SEM1720 USER GUIDE To avoid the risk of electric shock and fire, please read this instr ctions doc ment f lly before se.
Dual channel signal conditioner designed to accept RTD, Thermocouple or Potentiometer sensors and provide isolated, industrial process output signals in mA
or Volts. Each output channel may be linked to either input sensor or to a maths function of both sensor signals. This po erful feature allo s the device to operate
in a number of different modes.
S pplier Stat s Instr ments Ltd, Stat s B siness Park, Gannaway Lane, Tewkesb ry, Glo cestershire, UK GL20 8FD.
+44 (0) 1684 296818. www.stat s.co. k
IMPORTANT SAFETY REQUIREMENTS.
Max working voltage Terminals (101 to 104) and (201 to 204) Inp ts ±24 Vdc @ 10 mA
Max working voltage Terminals (105 to 108) and (205 to 208) O tp ts ±30 Vdc @ 50 mA
Max working voltage Terminals (S1 to S2) s pply 240 Vac, ± 240 Vdc
Isolation s pply to Inp t/o tp t 4200 V
Any inp t to any O tp t 3750 V
O tp t to O tp t, Inp t to Inp t 3750 V
•This eq ipment is s itable for environment Installation category II poll tion degree 1 and is classed as "PERMANENTLY CONNECTED
EQUIPMENT". The eq ipment is intended for ind strial and commercial application only and not s itable for domestic or medical se.
•The eq ipment m st be mo nted inside an enclos re that provides protection >= IP65. In NORMAL USE, the eq ipment will only be accessed
for maintenance by q alified personnel. Please ens re the eq ipment is mo nted vertically with terminals (101 to 204) at the bottom. This
will provide maxim m ventilation and correct cold j nction compensation. This eq ipment may generate heat, ens re the enclos re size is
adeq ate to dissipate heat. Be s re to consider any other eq ipment inside the enclos re.
•The eq ipment s rfaces may be cleaned with a damp cloth. Use a mild detergent/water on a damp cloth. Ens re the s pply is off before
cleaning and on completion of cleaning the eq ipment is completely dry before the s pply is t rned back ON.
•The eq ipment contains no serviceable parts, or internal adj stments. No attempt m st be made to repair the prod ct. Fa lty eq ipment
m st be ret rned to the s pplier for repair.
•This eq ipment m st be installed by a q alified person. All electrical wiring m st be carried o t in accordance with the appropriate
reg lations for the place of installation.
•DC s pply m st be derived from a local s pply and not a distrib tion system.
•To maintain CE EMC req irements, voltage inp t, DC s pply and voltage o tp t wires m st be less than 30 metres.
•S pply (20 to 240) Vac 50/60 Hz (20 to 240) Vdc. If s pply is a HAZARDOUS VOLTAGE a s pply isolation switch m st be installed close to
the eq ipment with the “OFF” position clearly marked. Also, the s pply m st be f sed with a s itable 1 A (T) f se (circ it breaker) installed
close the eq ipment.
•Receipt and npacking. Please inspect packaging and instr ment thoro ghly for any signs of transit damage. If damage is present, do not
se the eq ipment as safety protection may be affected. Please ret rn damaged eq ipment to s pplier.
•USB config ration can be performed witho t the s pply being connected. For safety reasons, se 24 Vdc for f nctional test of nit prior to
fixed installation. The following operations sho ld only be carried o t on a disconnected device and nder ESD safe conditions: General
mo nting, connection and disconnection of wires.
Specification, please refer to s pplier’s web site latest prod ct data sheet for f ll specification.
Basic specification
Supply (20 to 240) Vac 50/60 Hz or (20 to 240) Vdc, 3 W, max isolation 4.2 KV supply to input output
3.75 KV to all other ports
Input (SELV) RTD, Thermocouple, Potentiometer.
Output (SELV) Current (0 to 20) mA, Voltage (0 to 10) V
Ambient (-20 to 70) °C Approvals EN61010_1, EN61326
Config ration (Read the IMPORTANT SAFETY REQUIREMENTS) During configuration the equipment takes its po er from the USB port, therefore
no po er supply connection is required. The equipment can be configured hilst po ered but the computer used must be isolated from the supply earth to
avoid grounded earth loop effects. To avoid electric shock only use a 24 Vdc supply during bench configuration.
Device
USBSpeedLink software
www.stat s.co. k
USB CABLE
COMPUTER
Default settings inputs PT100, outputs (4 to 20) mA, process ranges (0 to 100) °C, fail high, Tag Channel 1 Channel 2.

D2572-01-03 CN5511 SEM1720 User Guide
Installation (Read the IMPORTANT SAFETY REQUIREMENTS)
isolation s itch
The equipment must be mounted on a DIN rail style DIN EN 50022 inside a plastic
or metal enclosure ith a protection level >= IP65. All iring must be secured. Max cable
sizes 2.5 mm. Connection via t o-part scre terminals.
ELECTRICAL CONNECTION - Ens re the s pply is isolated before carrying o t any installation or wiring. This eq ipment m st be
installed by a q alified person. All electrical wiring m st be carried o t in accordance with the appropriate reg lations for the place of
installation.
CH1 Input
CH2 Input CH2 Output
CH1 Output
USB
CPU
Po er Supply
USB
SUPPLY
(20 to 240) V dc 50/60 Hz
(20 to 240) V dc
Max Power 3W
S1
S2 +
205
206
207
208
105
106
107
108
104
103
102
101
204
203
202
201
INPUTS
Thermocouple
203
103
204
104
+
RTD
202102
203103
203
103
201101
Slide Wire
208108
OUTPUTS
Vdc
LOAD
207107
External Powered mA
+
207107
205105
Internal Powered mA
LOAD
207
107
Vout
206106
Voltage Output
+
205105
201101
204104
202102
+
Input Connections For cable length >3 metres use screen or t isted pair cables. Maximum cable run 30 metres.
Output connections for cable length >3 metres use screen or t isted pair cables. For current outputs max cable run 1000 metres, Voltage
output 30 metres.
Supply maximum cable run 30 metres if using a DC supply. As stated in the IMPORTANT SAFETY REQUIREMENTS the supply must be fused ith
a 1 A (T) fuse and provision provided to isolate the circuit hen hazardous voltages are being s itched.
Ambient Range
+ 70 °C Max
- 20 °C Min
Ø 3mm