RETURN AIR REQUIREMENTS
Provisions shall be made to permit the air in all rooms in the
living space to return to the air handler. Failure to comply may
cause a reduction in the amount of return air available to the
blower, causing reduced air ow resulting in improper heating
of the living space. The reduced air ow may cause the air
handler to cycle on the electric heater’s over-temperature limit
causing premature heating element failure.
The return air opening can be located in the oor, on a closet
front door, or in a side wall above the air handler cabinet. If the
opening for the return air is located in the oor, side walls, or
closet door anywhere below the appliance cabinet, a 6-inch
minimum clearance between the air handler and the wall or
door must be provided on the side where the return is located
to provide for proper air ow. The 6-inch minimum clearance
is not required if there is a return grille installed above the air
handler casing providing the grille has a sucient return air
opening.
For the air handler to work properly, a closet or alcove must
have a certain total free area opening for the return air.
For A/C and HP Air Handlers 1/3 HP Blower Motor On
(MSVE, MSVT18 & 24)
• Minimum 200 in free area opening
• Use Return Grille or Coil Cabinet
For A/C and HP Air Handlers 1/2 HP Blower Motors On
(MSVE, MSVT25, 30, & 36)
• Minimum 250 in² free area opening
• Use Return Grille, A/C Coil Cabinet, or any return grille with a
minimum 250 in² free area opening.
For A/C and HP Air Handlers with Electric Heat use 3/4 HP
Blower Motor On (MSVE, MSVT 37, 42, 48, & 60)
• Minimum 390 in² free area opening
• Use Return Grille, or A/C Coil Cabinet, or any return grille with
a minimum 390 in² free area opening.
For A/C and HP Air Handlers use 1.0 HP Blower Motor On
(MSVE, MSVT72)
• Minimum 430 in² free area opening
• Use Return Grille, or A/C Coil Cabinet, or any return grille with
a minimum 430 in² free area opening.
SECTION 4: AIR HANDLER ORIENTATION, SUPPLY AIR
DUCT, AND RETURN AIR FILTERS
The air handler is shipped from the factory congured to be
installed in an upow or horizontal right- to-left air-ow position.
Horizontal right-to-left means when facing the front of the air
handler and when it is laid on its side, the supply air opening is on
the left and the return opening is on the right. This air handler is
eld convertible to a horizontal left-to-right air-ow position.
UPFLOW APPLICATIONS
In an upow installation the discharge outlet is at the top. Care
should be taken to ensure air handler is level to permit proper
condensate drainage. Normal upow installation will be in a
closet or basement. If installed in a closet, the closet should have
a platform framed in that measures at least 12 inches in height
with an opening cut in the top of the platform for the return air
to enter the bottom of the air handler. A lter frame and lter
can be used that covers the opening and is sealed to prevent air
by-passing the lter. A lter grille can be used that is located as
described in RETURN AIR REQUIREMENTS.
The minimum lter size is shown as follows:
Standard Throw Away Air Filter @ 300 ft/min or Less
800 CFM = 20 x 20 x 1
1000 CFM = 20 x 25 x 1
1200 CFM = 20 x 30 x 1
1400 CFM = 25 x 30 x 1
1600 CFM = 25 x 30 x 1
1800 CFM = 30 x 30 x 1
2000 CFM = 30 x 40 x 1 or two 30 x 20 x 1
2400 CFM = 30 x 40 x 1 or two 30 x 20 x 1
Pleated Air Filter @ 500 ft/min or Less
800 CFM = 16 x 16 x 1
1000 CFM = 18 x 20 x 1
1400 CFM = 20 x 20 x 1
1200 CFM = 20 x 20 x 1
1600 CFM = 20 x 25 x 1
1800 CFM = 20 x 30 x 1 or two 20 x 15 x 1
2000 CFM = 20 x 30 x 1 or two 20 x 15 x 1
2400 CFM = 25 x 30 x 1 or two 14 x 30 x 1
Another option is to use a SunTherm Air Filter Base Accessory Kit
which can be used on the return air end of the air handler when
congured in the upow position (See Figure 5). The lter base
is placed over the return plenum in the oor and sealed to the
plenum using sealant or caulking material and/or tape. The air
handler is placed on top of the return lter base and the return
opening sealed to prevent leaks.
FILTER BASE ASSEMBLY KIT – FIELD INSTALLED
86ET0002 – 16”X 20” X 2”Small Cabinet 86ET0001 and
20”X 20” X 2” Medium Cabinet
86ET0003 – 20” X 24”X 2”Large Cabinet
Figure 5: Air Filter Base Accessory for 1” or 2” Air Filters.
Notes for Air Filter Base Accessory
• The lter size adjustment knobs are located on both sides of
the base.
• Make sure the ow arrow on the air lter is pointing towards
the coil.
• The Air Filter Base Accessory can also be used on the return
air end of the air handler when congured in the downow
position in place of a wall, door or ceiling mounted return
lter grille.
After the air handler has been secured to the return platform,
connect the supply air outlet to a plenum to the top of the air
handler and secure it with screws. Use a non-tape sealant such
as mastic or an aerosol sealant to seal duct leakage. If the air
handler is installed in a basement, run the supply and return
duct work in accordance with local codes. Use a non-tape
sealant such as mastic or an aerosol sealant to seal duct leakage.