Tech Controllers EU-401N PWM User manual

Tech
- 1 -
,,
EU-401N PWM

EU – 401N User’s manual v 1.1.3
- 2 -
I. Safety
Before using the device for the first time the user should read the following regulations carefully. Not
obeying the rules included in this manual may lead to personal injuries or controller damage. The user’s
manual should be stored in a safe place for further reference. In order to avoid accidents and errors it
should be ensured that every person using the device has familiarized themselves with the principle of
operation as well as security functions of the controller. If the device is to be sold or put in a different
place, make sure that the user’s manual is there with the device so that any potential user has access
to essential information about the device.
The manufacturer does not accept responsibility for any injuries or damage resulting from negligence;
therefore, users are obliged to take the necessary safety measures listed in this manual to protect their
lives and property.
WARNING
•High voltage! Make sure the regulator is disconnected from the mains before performing any
activities involving the power supply (plugging cables, installing the device etc.).
•The device should be installed by a qualified electrician.
•Before starting the controller, the user shoud measure earthing resistance of the electric motors
as well as the insulation resistance of the cables.
•The regulator should not be operated by children.
NOTE
•The device may be damaged if struck by a lightning. Make sure the plug is disconnected from
the power supply during storm.
•Any use other than specified by the manufacturer is forbidden.
•Before and during the heating season, the controller should be checked for condition of its
cables. The user should also check if the controller is properly mounted and clean it if dusty or
dirty.
Care for the natural environment is our priority. Being aware of the fact that we
manufacture electronic devices obligates us to dispose of used elements and
electronic equipment in a manner which is safe for nature. As a result, the
company has received a registry number assigned by the Main Inspector of
Environmental Protection. The symbol of a crossed out rubbish bin on a product
means that the product must not be thrown out to ordinary waste bins. By
segregating waste intended for recycling, we help protect the natural
environment. It is the user's responsibility to transfer waste electrical and
electronic equipment to the selected collection point for recycling of waste
generated from electronic and electrical equipment.

Tech
- 3 -
II. Use
EU-401N temperature regulator is intended for controlling solar collector systems in various
configurations. The device controls the collector pumps (or both the pump and the valve) on the basis
of solar batteries temperature and the accumulation tank temperature (two tanks). Optionally, it is
possible to connect an additional device: circulating pump, electric heater or to send a signal to CH
boiler in order to initialise the fire-up process.
Controlling the circulating pump and sending a fire-up signal to the CH boiler may be done
directly from the controller. An additional signal relay is necessary in order to control the heater.
The controller offers PWM pump control option enabling the user to adjust its rotational speed.
III. Principle of operation
Example control panel
Use buttons to navigate through the menu. Press MENU to enter the menu or confirm the
settings. Use PLUS and MINUS buttons to switch between menu options. Press MENU to confirm your
choice. In order to return to the main screen view (or higher level menu), press EXIT button. Follow
the procedure to adjust the settings.
Switching valve
Clock
Collector
temperature
Operation mode
Additional device
active
MENU
PLUS button
MINUS button
EXIT
Heat tank
temperature
Collector pump
Collector
temperature

EU – 401N User’s manual v 1.1.3
- 4 -
III. User menu
III.a) Home page
During standard operation of the controller, the graphic display shows the main page. Apart from the
selected scheme, the display also shows:
- operation mode (or type of alarm),
- current time,
- collector temperature
- current temperature of the heat tank
- temperature of all additional sensors depending on selected configuration
On the right-hand side of the screen you may see the following icons:
Active operation mode icon
Icon of active additional device
(peripherals)
Automatic operation mode
Circulating pump
Collector defrost mode
Pellet boiler fire-up (voltage-
free signal)
Holiday mode
Heater
Collector overheating (alarm
mode)
Anti-legionella
Sensor damage (alarm mode)
If one of the sensors is damaged, an additional icon will be flashing in the place of
the damaged sensor temperature. The icon indicates which sensor was disconnected or damaged.
Additionally, the pump icon will be displayed on the system scheme (if the pump is
working/rotating) or/and the valve icon will appear (with an indication of current circulation direction).

