SSET CE-S 28-4MD4-0.2 Series User manual

http://www.ce-transducer.com 3rdFloor,building1, Zaimaoindustrialpark, Baoji road, Bantian, Longgangdistrict,
sales@ce-transducer.com ShenzhenCity, ChinaPostcode:518049
TwoinputtwooutputDC currentsignal
isolator
TwoinputtwooutputDC voltagesignal
isolator
Istructions
CE-S*28-**4MD4-0.2
1Overview
Themainfunctionofthesignalisolatoristoisolatedtransmit the
inputDCvoltage(current)signalintothestandardcurrentor
voltagesignal.Theproductcontainstwoefficientmicropower
isolatedpowersupplies thatprovides anisolatedpowersupplyto
thepre-stageprimarysensorwhilepoweringtheinternalsignal
processingcircuitry. Theproductsarewidelyusedinanalog
signalisolationconversionofindustrialfield,suchas
communications,powerrail,industrialcontrolandother
automation andcontrolfields
Features:
ØFullyisolatedcircuit structure:
ØTwosignalinputsareisolatedfromeachother; twosignal
outputsareisolatedfromeachother; signalinput,outputand
auxiliarypowersupplyareisolatedfromeachother;
ØUsingelectromagneticisolationtechnology,stableand
reliableperformance;
ØTheoutputportandpowerportcanwithstand2KV surge
impact;
ØTheaccuracyisbetterthan0.2;
ØProvides theisolated24Vdistributionpoweroutput,
facilitates asensorpowersupply;
ØUsing18mmthinshell guiderail installation,space
utilizationishigh;
ØWiringusingplugterminals, easywiringand maintenance.
2 Case style
Figure1,MD4case
3 Partnumber
4 Specifications
Testconditions:auxiliarypower: +24 V
Inputrange:
Voltagerange:75mV~300VDC,
Thefirstwaycurrentrange:10mA~5ADC,
Thesecond waycurrentrange 10mA~200mADC;
Output: 0-20mA, 4-20mA, 0-5V,0-10V,0-15V(special)
Note:Wheninputsignalis1-5Vor4-20mA,it isnotallowedto
outputanegativesignal.Please specifytherequirementsof
"shieldingnegativesignal"whenordering,as describedinsection
IX.1.
Powersupply:+24VDC(-15%~+20%);
Powerdistributionoutput:24VDC 3.6V/25mADC;
Accuracy:0.2;
Loadcapacity:currentoutput ≤500Ω;voltageoutput ≥2kΩ;
Temperaturedrift: ≤200ppm/ ;
Isolationvoltage:2500VDC;
Response time: ≤100 mS;
Ratedpowerconsumption:<3W;
Outputripple:<10mV
Frequencyresponse range:none;
Surgeimmunity:
Powerport three 2KV(L-N/2Ω/integratedwave)
Outputport three 2KV (L-N/40Ω/integratedwave);
Impulse immunity:
input/powerport 2KV,analogI/Oport 1KV;
Inputoverloadcapacity:
2times nominalvalueforthemeasuredvoltage(applyasecond,
repeat10 times, interval10S);
20times nominalvalueforthemeasuredcurrentapplyasecond,
repeat5times, interval300S);
Operatingtemperature:-20~70 , humidity: ≤95%(nodew);
Storagetemperature:-40~+70 .
5 ConnectionsDiagram
(Onlyforreference only, theactualapplicationtotheproduct
wiringdiagramshall prevail)
http://www.ce-transducer.com 3rdFloor,building1, Zaimaoindustrialpark, Baoji road, Bantian, Longgangdistrict,
sales@ce-transducer.com ShenzhenCity, ChinaPostcode:518049
Fig. 2wiringreference mapofCE-S#28-##4MD4
6 Installations
DIN35 rail-mountedorscrew-mountedinstallation,theinstallation
size isas showninfigure3(inmm).
Fig.3
7 Product sService
1Installation
1.1 DIN rail installationmethod:
①Thetransducerfixedon thesideofthecardslotand hook
on themountingrail;
②Pull thespringpindown;
③Clipthetransducermounton themountingrail;
④Release thespringpinandclipthetransmitteron the
mountingrail.
1.2 Screwmountingmethod:
①4mm diameterholeinthefixedplateaccordingtothe
positionofthescrewholeshowninFig.9;
②Use thescrew Φ3.5toinsert intoholeandsecureit.
2Productsfactoryhas beenaccuratelysetaccordingtothe
"productstandard".Applypowerafterdeterminethecorrect
wiring.
3Themaximumwirediameteroftheterminalblockis2mm
(16-26AWG).Removethe4mm~5mminsulationlayerfrom
