TCS SuperSTAT Series User manual

|INSTALLATION MANUAL
202307
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
Communicating Thermostat
SZ1041

3
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com 32
Introduction ...........................................................................................................................................3
Opening the SuperSTAT .......................................................................................................................3
Mounting the SuperSTAT .....................................................................................................................3
Powering the SuperSTAT......................................................................................................................3
SuperSTAT Wiring Connections..........................................................................................................4
Power................................................................................................................................................................................. 5
RS-485 Port ...................................................................................................................................................................... 5
HVAC Unit Terminations ................................................................................................................................................ 6
Analog Outputs................................................................................................................................................................ 6
Temperature Inputs......................................................................................................................................................... 6
Digital Inputs .................................................................................................................................................................... 7
Contents

32800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
3
Introduction
Congratulations on choosing the SuperSTAT™ modulating thermostat! The SuperSTAT series of controllers are feature
rich, multifunction devices providing extensive controls across a wide range of HVAC applications.
This manual applies to Model SZ1041. It includes all the information necessary to install and wire your SuperSTAT. It
includes a breakdown of the input and output wiring for each model and each type of connection.
After installing your SuperSTAT, refer to the SZ1041 SuperSTAT Conguration Guide for instructions on conguring the
device, the communications network and other devices connected to this controller.
If you have any questions regarding your SuperSTAT, do not hesitate to contact TCS Technical Support at 800.288.9383,
ext. 2. Our Technical Support Department hours are Monday – Friday, 7:00 a.m. to 7:00 p.m. (CST).
Opening the SuperSTAT
The SuperSTAT consists of a base containing wiring terminal blocks and relays, and a front cover containing the keypad
and all other circuitry.
Mounting the SuperSTAT
Mount the base of your SuperSTAT on a vertical wall using two #6 sheet metal screws, either over a horizontally mounted
2" x 4" junction box or a 4" x 4" junction box, or directly to the wall. For best results, select an interior wall that represents
a normal room environment, at a height of about 48" from the oor. Mount the unit in a location which is accessible for
adjusting settings.
For best temperature measurement accuracy, avoid areas that are exposed to direct sunlight, unusual heating or cooling
sources, open doors and windows, unventilated locations, and hot or cold air from diffusers. If you are using a remote
room sensor, mount it in the same manner.
Powering the SuperSTAT
The SuperSTAT is powered from 24 VAC +15%/–5% and draws up to 10VA. If wiring for communications, you must use
dedicated power (transformer) to the unit. Several TCS controllers may be powered from the same transformer, provided
the transformer has sufcient power and you maintain proper polarity. While the SuperSTAT may be powered from the
HVAC unit controller, using a dedicated power source will avoid any potential ground loop issues between equipment
transformers.
When the SuperSTAT is used as a stand-alone thermostat without communications, the equipment transformer may be
used to power it. To do this, install a jumper between the “R” (Packaged Unit Terminations) and “+24” (Power) terminals.
The “–24” (Power) terminal must then be connected to the common side of the equipment transformer.
Installation

5
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com 5
Installation
4
1 2 3 4 5
ON
1 2
ON
RW1 W2 Y1 Y2 G GND
A1 A02 A01
A2
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
SuperSTAT Wiring Connections
The input/output terminals on the SuperSTAT utilize de-pluggable terminal blocks, with two, three, or four poles. Refer to
the diagram of the base below, which indicates which terminations are active.
NOTE: For ease of installation, you can remove the cover from the base by unplugging the ribbon connector. Plug the
connector back into its socket before final assembly.
Power Outside Air
Temp
RS-485
Digital
Inputs
HVAC Unit
Terminations
Analog
Output
Base
Temperature Sensor Dip Switch Settings
The dip switch panel must be properly congured when wiring
remote zone, discharge air, and/or outdoor sensors.
1 2 3 4 5
ON
Built-in room
sensor only
(Default)
1 2 3 4 5
ON
Remote room
sensor only
1 2 3 4 5
ON
Built-in room
sensor w/
discharge air
1 2 3 4 5
ON
Remote room
sensor w/
discharge air
1 2 3 4 5
ON
Built-in room
sensor w/ outdoor
air
1 2 3 4 5
ON
Remote room
sensor w/ outdoor
air
1 2 3 4 5
ON
Built-in room
sensor w/
discharge air and
outdoor air
1 2 3 4 5
ON
Remote room
sensor w/
discharge air and
outdoor air
Remote
Zone
Discharge
Air Temp
Dry
Contact
Cover
(Inside)

52800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
5
Installation
RS-485 Port
For communication wiring, use 22AWG three-wire twisted, stranded shielded copper wire. Must run separately.
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
RW1 W2 G Y2 G GND
A1 A02 A01
A2
A
B
REF
Optional: When used as a standalone thermostat with no communications, you can power the unit via the HVAC
unit's transformer. To do this, install a jumper connecting the "R" and "+24" terminals. The "–24" terminal must then be
connected to the common side of the unit transformer.
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
RW1 W2 G Y2 G GND
A1 A02 A01
A2
R
+–
24V
R
Com
Unit
Transformer
Jumper
Power
Connect the power source using 18AWG two-wire twisted, stranded copper wire.
NOTE: Do not connect to 120VAC. When multiple TCS/Basys Controls devices are using a single transformer, be sure to
maintain the polarity of the power wiring. All TCS devices are half-wave rectified and have common return paths.
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
RW1 W2 G Y2 G GND
A1 A02 A01
A2
+–
24V
+ –

7
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com 7
Installation
6
Analog Outputs
Connect 4 – 20mA, analog output devices using 18 – 22AWG two-wire twisted, stranded shielded or unshielded wire.
Connected actuators, motors, or drives must be powered separately from the SuperSTAT. If you desire a voltage output,
use an included 500Ω resistor.
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
RW1 W2 G Y2 GGND
A1 A02 A01
A2
+ –
*
* = Optional
500ΩResistor
GNDA01
HVAC Unit Terminations
HVAC unit signals may be up to 28VAC from the equipment terminations.
RW1 W2 G Y2 GGND
A1 A02 A01
A2
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
Y1R W1 W2 GY2
RW1 W2 Y1 Y2 G
Temperature Inputs
Connect 1000Ω PtRTD temperature sensor inputs (range of –40ºF to 160ºF) using 18AWG two-wire twisted, stranded
shielded wire, maximum 250 ft. length. Sensors can be used for remote zone temperature, return air temperature,
discharge air temperature, or outside air temperature. Sensor wires should be kept at least ve feet from live voltage
wiring.
NOTE: When using remote sensors, the unit may need to be calibrated See the SZ1041 SuperSTAT Conguration Guide
for more information.
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
RW1 W2 G Y2 G GND
A1 A02 A01
A2
Red
Black
Red
Black
Red
Black
Discharge
Air Temp
Remote
Zone/Return
Outside
Air Temp
DI3 OVR T1 T1 T2 T2 T3 T3

72800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
7
Installation
Digital Inputs
Digital inputs are used to receive status signals such as lter status, fan status, etc. Use unpowered dry contacts only with
18AWG two-wire twisted, stranded shielded or unshielded wire.
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
RW1 W2 G Y2 G GND
A1 A02 A01
A2
DI1 DI2 DI3 OVR T1 T1
Other manuals for SuperSTAT Series
2
This manual suits for next models
1
Table of contents
Other TCS Thermostat manuals
Popular Thermostat manuals by other brands

Levoit
Levoit Aura Sensor user manual