Tech
- 5 -
III.b) Main menu – block diagram
Due to multiple functions fulfilled by the controller, the menu is divided into Main menu and Service
menu.
The main menu includes basic controller options such as operation mode, time and date settings,
language version etc. It is illustrated by the following block diagram.
* The parameter is available only when an additional device (heater) is connected.
III.c) Operation mode
This function enables the user to select the operation mode.
Automatic operation.
In automatic operation mode the pump is active when the minimum difference between collector and
tank temperature is reached (the temperature difference at which the pump is enabled is defined as
Solar pump activation delta in: SERVICE MENU>Pumps>Solar pump activation delta).
The pump remains active until the pre-set temperature is reached (to define the pre-set temperature
go to SERVICE MENU>Accumulation tank>Pre-set temperature) or until the difference between
collector and tank temperature reaches solar pump deactivation delta : SERVICE MENU>Pumps>Solar
pump deactivation delta (in this case the pump will be activated again when the collector temperature
exceeds the tank temperature by the value of solar pump activation delta). When the pump is disabled
after the pre-set temperature is reached, it will be activated again when the temperature drops below
the pre-set value by the tank hysteresis value (the hysteresis may be defined in SERVICE
MENU>Accumulation tank>Tank hysteresis).
Main menu
Operation mode
Automatic operation
Collector defrost
Holiday mode
Anti-legionella*
Manual mode
Clock
Date
Ethernet module
ON/OFF
Registration
DHCP
IP
Network mask
Gate
DNS
Information
GSM ON/OFF
Information
Statistics
Gains
Collector overheats
Power failuresBacklight
Display contrast
Language
Information
Factory settings
Service menu

EU – 401N User’s manual v 1.1.3
- 6 -
Collector defrosting
This function enables the user to activate the collector pump manually in order to cause the snow
deposited on the solar collector to melt. After this function has been activated, the mode is active for
a user-defined period of time. After this time automatic operation is resumed. To set the defrosting
time go to: SERVICE MENU > Solar collector > Defrosting time. The function may be deactivated
manually, to shorten its operation time, by selecting a different operation mode.
Holiday mode
After this mode has been activated, the pump is active when one of the following conditions has been
fulfilled:
Collector temperature reaches the overheating temperature value (SERVICE MENU> Solar collector>
Overheating temperature) minus the value of Holiday delta parameter (SERVICE MENU>Solar
collector>Holiday delta). When this condition is fulfilled, the pump is activated in order to cool the
collector down. The pump is disabled when the temperature drops by 5°C.
Collector temperature is lower than the tank temperature – the pump is activated in order to cool the
tank down. It remains active until the temperatures of the tank and the collector are equal.
Anti-legionella
This function is active only when an additional device is connected (one of the Peripherals in the Service
menu must be selected).
Thermal disinfection involves raising the temperature of water in the tank to the required disinfection
temperature, read from the upper sensor of the tank (in the case of using an optional sensor, the user
should make sure that it measures the temperature of water in the upper part of the tank, as it is the
priority sensor for this function). Disinfection aims to eradicate Legionella pneumophila – bacteria which
lower the cell-mediated immunity. The bacteria often multiplies in hot water reservoirs (optimum
temperature: 35°C). After this function has been activated, the water tank is heated until the pre-
defined temperature is reached (SERVICE MENU > Peripherals > Heater > Anti-legionella > Anti-
legionella temperature). The temperature is maintained for the whole disinfection time (SERVICE MENU
> Peripherals > Heater > Anti-legionella > Anti-legionella time). Next, the standard operation mode is
restored.
Disinfection temperature needs to be reached within a pre-defined period of time from its activation
(SERVICE MENU > Peripherals > Heater > Anti-legionella > Maximum anti-legionella time). Otherwise,
the function will be automatically deactivated.
Manual mode
This function enables the user to check the system devices manually (using MENU button) by switching
ON/OFF:
- the solar pump,
- the second solar pump or the switching valve,
- peripherals - additional devices ( voltage-free contact e.g. for firing up the pellet boiler).
III.d) Clock
This function is used to set current time.
III.e) Date
This submenu enables the user to set current date. Time and date settings are essential for energy
counting function to operate correctly.

