TCS SuperSTAT SZ1053 User manual

2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
|CONFIGURATION GUIDE
202308
Communicating Thermostat
SuperSTAT SZ1053

3
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com 332
Introduction ...........................................................................................................................................3
Display Screen and Keypad..................................................................................................................3
Locating the Programming Keypad .................................................................................................................3
Programming Keypad Access .........................................................................................................................4
Navigating Via Keypad..........................................................................................................................4
Program Setup Mode ............................................................................................................................5
Basic Setup.....................................................................................................................................................5
System Mode .................................................................................................................................................................... 5
Occupancy Settings ........................................................................................................................................................ 6
Heat/Cool Digital Outputs............................................................................................................................................. 7
Time Clock........................................................................................................................................................................8
Modulating Outputs........................................................................................................................................................ 8
Digital Inputs ..................................................................................................................................................................10
Energy Saving.................................................................................................................................................................10
Keypad Access Code..................................................................................................................................................... 11
Setting Clock and Schedule............................................................................................................... 11
Time and Date ................................................................................................................................................................ 11
Occupancy Schedules .................................................................................................................................................. 12
Holiday Occupancy Schedules ................................................................................................................................... 12
Daylight Saving .............................................................................................................................................................. 13
Contents

32800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
3
Configuration
3
TUE 07-04-23
9:00 AM 72F
service
status
fan
switch
system
switch
program
setup
clock
setup
OVERRIDE
COOLER
WARMER
Occupied
Heating
Cooling
Fan
Service
Data/
Program
Building Automation Solutions
TUE 07-04-23
9:00 AM 72F
Locating the Programming Keypad
The SuperSTAT is programmed through a keypad behind the panel on the left side of the cover. Access the keypad by
swinging open the cover panel.
Introduction
Congratulations on choosing the SuperSTAT™ Thermostat SZ1053! The SuperSTAT series of thermostats are feature rich,
multifunction devices providing extensive controls across a wide range of HVAC applications.
Complete the conguration after installation (refer to the SZ1051/1053 SuperSTAT Installation Manual for instructions
on mounting the device, wiring the communications network and connecting other devices to the SuperSTAT.) Your
conguration settings will be uploaded to Ubiquity Cloud the rst time you make a connection to the site. Alternatively, you
can skip conguring the SuperSTAT via the keypad and perform all congurations via Ubiquity Cloud, or via a PC running
TCS Insight software, which is available for download on the TCS website.
NOTE: When configuring the SuperSTAT via a connected PC, you must first set the SuperSTAT’s address, baud rate, and
temperature scale using the keypad (see “Programming Keypad Access” on page 4).
If you have any questions regarding your SuperSTAT, do not hesitate to contact TCS Technical Support at 800.288.9383,
ext. 2. Our Technical Support Department hours are Monday – Friday, 7:00 a.m. to 7:00 p.m. (CST).
Display Screen and Keypad
The display screen on the right side of the cover provides at-a-glance information including day, date, time, and
temperature (based on sensor selection and wiring).
Cover panel (shaded)
swings open

