galvanised steel optional
Protection class: ............................................III (according to EN 60 730)
Protection type:..............................................IP 65 according to IEC 529)
Standards:
..........................................................CE conformity, electromagnetic compatibility
according to EN 61326+ A1+ A2, EMC directive 89 ⁄ 336 ⁄ EWG
Optional:...............................................................8-digit display, cutout 36x14 mm (Wx H),
for displaying actual CO2content and actual air quality
Connecting diagram ACO2⁄ KCO2Connecting diagram ALQ - CO2⁄ KLQ - CO2
KCO2
KLQ-CO2
ACO2
ALQ-CO2
ACO2
ALQ-CO2
with display