Tech
- 7 -
III.f) Ethernet module
NOTE
This type of control is available only after purchasing and connecting an additional
controlling module ST-505 which is not included in the standard controller set.
Internet module is a device enabling the user remote control of the solar heating system via the
Internet at emodul.eu. The user controls the status of all heating system devices on the home computer
screen and the operation of each device is presented in the form of animation. Apart from the possibility
to view the temperature of every sensor, the user can change the pre-set temperature of the tank etc.
The installation process is intuitive. Connect the module and go to the main controller
menu to activate the Internet module (Menu>>Ethernet module>>ON). Once Regis-
tration option has been selected, the device generates a code which must be entered
on the website.
NOTE
The code is valid for 60 minutes. If the user fails to register on the website within this
time, a new code must be generated.
Internet module parameters such as IP address, IP mask, gate address etc. may be set manually or by
selecting DHCP option.
III.g) GSM module
NOTE
This type of control is available only after purchasing and connecting an additional
controlling module ST-65 which is not included in the standard controller set.
GSM module is an optional device which, cooperating with the controller, enables the user remote
control of the CH boiler operation via a mobile phone. The user is sent an SMS every time an alarm
occurs. Moreover, after sending a certain text message, the user receives feedback on the current
temperature of all the sensors.
The ST-65 module may operate independently of the collector controller. It has two additional
inputs with temperature sensors, one contact input to be used in any configuration (detecting
closing/opening of contacts) and one controlled output (e.g. a possibility of connecting an additional
contractor to control any electric circuit)
When any of the temperature sensors reaches the pre-set maximum or minimum temperature, the
module automatically sends an SMS message with such information.A similar procedure is used in the
case of opening or closing of the contact input, which may be used as a simple means of property
protection.
III.h) Statistics
This submenu enables the user to monitor current operating status of the controller:
III.h.1) Gains
This parameter enables the user to check how much energy was gained in different time periods: daily,
weekly, monthly, annually and temporary.
NOTE
Statistics provide only approximate data to illustrate roughly the energy gain.

EU – 401N User’s manual v 1.1.3
- 8 -
IV. Collector overheats
This submenu shows a list of collector overheats (instances of too high temperature detected by the
collector sensor). The user may view:
- date of the overheat incident
- time
- duration
- reading from collector sensor
V. Power failures
This submenu shows a list of power failures registered by the controller. The user may view:
- date
- time
- duration
V.a) Backlight
This parameter is used to adjust the screen brightness. The screen brightness changes after a few
seconds of inactivity.
V.b) Display contrast
This parameter is used to adjust the display contrast.
V.c) Language
This option is used to select the language version of the controller menu.
V.d) Information
Once this option has been selected, the display shows the controller manufacturer’s logo and current
software version.
V.e) Factory settings
This function is used to restore factory settings saved previously in the service menu.
IV. Service menu
In order to enter the service menu, select SERVICE MENU, enter the code using plus and minus: 0112
and confirm by pressing MENU. In order to return to the main screen view (leave the service menu),
press EXIT a few times or wait about 30 seconds ( the controller will leave the service menu
automatically).
A block diagram of the service menu is presented below.
The EU-401N controller may support different heating installation schemes and selecting a different
scheme results in changes in the service menu layout. Additional parameters are marked with * in the
following block diagram.