5
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
4 5
Configuration
1 2 3 4 5
ON
1 2
ON
RW/Y1 W/Y2 G Y2 GGND
A1 A02 A01
A2
DI1
A BREF
+–
24V DI2 DI3 OVR T1 T1 T2 T2 T3 T3
Programming Keypad Access
The keypad can be congured to restrict access to the Programming Setup and Clock and Schedule functions. You can
control the access to either function by conguring the keypad dip switches on the inside of the front cover as shown.
Cover
(Inside)
Keypad Dip Switch Settings
The dip switch panel controls access to clock,
schedules, and programming.
1 2
ON
Access to
PROGRAM
SETUP and
CLOCK SETUP
(Default)
1 2
ON
Access to
PROGRAM
SETUP only
1 2
ON
No access to
PROGRAM
SETUP and
CLOCK SETUP
1 2
ON
Access to
CLOCK SETUP
only
Keypad Button Functions
fan
switch
Press to change fan
speed and system
modes (when
enabled)
Press to raise or
lower temperature
settings when
OCCUPIED LED is on
system
switch
program
setup
Press to change
fan thermostat’s
program or
temperature setback
times (when
enabled)
OVERRIDE
Press when
OCCUPIED LED is off
to restore occupied
temperature settings
clock
setup
service
status
Press to review
service screens
Keypad
service
status
fan
switch
system
switch
program
setup
clock
setup
OVERRIDE
COOLER
WARMER
Occupied
Heating
Cooling
Fan
Service
Data/
Program
Navigating Via Keypad
All settings on the SuperSTAT can be made via the keypad. Each screen will display the name of the setting, a selection
option, and current values for that screen, which will ash to indicate which is active. Pressing the WARMER button will
increase the value or advance the active setting to the next option on the screen; pressing the COOLER button will reverse
the process. For screens with multiple values (e.g., date setup), pressing the OVERRIDE button will advance you to the
next value. After adjusting the values, press the PROGRAM SETUP or CLOCK SETUP button again to save the values and
advance to the next screen.
NOTE: Press and hold the PROGRAM SETUP, CLOCK SETUP, WARMER, or COOLER buttons in order to scroll through
screens and values more quickly. Press the SERVICE STATUS button to exit PROGRAM SETUP Mode or CLOCK SETUP
Mode and return to the main screen.

52800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
5
Configuration
Program Setup Mode
Before entering PROGRAM SETUP Mode, ensure that the temperature sensor dip switch settings match your intended
use (see the SZ1051/1053 SuperSTAT Installation Manual). If the dip switch settings do not match the conguration
settings in this section, the SuperSTAT will not function properly.
NOTE: PROGRAM SETUP Mode can be disabled via dip switch settings (see “Programming Keypad Access” on page
4, or access can be restricted by requiring an access code (see “Keypad Access Code” on page 11).
The main screen displays when not in PROGRAM SETUP Mode or
CLOCK SETUP Mode. The SuperSTAT will revert to this screen if no
entries are made after 10 minutes.
From the main screen, press the PROGRAM SETUP button on the
keypad to congure the settings.
TUE 07-04-23
9:00 AM 72F
ENTER ACCESS
CODE 000
If the SuperSTAT has been congured to require an access code to
enter PROGRAM SETUP Mode, this screen will appear (see “Keypad
Access Code” on page 11). If you enter the wrong code, the screen
will revert to the main screen.
Basic Setup
STEP 1 Controller Address: Select a unique address between 0 and
255, excluding 248 (each controller on a network must have a
unique address).
SET ADDRESS:
000
SET BAUD RATE
9.6K
STEP 2 Communication Baud Rate: Choose a baud rate between
2.4K, 4.8K, 9.6K, and 19.2K (each controller on network must
have the same baud rate).
TEMP SHOWN IN:
FAHRENHEIT
STEP 3 Temperature Scale: Choose between Celsius or Fahrenheit
for temperature display.
SET SYSTEM
MODE: AUTO
STEP 2 Set System Mode: Select AUTO, HEAT, COOL, or OFF mode.
System Mode
STEP 1 System Access: Select whether to enable or disable user
access to the System Mode settings. USER ACCESS TO
SYSTEM MODE? YES
USER ACCESS TO
FAN MODE? YES
STEP 3 User Access to Fan Mode: Select whether to allow user
access to FAN MODE.

