
CEILAIR OHS SERIES INSTALLATION, OPERATION AND MAINTENANCE MANUAL
5
to turn on, removing humidity. At the same time, the heater(s)
are turned on to offset the cooling effect, thus maintaining
the temperature of the space to be conditioned. Refer to the
electrical drawing supplied with your unit for details specific to
your system.
1.6.2 Temperature/Humidity Sensor
As a standard for systems that use the E² microprocessor
controller, a temperature/humidity (T/H) sensor is typically
factory mounted in the return airstream for room air control.
As an option, the T/H sensor may be shipped loose for field
installation. See 2.7.6.5 on page 25 and the electrical
drawing supplied with your unit for details specific to your
system.
1.6.3 Heaters
The OHS unit may incorporate heaters for reheating the
supply air as required to offset the sensible cooling of the
system during the dehumidification cycle and for the auto-
matic heating mode. Electric resistance heating elements
are factory installed in the supply airstream to heat the sup-
ply air. The heating elements are protected with line fuses
(manual and/or automatic), thermal fuse links and over-
temperature safety switches which automatically reset.
As an option, hot water reheat may be selected for auto-
matic sensible reheating during the dehumidification cycle.
A hot water heating coil is factory installed in the supply air-
stream. A valve is provided to control the flow of hot water
through the coil to maintain the correct reheat temperature.
Hot gas reheat may be selected (for CeilAiR units with DX
cooling only) for automatic sensible reheating during the
dehumidification cycle. Hot compressor discharge gas
is diverted from the condenserto a hot gas heating coil
mounted in the supply airstream.
1.6.4 Humidifier
CeilAiR systems may utilize an optional electrode steam
humidifier. The humidifier is factory installed inside the air
conditioner and includes fill and drain valves and associat-
ed piping. Operation of the humidifier’s fill and drain cycles
is based on water conductivity and is maintained by the
humidifier controller. An operating manual for the humidi-
fier is provided with the unit under separate cover. Refer to
that manual for detailed information about operating the
humidifier.
1.6.5 Condensate Pump
An optional, factory-installed condensate pump may be
provided. The pump automatically eliminates condensate
and humidifier flush water (if applicable) from the drain
pan. Should an overflow occur in an E²-based system, the
pump overflow safety switch triggers a contact signal to
the controller that indicates the alarm condition, and the
controller automatically shuts down the compressor and
optional humidifier until the condition is corrected. The
blower(s) will continue to operate. In an ATech system, the
pump safety switch is wired directlyto the OHS remote
stop/start terminals to cut power to the system.
1.6.6 Smoke Detector
A smoke detector may be mounted in the return airstream
to sense the presence of smoke and, when smoke is
detected, shut down the air conditioner, either via the E²
controller or in ATech systems via connection to the OHS
remote stop/start terminals.
1.6.7 Firestat
A fire detector (firestat) may be mounted in the return
airstream to sense high return airtemperature indicative of
a fire. The system shuts down, either via the E² controller
or, in an ATech system, via connection to the OHS remote
stop/start terminals. Following activation, the firestat must
be manually reset using the reset button on the firestat
before restarting the unit.
1.6.8 Water Detector
As an option, STULZ offers spot type or strip/cable type
water detectors. In units equipped with an E² controller,
when water is detected the controller turns off cooling and
humidification, while the blower(s) continue to operate. The
unit will automatically restart when the condition is correct-
ed. In units equipped with an ATech thermostat, the water
detector is wired to the OHS remote stop/start terminals
and power to the system is cut when water is detected.
1.7 Free-cooling Operation
The free-cooling (FC) configuration illustrated in Figure 4
is available to minimize the use of compressor operation
during low ambient conditions for system energy savings.
An FC system utilizes a remote drycooler to provide water/
glycol coolant to a free-cooling coil positioned within a DX
refrigerant system. If outdoor air temperatures permit free-
cooling operation (adjustable user setpoint), the free-cool-
ing mode is enabled to take advantage of the low ambient
conditions to provide cooling with partial use or without the
use of the system compressor(s). Free-cooling provides
an excellent opportunity for reduced operational cost by
reducing the compressor operating hours. The free-cooling
sequence is enabled if the entering fluid temperature is be-
low the user adjustable free-cooling-enable setpoint and
the return air temperature rises to the free-cooling setpoint