
STEIEL ELETTRONICA SRL
Viale Europa n° 24 -Z.I. Roncajette -35020 Ponte San Nicolò (PD) -ITALY
MA2000_IST_ING Rev.00 del 20-07-01 Page 5of 7
2) MA2000 will display REGOLAZIONE DATA/ORA (DATE/TIME set ) on the first line and the day of the
week will flash.
3) Press PLUS MINUS to select the day.
4) Press CAL or NEXT to confirm selection.
5) Time will now flash; select time using PLUS MINUS and press CAL to confirm.
6) Repeat steps 3, 4 and 5 to set minutes and seconds.
The time set is “buffered” by a lithium battery. This means that in the event of a power failure, the clock will
continue to work. The battery has an estimated life of about 2 years. If you notice that upon each power failure
the clock indicates the wrong time, send the MA2000 unit to Steiel for battery replacement (LITHIUM 3V
CR2032).
PROGRAMMING FROM FRONT PANEL
When programming, it is possible to “instruct” the MA2000 by setting the captions corresponding to the
various inputs, whether or not thery are NO or NC, and so on. To start programming procede as follows:
1) Make sure that a possible tripping of the output relays does not cause problems to the system (during
programming, alarms may trigger changing the contact from NO to NC).
2) Press NEXT.
3) PROGRAMMING appears on the MA2000 display, press CAL to confirm
4) Press CAL to confirm that you actually wish to enter the programming mode.
5) PASSWORD = 000 is then displayed.
6) Press PLUS MINUS to set correct password (e.g. 012) and press CAL to confirm.
7) If the password is correct, programming can begin and the values of the first input are displayed. A typical
display might be: PAR01 IN.01 NO NO SHUT DPSL01
8) The data displayed indicate: PAR01 = number of parameter being modified, IN.01 = number of relevant
input, NO = normally open (NC = normally closed), NO SHUT = the relevant input (no. 1 in the example)
does not generate an alarm on the SHUT relay (the alternative is SI SHUT), DPSL01 = alphanumeric
identification code for the relevant input.
9) Note that the cursor appears under the modifiable parameter (in the example PAR01 the value of which is
NO).
10) Press CAL to change the parameter; the value of the parameter will flash (in this example NA [normally
open] will flash). If you wish to change it press PLUS MINUS to set the new value and press CAL to
confirm; the value now enters the permanent memory (EEPROM) and will not be lost even in case the unit
is disconnected from the power supply.
11) Press NEXT to exit programming.
12) To see/change the other parameters, press PLUS MINUS (PARxx and cursor variations can be seen)
and repeat step 10 to change them.
13) Alternatively, if no buttons are pressed after 30 seconds the MA2000 automatically exits programming,
nevertheless saving the data set.
PROGRAMMABLE DATA
10 parameters can be programmed for each input:
1st parameter
NO/NC
determines whether the input
triggers the alarm upon closing
(NO) or upon opening (NC);
possible NO or NC values.
2nd parameter NO/SI SHUT determines whether this input
activates the SHUT output too;
possible values YES or NO.
3rd –10th parameter 1 to 8 characters for input name values; both numeric
(0-9) and alphabetic (a-z, A-Z)
values can be entered;