Tech
- 9 -
Service menu
Accumulation tank
Pre-set temperature
Maximum temperature of tank 1
Tank hysteresis
Minimum temperature of tank 1
Cooling to pre-set temperature
Holiday delta
Solar collector
Overheat temperature
Minimum heating temperature
Alarm hysteresis
Defrosting time
Anti-freeze temperature
Pumps
Regulated revolutions
Maximum collector temperature
Solar pump deactivation delta
Solar pump activation delta
Gear coefficient
Solar pump working minimum
Solar pump working maximum
Installation sampling
Control revolutions
Peripherals
None
Circulating pump
Pellet boiler pump
Heater
DHW cooling
Contact incompatible with pump
Contact compatible with pump
Energy counting
Number of collectors
Flow
Type of medium
Glycol solution
Calibration
Alarm sounds
Factory settings
Edit service code

EU – 401N User’s manual v 1.1.3
- 10 -
IV.a) Accumulation tank
This menu enables the user to adjust all the parameters related to the tank (heat accumulator).
IV.a.1.) Pre-set temperature
This function is used to adjust the pre-set tank temperature. After reaching this temperature the
collector pump is deactivated.
IV.a.2) Maximum temperature of tank 1
Using this option, the user may declare the maximum acceptable safe temperature value which the
tank can reach in case of collector overheat.
If the collector reaches its alarm temperature (overheat), the pump is activated automatically in order
to cool down the heated collector, regardless of the pre-set temperature. The pump operates until the
tank maximum temperature is reached or until the collector temperature drops by the value of the
alarm hysteresis (see: SERVICE MENU > Solar collector> Alarm hysteresis).
IV.a.3) Minimum temperature of tank 1
Using this parameter, the user may declare the minimum acceptable temperature value which the tank
can reach. Below this temperature the pump is not activated in collector defrosting mode.
IV.a.4) Tank hysteresis
Using this function, the user declares the tank hysteresis value. If the tank reaches the pre-set
temperature and the pump is deactivated, it will be activated again after the tank temperature drops
below the pre-set value by the value of this hysteresis.
IV.a.5) Cooling to pre-set temperature
When the collector reaches the overheat temperature, the pump is activated in emergency mode to
cool it down. In this case, the heat is transferred to the tank until the maximum temperature is reached.
To prevent the accumulation of too hot water in the tank, Cooling to pre-set temperature function
should be activated. Once activated, when the collector temperature drops below the temperature of
the tank, the pump is activated in order to cool down the tank until it reaches the pre-set temperature.
IV.a.6) Holiday delta
This function is active only in Holiday mode. This parameter determines how many °C before reaching
the collector overheat temperature the pump is activated in order to cool it down. The pump is
deactivated after the collector temperature drops by at least 5°C.
IV.b) Solar collector
These parameters enable the user to configure solar collector operation.
IV.b.1) Overheat temperature
It is acceptable alarm temperature of the solar collector at which the pump is forced to activate in order
to cool down the solar panels. The discharge of warm water will take place regardless of the tank pre-
set temperature. The pump will operate until the tank temperature drops below the alarm temperature
by alarm hysteresis value (Service Settings > Solar collector > Alarm hysteresis) or until the tank
reaches the maximum acceptable temperature (Service settings > Accumulation tank > Maximum
temperature).
IV.b.2) Minimum heating temperature
It is the collector threshold temperature. If the collector temperature is higher and starts to drop, the
controller disables the pump when the minimum heating temperature is reached. When the collector
temperature is below this threshold and starts to increase, the pump is activated when the minimum
heating temperature plus hysteresis ( 3°C ) is reached. The threshold heating temperature is not active
in the emergency mode, manual mode or collector defrosting.