7
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
6 7
Configuration
SET UNOCCUPIED
FAN MODE? AUTO
STEP 2 Unoccupied Fan Mode: Choose between AUTO or COOL for
fan run times during unoccupied periods.
OCCUPIED HEAT
SETPOINT A: 70F
STEP 3 Occupied Heat Setpoint A: Set the heatpoint for the occupied
period.
OCCUPIED COOL
SETPOINT C: 75F
STEP 10 Occupied Cool Setpoint C: Set the cooling setpoint for this
occupied period.
OCCUPIED COOL
SETPOINT B: 75F
STEP 9 Occupied Cool Setpoint B: Set the cooling setpoint for this
occupied period.
OCCUPIED COOL
SETPOINT A: 75F
STEP 8 Occupied Cool Setpoint A: Set the cooling setpoint for this
occupied period.
UNOCCUPIED HEAT
SETPOINT: 60F
STEP 7 Unoccupied Heat Setpoint: Set the Unoccupied Mode’s
heating setpoint.
OCCUPIED HEAT
SETPOINT B: 70F
STEP 4 Occupied Heat Setpoint B: Set the heatpoint for the occupied
period.
OCCUPIED HEAT
SETPOINT C: 70F
STEP 5 Occupied Heat Setpoint C: Set the heatpoint for the occupied
period.
OCCUPIED HEAT
SETPOINT D: 70F
STEP 6 Occupied Heat Setpoint D: Set the heatpoint for the occupied
period.
Occupancy Settings
STEP 1 Occupied Fan Mode: Choose between ON (continuous),
COOL (gas heat or no heat), or AUTO for fan run times during
occupied periods.
SET OCCUPIED FAN
MODE: AUTO

72800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
7
Configuration
SET OVERRIDE
TIME 180 MINUTES
STEP 14 Override Time: The number of minutes (0 – 255) the
SuperSTAT will maintain overridden occupied setpoints.
LIMIT SETPOINT
ADJUST +/- 05F
STEP 13 User Setpoint Limit: Enter the amount a user is allowed the
to adjust the preset occupied setpoints
UNOCCUPIED COOL
SETPOINT: 80F
STEP 12 Unoccupied Cool Setpoint: Set the Unoccupied Mode’s
cooling setpoint.
OCCUPIED COOL
SETPOINT D: 75F
STEP 11 Occupied Cool Setpoint D: Set the cooling setpoint for this
occupied period.
STAGE 1
OFFSET: 00F
STEP 2 Stage 1 Offset: Enter a stage 1 offset value (normally 0).
NOTE: This screen will only display if Stage Output (Step 1)
is enabled.
STAGE 1
DIFF: 01F
STEP 3 Stage 2 Differential: Enter a stage 1 differential value.
NOTE: This screen will only display if Stage Output (Step 1)
is enabled.
STAGE 2
OFFSET: 00F
STEP 4 Stage 2 Offset: Enter a stage 2 offset value (normally 0).
NOTE: This screen will only display if Stage Output (Step 1)
is enabled.
STAGE 2
DIFF: 01F
STEP 5 Stage 2 Differential: Enter a stage 2 differential value.
NOTE: This screen will only display if Stage Output (Step 1)
is enabled.
Heat/Cool Digital Outputs
STEP 1 Stage Output: Select whether stages 1 and 2 perform heating
or cooling, or whether both are disabled. STAGE OUTPUT 1&2
AS: COOL
SET CONTROL
MODE: P
STEP 6 Control Mode: Select whether to control both Stage Outputs
by temperature only (P) or whether to add a time factor (P+I).

9
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
8 9
Configuration
Time Clock
STEP 1 Time Clock Output: Select whether the auxiliary output will be
OPEN during occupied periods and closed during unoccupied
periods, or CLOSED during occupied periods and open during
unoccupied periods.
TIME CLOCK OUTPUT
OCCUPIED = OPEN
Modulating Outputs
STEP 1 Output 1 Proportional Band: Enter the number of degrees
away from the heating setpoint that the valve or damper will be
fully open.
MO1 PROPORTIONAL
BAND 04F
MO2 PROPORTIONAL
BAND 04F
STEP 2 Output 2 Proportional Band: Enter the number of degrees
away from the heating setpoint that the valve or damper will
be fully open
MOD OUT 1 UNOCC
ACTION: MOD
STEP 9 Output 1 Unoccupied Action: Select whether the unoccupied
action will be 0mA, 4mA, 20mA, or modulating.
MO1 SETPOINT
OFFSET 00F
STEP 3 Output 1 Setpoint Offset: Enter the number of degrees below
the heating setpoint before the output begins to modulate.
MO2 SETPOINT
OFFSET 00F
STEP 4 Output 2 Setpoint Offset: Enter the number of degrees below
the heating setpoint before the output begins to modulate.
MOD OUT 1
ACTION: DIRECT
STEP 5 Output 1 Action: Select whether the output will be direct or
reverse acting.
MOD OUT 2
ACTION: DIRECT
STEP 6 Output 2 Action: Select whether the output will be direct or
reverse acting.
MOD OUT 1
RANGE 4-20MA
STEP 7 Output 1 Range: Select whether the range will be 0 – 20mA
or 4 – 20mA.
MOD OUT 2
RANGE 4-20MA
STEP 8 Output 2 Range: Select whether the range will be 0 – 20mA
or 4 – 20mA.

