
Product design, software and literature are Copyright © 2011 by:
tekmar Control Systems Ltd. and tekmar Control Systems, Inc. 2 of 2 All specifications are subject to change without notice.
Printed in Canada. Q 538 - 12/11.
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road,
Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com
User Interface7.
Critical Settings8.
For a full list of settings and operational details, please refer to the thermostat Installation and Operation Manual
(D538) included with compatible tekmarNet®controls or download the brochure from www.tekmarcontrols.com
Display Range Access Description Set to
°F or °C
Default = °F
Installer
User
TEMPERATURE UNITS
Press the or the button to change from °F to
°C and vice versa.
H1
ADJUST
SUPPLY
OFF or On
Default = On Installer
HEAT SUPPLY PUMP
During heating, select whether or not the system supply
pump should turn on or be off to allow a zone group
pump per manifold.
Available when:
A reset control is present on the tekmarNet®system.•
H1
ADJUST
SUPPLY
OFF or On
Default = OFF Installer
HEAT SUPPLY PUMP DELAY
During heating, select whether or not the system supply
pump should be delayed by 3 minutes before coming
on (for thermal motor or wax actuator).
Available when:
A reset control is present on the tekmarNet®system.•
On or Off
Default = On Installer
ROOM SENSOR
Select whether the built-in air temperature sensor is
on or off.
Available when:
A floor sensor or room sensor is installed on the
auxiliary sensor input.
Off, Room,
Outdoor,
Floor, Floor
dSP
Installer
AUXILIARY SENSOR
Select the type of auxiliary sensor.
Floor dSP = Show floor sensor reading in upper
number field.
Available when:
Auxiliary sensor automatically detected.
• Press and hold down both the and buttons for 2 seconds to change from one step to the next.
• Release both buttons once the step has been reached.
• Press the or the button to change the setting, if available.
• Press and hold down both the and buttons for 2 seconds to go to the next step, OR
• After 10 seconds of no button activity, the display goes back to normal operation.
Press
+
Together
The following settings are essential to the successful operation of the system.
Important
Note: Set switch setting #3 and tekmarNet®system control to Unlock to change Access level to Installer. Return to Lock
setting once installation has been completed.