Tech
- 11 -
IV.b.3) Anti-freeze temperature
Due to the different freezing temperatures of the liquid in the solar installation anti-freeze temperature
was introduced. This parameter determines the minimum safe temperature at which glycol liquid does
not freeze (temperature measured at the collector). In case of a significant drop in the collector
temperature (to the value of anti-freeze temperature), the pump is activated and operates continuously
until the collector reaches safe temperature. The setting range of this parameter is within -50: +10°C.
IV.b.4) Alarm hysteresis
Using this function the user sets the value of the collector alarm hysteresis. If the tank reaches the
alarm temperature (Overheat temperature) and the pump is activated, it will be deactivated again when
the collector temperature drops below the maximum temperature by alarm hysteresis value.
IV.b.5) Defrosting time
Using this function the user determines for how long the pump is enabled once collector defrosting
function has been activated.
IV.c) Pumps
IV.c.1) Pump revolutions - regulated or constant
Using this function the user defines the mode of the pump operation: constant revolutions, when the
pump operates at all times at full power (when enabled) or regulated revolutions. In the case of
regulated revolutions, the user should adjust several additional parameters (see below).
IV.c.2) Maximum collector temperature
Using this setting the user declares the value of the collector maximum alarm temperature at which
the pump may be damaged. This temperature should be adjusted according to the collector technical
specification. Due to the phenomenon of glycol "gelation" at high temperatures and the risk of damaging
the solar pump, the pump is deactivated after reaching the maximum alarm temperature (the controller
switches to Collector overheat mode.).
IV.c.3) Solar pump deactivation delta
This function determines the difference between the collector temperature and the tank temperature
at which the pump is deactivated (so as not to cool down the tank).
IV.c.4) Solar pump activation delta
This function determines the difference between the collector temperature and the tank temperature
at which the pump is enabled (this is the pump activation threshold).
IV.c.5) Gear coefficient
This parameter is available only if regulated revolutions option is selected. When the conditions for the
pump activation are met, it is initially activated at minimum speed (solar pump work minimum). Then
the pump speed increases according to this coefficient which determines the difference (°C) between
the collector temperature and the tank temperature at which the pump speeds up by 10%. The gear
coefficient applies only to the pump operating revolutions, namely the value of revolutions within the
limits of the solar pump work minimum (0% for the gear coefficient) as well as the solar pump work
maximum (100% for the gear coefficient). The greater the difference between the collector
temperature and the tank temperature, the higher the pump speed.

EU – 401N User’s manual v 1.1.3
- 12 -
Example:
If the gear coefficient value is 3, each 3°C difference between the tank temperature and the collector
temperature results in 10% increase in pump speed.
The table below contains examples of the coefficient values and its results.
Gear coefficient 3
Gear coefficient 4
Gear coefficient 5
Gear coefficient 6
Pump working
revolutions
Δ value
(collector temp.
– tank temp.)
Δ3
Δ4
Δ5
Δ6
10%
Δ6
Δ8
Δ10
Δ12
20%
Δ9
Δ12
Δ15
Δ18
30%
Δ12
Δ16
Δ20
Δ24
40%
Δ15
Δ20
Δ25
Δ30
50%
IV.c.6) Solar pump work minimum
This parameter is available only if regulated revolutions option is selected. Using this setting the user
should define the pump minimum initial speed.
IV.c.7) Solar pump work maximum
This parameter is available only if regulated revolutions option is selected. Using this setting the user
should define the pump maximum operating speed (%).
IV.c.8) Installation sampling
This function enables the user to activate or deactivate circulation sampling, aimed at updating the
temperature reading, by activating the collector pump for a short period of time (when standard
conditions of pump activation are not met). Sampling forces short-time activation of the pump after
the collector temperature increase of at least 3°C.
IV.c.9) Control revolutions
These parameters enable the user to choose the type of PWM pump used:
•Increase
It concerns PWM pump whose speed increases when the signal increases.
•Decrease
It concerns PWM pump whose speed decreases when the signal increases.
IV.d) Peripherals
The user may connect and configure the settings of an additional device. If there is no additional device,
the user should select NONE (deactivate). Additional devices to choose from and examples of
connections supporting all available installation schemes are presented below. In the case of schemes
12 and 14 it is not possible to connect an additional device - the function is unavailable.
IV.c.10) Circulating pump
Once this device is selected, the user should adjust operation time and pause time of the pump during
its activity. Next, the user should define the hours of pump operation using From hour and Through
hour functions. Entering the same times (from – through) will result in the device being active
throughout the whole day.

Tech
- 13 -
IV.c.11) PLT (pellet) boiler fire-up
This option is used to set the voltage-free signal to fire up the pellet boiler. The user defines activation
delta - the difference between the pre-set tank temperature and the current tank temperature at which
the controller sends a signal to fire up the boiler. Next, the user selects the time period throughout
which this function will be active (with the use of from hour and through hour parameters).