92800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
9
Configuration
MOD OUT 2 UNOCC
ACTION: MOD
STEP 10 Output 2 Unoccupied Action: Select whether the unoccupied
action will be 0mA, 4mA, 20mA, or modulating.
ENABLE DISCHARGE
AIR FUNCT.? YES
STEP 11 Discharge Air Sensor: Select whether to use a discharge air
sensor. To monitor only, select NO.
NOTE: Refer to the SZ1051/1053 SuperSTAT Installation
Manual for dip switch settings, which must also be set
DISCHARGE AIR
LOW LIMIT: 045F
STEP 12 Discharge Air Low Limit: Enter a discharge air low-limit value:
NOTE: This screen appears only if the discharge air sensor
function is enabled (Step 11).
DISCHARGE AIR
HIGH LIMIT: 125F
STEP 13 Discharge Air High Limit: Enter a discharge air high-limit
value:
NOTE: This screen appears only if the discharge air sensor
function is enabled (Step 11).
MOD OUT 1 BASED
ON: DISCHARGE
STEP 14 Output 1 Control: Select whether to control the modulating
output based on DISCHARGE air reset or SPACE temperature.
MOD OUT 2 BASED
ON: DISCHCHARGE
STEP 15 Output 2 Control: Select whether to control the modulating
output based on DISCHARGE air reset or SPACE temperature.
ENABLE HEATING
LOW LIMIT NO
STEP 16 Heating Low Limit: Select whether to enable Heating Low-
Limit.
MO 1 DISCHARGE
SETPOINT: 90F
STEP 17 Output 1 Discharge Air Setpoint: Enter the discharge air
heating setpoint.
MO 2 DISCHARGE
SETPOINT: 60F
STEP 18 Output 2 Discharge Air Setpoint: Enter the discharge air
cooling setpoint.
MO 1 RESET RATIO
FACTOR: 2.0F
STEP 19 Output 1 Reset Ratio: Enter the degrees that the discharge
air setpoint is raised when the space temperature falls by 1
degree.
MO 2 RESET RATIO
FACTOR: 2.0F
STEP 20 Output 2 Reset Ratio: Enter the degrees that the discharge
air setpoint is raised when the space temperature rises by 1
degree.

11
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
10 11
Configuration
ENABLE SMART
RECOVERY? NO
STEP 2 Smart Recovery: Select whether to use Smart Recovery
Mode.
NOTE: Smart Recovery is not available when DI3 (see “Digital
Inputs: STEP 4” on page 10) is congured for an external
time clock.
Energy Saving
STEP 1 Delay on Powerup: In the event of a power interruption,
entering a value (in seconds) that will delay the powerup of the
SuperSTAT.
DELAY ON POWERUP
010 SECONDS
DI2 USED FOR
MONITOR
STEP 2 DI2: Select SERVICE, AQUASTAT, or MONITOR. If DI2 is
unused, select MONITOR.
SET DI2 SETPOINT
SHIFT: 00F
STEP 3 DI2 Setpoint Shift: Enter the setpoint shift value.
NOTE: This screen will only appear if DI2 is set to Monitor
(Step 2).
DI3 USED FOR:
FILTER SERVICE
STEP 4 DI3: Select FILTER, SERVICE, EXTERNAL OVERRIDE, or
EXTERNAL TIMECLOCK. If DI3 is unused, select EXTERNAL
OVERRIDE.
Digital Inputs
STEP 1 DI1: Select either FAN PROVING or MONITOR. If DI1 is unused,
select MONITOR. DI1 USED FOR
MONITOR
ENABLE OUTDOOR
AIR FUNCT? YES
STEP 21 Outdoor Air Sensor Function: Select whether you are using
an outdoor air sensor. To monitor only, select NO.
NOTE: Refer to the SZ1051/1053 SuperSTAT Installation
Manual for dip switch settings, which must also be set
COOLING LOCKOUT
TEMP 60F
STEP 22 Cooling Lockout: Enter an outdoor air cooling lockout
temperature.
NOTE: This screen appears only if the discharge air sensor
function is enabled (Step 21).
HEATING LOCKOUT
TEMP 70F
STEP 23 Heating Lockout: Enter an outdoor air heating lockout
temperature.
NOTE: This screen appears only if the discharge air sensor
function is enabled (Step 21).

