
408- 10271
Rev D2 of 5
— A DC disconnect switch must be incorporated in
the installation in accordance with Article 690 of
the NEC.
— This non--metallic enclosure DOES NOT
provide grounding between conduit connections.
Use grounding--type bushings and jumper wires for
grounding the equipment.
— ALWAYS use insulated tools.
— ALWAYS disconnect the combiner box
assembly from loads; such as, moving the AC/DC
switches to off position and covering the solar cells
with opaque (dark) material, before connecting or
disconnecting SOLARLOK connectors or installing
or replacing fuses.
— ALWAYS disconnect SOLARLOK connectors
before working with the combiner box assembly.
— DO NOT connect or disconnect wires when
electrical current from SOLARLOK connectors or
external source is present.
— DO NOT work with the combiner box assembly
if it is wet.
— DO NOT alter the combiner box assembly in
any way.
WARNING: PV modules generate electricity when
exposed to light and can cause electrical shock or
burn. Multiple power sources could be present inside
the combiner box assembly, and hazardous voltages
could exist on exposed wiring and disconnected
terminals. Care must be taken not to touch live
terminals or conductive materials without personal
protection.
WARNING: There is a risk of electrical shock.
Normally grounded conductors may be ungrounded
and energized when a ground--fault is indicated.
2. DESCRIPTION
Each combiner box assembly consists of a box, cover
(with hinges), transparent dead front lid (under the
cover), and 10 pre--terminated SOLARLOK
connectors each with a removeable seal cover.
The box features 4 knockouts (for output wiring), a
lock tab, ground assembly, and mounting slots. See
Figure 1.
The interior of the box contains 5 fuse blocks
pre--wired to the positive SOLARLOK connectors,
5 terminal blocks pre--wired to the negative
SOLARLOK connectors, and an equipment ground
terminal block used to ground the equipment (if
required). Fuses are not included.
Each combiner box assembly accepts:
Output wire: copper wire sizes 14 through 4 AWG
with a maximum of 19 strands (conductor size
must be determined by the system designer with
respect to the NEC)
Use copper wire rated at 90_C [194_F] minimum
Input wire: (10) SOLARLOK connectors with wire
suitable for application (for field installation of
SOLARLOK connectors onto wire, refer to
instruction sheet 411--18305--1)
Conduit hub (fitting): trade size 21 mm [3/4in.] in
diameter (maximum outside diameter of 44.2 mm
[1.74 in.]) meeting standards of UL 514B —
required to maintain weather resistance for the
combiner box assembly
Use only UL Listed rain--tight or wet--location hubs
for entry into the enclosure
Fuse size: (qty: 5) 10 by 38--mm [13/32 by 11/2-- i n . ]
Midget/5AG form factor — consult with the PV
module manufacturer and refer to NEC Article 690
for appropriate fuse rating
Fuses must be UL Listed and have ratings of
600 VDC (minimum) and 15 A (maximum).
For PV systems, the NEC requires that all fuses
and wiring be sized for a minimum of 1.56 times
the short circuit current rating (Isc) of the PV
module used in the system, then rounded up to
the next standard fuse size. For example, if the
Isc of the PV module is 7.2 A, then the fuse size
would be 11.2 (1.56¢7.2). The next standard
fuse size would be 12 A.
3. INSTALLATION
WARNING: The combiner box assembly must be installed
and serviced by qualified personnel only.
Qualified personnel must be knowledgeable in
safety procedures for working with electricity.
Installation must be performed in compliance with
all applicable building and safety codes including
the NEC, ANSI/NFPA 70, and local utility
interconnection requirements.
3.1. Mount the Combiner Box Assembly
To avoid contact with electricity, DO NOT mount
the combiner box assembly if the combiner box
assembly is attached to any live electrical source.
1. Using a small flat blade screwdriver, remove
one of the knockouts to be used for output wire
(knockout located on the side of the combiner box
is preferred). Take care not to damage any of the
interior components while removing the knockout.
2. Mount the combiner box onto a planar surface
using the mounting slots (DO NOT drill holes into
the combiner box) and appropriate hardware:
stainless steel 1/4-- o r 3/8--in. bolts or screws with
washers. See Figure 2 for mounting dimensions.
NOTE
i
NOTE
i
DANGER