EU – 401N User’s manual v 1.1.3
- 14 -
IV.c.12) Heater
The heater is used to electrically heat the tank. The principle of operation is similar to that in the
previous case but the heater should be connected by means of an additional contactor. The user defines
the activation delta (the difference between the pre-set tank pre-temperature and current tank
temperature) below which the controller activates the heater. Next, the user selects the time period in
which the electric heating function will be active (using from hour and through hour parameters).
IV.c.13) Contact (in)compatible with pump
This setting determines the operation of the voltage-free contact. If the option Contact compatible with
pump is selected, the voltage-free contact will always close when the pump operates (the additional
device will be enabled). Otherwise (when the icon is deselected), the contact will open at each activation
of the solar pump.
IV.c.14) Cooling down with DHW pump
This function is active beyond the time period, which means all the time. Sensor 4 is required
for it to operate correctly (it should be installed in the external DHW tank). This function will not operate
in the installation scheme which uses all the sensors. The tank sensor is also necessary for it to operate
(in the case of two sensors in the tank - the top sensor).
If the conditions listed above are met, the peripheral device will be activated (contact closing) when:
➔the tank temperature during its growth exceeds its maximum temperature reduced by cooling
activation delta and operates until the temperature drops below the tank maximum temperature
reduced by cooling deactivation delta (both parameters may be adjusted in the menu).
➔the temperature in the tank is higher than the DHW temperature. A constant hysteresis of 3°C
is used here.
IV.e) Energy counting
The following parameters need to be configured to achieve more accurate energy measurement.
IV.c.15) Number of collectors
On the basis of the number of collectors the controller calculates how much heat has been produced
by the solar installation (energy gain).
IV.e.2) Flow
The user should specify the amount of glycol that flows through the pump during one minute.

Tech
- 15 -
IV.e.3) Type of medium
The user chooses the agent used: ethylene glycol, propylene glycol or water.
IV.e.4) Glycol solution
The user specifies glycol concentration in water (given in percent.
IV.e.5) Calibration
This function allows the user to calibrate the temperature difference between the sensors. The
temperature is measured in the place where the temperature sensor is installed. Deviations may occur
in the flow and temperature measurement at the tank return. The manufacturer does not recommend
changing this setting.
IV.f) Alarm sound
This function enables the user to activate/deactivate the sound signal after an alarm occurs.
IV.g) Factory settings
The controller is pre-configured for operation. However, the settings should be customized to the user's
needs. Return to factory settings is possible at any time. Once the factory settings option is activated,
all customized settings of the solar installation controller (saved in the user's menu) are lost and
replaced with the manufacturer's settings. Then, the parameters may be customized anew. Return to
factory settings results in activating the default installation scheme.
IV.h) Edit service code
It is possible to edit service menu code. Go to this submenu, enter the code and confirm the settings.
V. Protections
In order to ensure safe and failure-free operation, the controller is equipped with a range of
protections.
1. Sensor protection.
If one of the sensors is damaged, an acoustic signal is activated and the following symbol will
appear on the right hand side of the display. An additional icon informing the user which sensor is
disconnected or damaged will flash in the place of its temperature. In order to deactivate the alarm
signal in case of error, press EXIT button.
2. Protection against collector overheating.
If the maximum (alarm) temperature is reached, the regulator switches to the so-called collector
overheat mode and the display shows a corresponding symbol . The pump is enabled in order
to cool down the collector until the maximum tank temperature is reached or until the collector
temperature drops by the value of the alarm hysteresis (see: SERVICE MENU > Solar Collector> Alarm
Hysteresis) In the case of two tanks, both of them are used to cool down the overheated collector (at
the same time or one by one, depending on the operation algorithm setting).
3. Heat tank protection.
In the event of collector overheating, each tank may be heated to no more than the pre-set maximum
safe temperature. After reaching this temperature, the pump of a given tank is disabled (in system
configuration with two tanks and a valve, the circulation is switched to the second tank).
4. Fuse.
The regulator is equipped with a WT 3.15A tube fuse-link protecting the network.