theend ofthemountingwireand insert it intotheterminal
block, thentightenthescrew.
4Productsupplypowerrequires theisolationvoltage ≥2000VAC,
ACripple<10mV.Multipletransducerscanshareacommon
setofpowersupplies,butthepowercircuit cannolongerbe
usedtodriverelaysand othercanproduce spikes intheload,
inordertoavoidinterference signaltransmission tothe
transducer.
5 Thetransducersoutput0-20mA(or4-20mA),theRLstandardis
≤500Ω,and 0-5VvoltageoutputRLstandardis ≥2KΩ,can
guarantee theoutputaccuracyand linearityovertheentire
ratedinputrange.
8 Example ofproductaccuracy levelverification
1Accordingtothedefinitionofthetransducerterminalsto
connectthetestcircuit.
Figure4,testwiringdiagramofaccuracyoftwoinputstwo
outputsisolator
(Takethe CE-SU28-344MD4-0.2 as anexample)
2Thetestshall becarriedoutunderthefollowingenvironmental
conditions:
◆Powersupply:nominal 5%, ripple ≤10mV;
◆Ambienttemperature:25 °C 5°C;
◆Relativehumidity:RH (45 ~80)%;
◆Theaccuracyofthesignalsource and measurement
instrumentis0.05%above.
3Powerpreheat2mins;
4VoltageUandCurrentIinputand monitoringmethods:
Ahigh-precision high-currentmetercalibratorcandirectlyinput
ACcurrentIorvoltageVo,andrecordthedisplaydataofthe
metercalibration instrument.
5Assumingthatthefirstwayinputrangeofisolatoris0-5VDC,
output0-5VDC,thesecond wayinputrangeis0-10VDC,
outputis0-20mADC,giveinputvalueVi1and Vi2withinthe
rangeoftheisolator,theexpectedtheoreticaloutputVzandIz
oftheisolatoriscalculatedas follows:
Vz=Vi1 ÷5VDC ×5V
Iz=Vi2 ÷10VDC ×20 mA
6MeasurethefirstwayoutputvalueVoandthesecondway
outputvalueIowiththeoutputmonitoringtable:
|Vz-Vo|≤10mVisnormal, orexcessive(0-5VDC output,0.2);
|Iz-Io|≤40uAisnormal, orexcessive(0-20mADC output,0.2);
7RepeatNO.5andNO.6operations,theresultingphase errorin
eachpointarewithinthespecifiedaccuracy,thetransducer
accuracylevelisqualified.
Note: please consult withourcompanyfortheverification method
http://www.ce-transducer.com 3rdFloor,building1, Zaimaoindustrialpark, Baoji road, Bantian, Longgangdistrict,
sales@ce-transducer.com ShenzhenCity, ChinaPostcode:518049
ofothertechnicalindicators.
9 Notes
1Please payattention tothepowersupplyinformation onthe
productlabel,andthepowersupplyusedgradeofthe
transducer,otherwise it will cause theproducttobe
damaged.
2Transducerfortheintegratedstructure,notremovable,and
shouldavoidcollisionandfall.
3Thetransducersareusedinenvironmentswithstrong
electromagneticinterference.Standardprecautionsuchas
shieldingtheinputand/oroutputlines shouldbeobserved.All
lines shouldbeas short as possible. Ifagroup oftransducersare
mountedtogether,keepaspacemorethan10mmbetween
adjacentunits.
4Theinputvaluegivenon thetransducerlabelreferstotheRMS
valueoftheac signal.
5Onlyuse theeffectiveterminalofthetransducer.Theother
terminalsmaybeconnectedwiththeinternalcircuitofthe
transducer, andcan’tbeusedforotherpurposes.
6Transducerhas acertainanti-lightningability,butwhenthe
transducerinputand outputfeedersexposedtoextreme bad
environments, mustbetakenlightningprotection measures.
7Don’tdamageormodifytheproductlabelandlogo.Don’t
disassembleormodifythetransmitter,otherwise thecompany
will nolongerprovidetheproduct"three guarantees"
(replacement, return, repair) services.
8Thetransducersuse flame-retardantABSplasticshellpackage.
whichlimit temperatureis+75 .Theshell will bedeformed
withhigh-temperaturebaking,andwill affectproduct
performance.Donotuse orsavetheproductneartheheat
source. Donotbaketheproductinahigh-temperatureoven.
9Whenmeasuringthevoltageorcurrentwiththemulti meterpen,
please screwtheterminalscrewintheend,otherwise it may
notmeasurethevoltageorcurrentoutputvalue.