11 2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
11
Configuration
SET DATE:
08-08-18
STEP 2 Date: Set the month, date, and year.
Time and Date
STEP 1 Time and Day: Set the hour, minute, AM or PM, and day of the
week. SET TIME & DAY:
12:00 AM MON
ENTER ACCESS
CODE 248
STEP 3 Access Code: This screen will appear if you congured
an access code requirement for either the Programming
Setup or Clock and Scheduling Setup om the previous two
steps. Select an access code value (0 – 255) to access the
Programming Mode and/or the Clock and Schedule Mode.
The default value is 248.
REQUIRE CODE FOR
CLOCK/SCHED? YES
STEP 2 Clock and Schedule Access: Select whether an access code
is required to access the Clock and Schedule menus.
NOTE: Use dip switch settings to lock out access completely
(see ““Programming Keypad Access” on page 4).
Keypad Access Code
STEP 1 Programming Access: Select whether an access code is
required to access Programming Setup.
NOTE: Use dip switch settings to lock out access completely
(see ““Programming Keypad Access” on page 4).
REQUIRE CODE FOR
PROGRAMMING? YES
Setting Clock and Schedule
NOTE: Access to the Clock and Schedule Mode can be completely disabled via dip switch settings (see “Programming
Keypad Access” on page 4, or access can be restricted by requiring an access code (see “Keypad Access Code” on
page 11).
The main screen displays when not in Programming Setup Mode or
CLOCK SETUP Mode. The SuperSTAT will revert to this screen if no
entries are made after 10 minutes.
From the main screen, press the CLOCK SETUP button on the keypad to
congure the settings.
TUE 07-04-23
9:00 AM 72F
ENTER ACCESS
CODE 000
If the SuperSTAT has been congured to require an access code to
enter Programming Mode, this screen will appear (see “Keypad Access
Code” on page 11). If you enter the wrong code, the screen will revert
to the main screen.

13
2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
12 13
Configuration
COPY SUN FOR
HOL#1? NO
STEP 2 Copy Sunday For Holiday 1: Holiday 1 gives you the option
of copying the schedule from the previous Sunday. If you
select YES, the occupancy time periods from the previous
day (Sunday) will be copied and you will skip to Step 4. If you
select NO, screens for Occupancy Periods A – D (not shown)
will appear. As with the occupancy time periods for regular
days, You can enter up to four different occupancy time
periods.
Holiday Occupancy Schedules
The SuperSTAT has two separate holiday occupancy groups (Holiday #1 and Holiday #2). Within each occupancy group
you can assign up to four occupancy time periods (A – D). After programming the occupancy time periods, you can then
assign them to multiple holidays. You can also congure the duration for each holiday schedule (in days).
STEP 1 Set Occupied Times Holiday No. 1: This screen indicates that
the occupancy time periods for the rst holiday group are
ready to be congured. Press the CLOCK SETUP button on the
keypad to advance to the setup screens for the holiday group.
SET OCCUPIED
TIMES HOLIDAY #1
COPY MON FOR
TUE? NO
STEP 5 Copy Schedules: Select whether to copy the occupancy time
periods from the previous day. If you select YES, the settings
from the previous day’s Steps 2 and 3 will be copied to the
day shown and you will skip to the next day. If you select NO,
the screens for Occupancy Time Periods will appear, allowing
you to enter different schedules for that day. Repeat this
process for each day of the week.
SET OCCUPIED
TIMES TUESDAY:
STEP 4 Set Occupancy Time Periods: This screen indicates the
day of the week shown is ready for conguring up to four
occupancy time periods. Press the CLOCK SETUP button
on the keypad to advance to the setup screens for the day
shown.
A:08:00 TO 17:00
B:00:00 TO 00:00
STEP 2 Occupancy Time Periods (1 of 2): Set hours and minutes
(military time) for start and stop times for occupancy time
periods A and B.
NOTE: Time periods with start and end times of 00:00 are
inactive.
C:00:00 TO 00:00
D:00:00 TO 00:00
STEP 3 Occupancy Time Periods (2 of 2): Set hours and minutes
(military time) for start and stop times for occupancy time
periods C and D.
Occupancy Schedules
STEP 1 Set Occupancy Time Periods: This screen indicates that the
day of the week shown is ready for conguring up to four
occupancy time periods. Press the CLOCK SETUP button on
the keypad to advance to the setup screens for the day shown.
SET OCCUPIED
TIMES MONDAY:

13 2800 Laura Lane •Middleton, WI 53562 |800.288.9383 |www.tcsbasys.com
13
Configuration
SET OCCUPIED
TIMES HOLIDAY #2
STEP 3 Set Occupied Times Holiday No. 2: This screen indicates that
the occupancy times for second holiday group are ready to
be congured. Press the CLOCK SETUP button on the keypad
to advance to the setup screens for the holiday group.
ENTER DATES FOR
HOLIDAY #2:
STEP 8 Holiday Group 2 Dates: This screen indicates that the
Holiday 1 occupancy time periods are ready to be assigned
to specic holidays. Press the CLOCK SETUP button on
the keypad to advance to the setup screens for the holiday
group.
HOL1 01=00=00
DURATION=00 DAYS
STEP 7 Holiday Group 1 Dates: In this screen, you can assign the
Holiday 1 occupancy time periods to as many as 12 holidays.
Enter the two-digit month, date, and duration in days. To add
additional dates to this group, press the OVERRIDE button.
Press the WARMER button to advance the Date number and
add additional months and dates.
C:00:00 TO 00:00
D:00:00 TO 00:00
STEP 5 Occupancy Time Periods (2 of 2): Set hours and minutes
(military time) for start and stop times for occupancy periods
C and D.
A:08:00 TO 17:00
B:00:00 TO 00:00
STEP 4 Occupancy Time Periods (1 of 2): Holiday 2 does not give
you the opportunity to copy occupancy time periods from a
regular day. Set hours and minutes (military time) for start
and stop times for occupancy periods A and B.
NOTE: Occupancy time periods with start and end times of
00:00 are inactive.
ENTER DATES FOR
HOLIDAY #1:
STEP 6 Holiday Group 1 Dates: This screen indicates that the Holiday
1 occupancy time periods are ready to be assigned to
specic dates. Press the CLOCK SETUP button on the keypad
to advance to the setup screens for the holiday group.
HOL2 01=00=00
DURATION=00 DAYS
STEP 9 Holiday Group 2 Dates: In this screen, you can assign the
Holiday 1 occupancy time periods to as many as 12 holidays.
Enter the two-digit month, date, and duration in days. To add
additional dates to this group, press the OVERRIDE button.
Press the WARMER button to advance the date and add
additional months and dates.
Daylight Saving
STEP 1 Set Daylight Saving Time: Determine whether to enable
automatic Daylight Saving adjustments to your time periods. DAYLIGHT
SAVING? YES
Table of contents
Other TCS Thermostat manuals
Popular Thermostat manuals by other brands

Sygonix
Sygonix HT100 user manual

Honeywell
Honeywell TRADELINE T8011R Product data

ritetemp
ritetemp 6008 Operation guide

Carrier
Carrier Performance Non-Programmable ADGE owner's manual

United Electric Controls
United Electric Controls 55HT Series Installation and maintenance instructions

CLIMASET
CLIMASET Prossimo Series instruction manual