EU – 401N User’s manual v 1.1.3
- 16 -
WARNING
Higher amperage fuse should not be used as it may lead to controller damage.
V. Software update
NOTE
Software update shall be conducted only by a qualified fitter. After the software has been
updated, it is not possible to restore previous settings.
In order to install new software, the controller must be unplugged from the power supply. Next, insert
the flash drive with the new software into the USB port. Connect the controller to the power supply
holding MENU button at the same time until a single sound signal is heard. It indicates that the software
updating process has started.
VI. Maintenance
Before and during the heating season, EU-401N controller should be checked for condition of its cables.
The user should also check if the controller is properly mounted and clean it if dusty or dirty.
Power supply
230V ±10% / 50Hz
Power consumption
4W
Collector sensor thermal resistance
-30÷180˚C
Tray sensor thermal resistance
-30÷99˚C
Pump 1 max. output load
1A
Pump 2/Valve max. output load
1A
Additional output 1 max. output load
1A
Fuse
3,15A
VII. How to install the device
CAUTION:
The controller should be installed by a qualified electrician! Make sure that the plug is
disconnected from the power supply at that time.
NOTE
The cable connecting the temperature sensor should be put in a protective tube and it
should not be exposed to weather conditions. The cable connection of the solar controller
should be durable, made under shelter and well insulated. Metal parts of the sensor and
the collector system should be earthed.

Tech
- 17 -
Pictorial diagram - collectors
*Pictorial diagram – it cannot replace CH installation project. Its aim is to present how the controller
may be expanded. This heating installation diagram does not include protective elements which are
necessary to ensure correct installation.

EU – 401N User’s manual v 1.1.3
- 18 -
PWM pump connection scheme:

Tech
- 19 -
EU DECLARATION OF CONFORMITY
Hereby, we declare under our sole responsibility that EU-401N PWM manufactured by TECH STEROWNIKI,
head-quartered in Wieprz Biała Droga 31, 34-122 Wieprz, is compliant with Directive 2014/35/EU of the
European Parliament and of the Council of 26 February 2014 on the harmonisation of the laws of Member
States relating to the making available on the market of electrical equipment designed for use within
certain voltage limits (EU OJ L 96, of 29.03.2014, p. 357), Directive 2014/30/EU of the European Parliament
and of the Council of 26 February 2014 on the harmonisation of the laws of Member States relating to
electromagnetic compatibility (EU OJ L 96 of 29.03.2014, p.79), Directive 2009/125/EC establishing a
framework for the setting of ecodesign requirements for energy-related products as well as the regulation by
the MINISTRY OF ENTREPRENEURSHIP AND TECHNOLOGY of 24 June 2019 amending the regulation
concerning the essential requirements as regards the restriction of the use of certain hazardous substances
in electrical and electronic equipment, implementing provisions of Directive (EU) 2017/2102 of the European
Parliament and of the Council of 15 November 2017 amending Directive 2011/65/EU on the restriction of the
use of certain hazardous substances in electrical and electronic equipment (OJ L 305, 21.11.2017, p. 8).
For compliance assessment, harmonized standards were used:
PN-EN IEC 60730-2-9:2019-06, PN-EN 60730-1:2016-10.
Wieprz, 08.04.2022

EU – 401N User’s manual v 1.1.3
- 20 -
Table of contents
Other Tech Controllers Temperature Controllers manuals

Tech Controllers
Tech Controllers EU-402N PWM User manual

Tech Controllers
Tech Controllers EU-297 v3 User manual

Tech Controllers
Tech Controllers EU-293v3 User manual

Tech Controllers
Tech Controllers ST-280 User manual

Tech Controllers
Tech Controllers EU-F-2z v1 User manual

Tech Controllers
Tech Controllers EU-T-3.1 User manual

Tech Controllers
Tech Controllers EU-281C User manual

Tech Controllers
Tech Controllers EU-281 User manual

Tech Controllers
Tech Controllers EU-292n v2 User manual

Tech Controllers
Tech Controllers EU-297 v2 User manual