
E/0204/39/19
ADDITIONAL OPERATING MODES
Standard versions type 1 (with C1010 controller)
Free-cooling mode. On units type 1, there is a damper equipped with servomotor which directs
internal and external air flows. This damper is proportionally controlled by a modulating signal
comingfrom C1010controller(for free-coolinglogic see Chapter11: Control,Monitoringand Safety
Components). Its position can be adjusted from 0 to 100% of fresh air, to regulate free-cooling
capacity.When the free-cooling damper opens, external air is taken from the external environment
and blown directly to the internal ambient.
Mixed mode. When the temperature of the external air is low enough to enable the free-cooling
mode, but the effect of this operating mode is not sufficient to keep the internal temperature within
the admitted range, the compressor is switched ON while the free-cooling damper is still open. In
this way, the evaporator cools external air instead of internal re-circulating air, combining benefit of
free-cooling with cooling mode.
Emergency ventilation. When there is a power failure, units work in emergency ventilation mode,
fed by a back-up battery. During main power supply shortages, the system, including evaporator
fans,control componentsandfree-cooling dampermotor,is energizedbyemergency powersupply.
In this way, continuous circulation of air inside the shelter is always assured.This circulation of air
is combined with free-cooling mode, when the necessary conditions to enable this operation mode
are respected.Versions with 48VDC (standard) and 24 VDC (optional) emergency power supplies
are available.When the power supply is present, the DC components are supplied by the back-up
battery with standard configuration.When the TRAREC option is ordered, the DC power supply is
obtained transforming main power supplied to the unit.
Dehumidification. Units equipped with C1010 include also as standard a mechanical hygrostat.
When humidity inside the shelter is higher than the set value, this hygrostat enables the
dehumidification mode on C1010 controller (for a description of this hygrostat and logic of
dehumidification see Chapter 11: Control, Monitoring and Safety Components).
The dehumidification can also be controlled by a RHC humidity sensor (optional see chapter 19).
Both versions type 1 and type 2 + heating elements option
Heating. With heating elements option (see RSC option on Chapter 19:Options), units include an
electric coil in the evaporator section. When the temperature is low, the heating coil turns on
(compressor off) and the free-cooling damper is in complete re-circulation position, in order to heat
internal air. This mode is controlled by C1010 microprocessor, when present (see Chapter 11:
Control, Monitoring and Safety Components for heating logic). When units are mechanically
controlled, an additional TMC thermostat will be supplied for the heater control (see Chapter 19:
Options).