This manual suits for next models

2

Popular Industrial Electrical manuals by other brands

Murata GQM2195C2A9R1DB01 Series Reference sheet

Murata

Murata GQM2195C2A9R1DB01 Series Reference sheet

Murata GRM0225C1ER90BA03 Series Reference sheet

Murata

Murata GRM0225C1ER90BA03 Series Reference sheet

ABB Relion 615 series Point List Manual

ABB

ABB Relion 615 series Point List Manual

POWERSYS RECLOSER manual

POWERSYS

POWERSYS RECLOSER manual

AKO-Agrartechnik BA-1092 instruction manual

AKO-Agrartechnik

AKO-Agrartechnik BA-1092 instruction manual

ProSoft Technology inRAx MVI71-N2 user manual

ProSoft Technology

ProSoft Technology inRAx MVI71-N2 user manual

Siemens SINAMICS G110 operating instructions

Siemens

Siemens SINAMICS G110 operating instructions

Moore Industries ECT installation manual

Moore Industries

Moore Industries ECT installation manual

Murata GRM0335C1E8R5CA01 Series Reference sheet

Murata

Murata GRM0335C1E8R5CA01 Series Reference sheet

Murata GRM1555C1H821JA01 Series Reference sheet

Murata

Murata GRM1555C1H821JA01 Series Reference sheet

Murata GRM1885C1H4R0CA01 Series Reference sheet

Murata

Murata GRM1885C1H4R0CA01 Series Reference sheet

Murata GRM1555C2A4R5CA01 Series Reference sheet

Murata

Murata GRM1555C2A4R5CA01 Series Reference sheet

Murata LLA215R71C104MA14 Series Reference sheet

Murata

Murata LLA215R71C104MA14 Series Reference sheet

National Instruments PXIe-6674T CALIBRATION PROCEDURE

National Instruments

National Instruments PXIe-6674T CALIBRATION PROCEDURE

Murata GRM0335C1H8R8CA01 Series Reference sheet

Murata

Murata GRM0335C1H8R8CA01 Series Reference sheet

FEC Handheld Nutrunner HFC3000 instruction manual

FEC

FEC Handheld Nutrunner HFC3000 instruction manual

Murata GRM0335C1H7R7BA01 Series Reference sheet

Murata

Murata GRM0335C1H7R7BA01 Series Reference sheet

CONTACLIP STK1 operating instructions

CONTACLIP

CONTACLIP STK1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.