
© 2008 W 542 - 12/08 6 of 8
Wire the tN4 communication to terminals tN4 and C.
If a Zone Manager is used:
Connect the tN4 on the thermostat to the tN4 on the
proper zone of the Zone Manager used for the first stage
of heat. The C terminal is already connected.
If a Zone Manager is not used:
Connect the tN4 on the thermostat to the tN4 on another
tN4 device on the same tN4 bus.
Connect the C on the thermostat to the C terminal on
another tN4 device on the same tN4 bus.
tN4 Communication Terminals 1, 2
Wire the first stage of heating to the Heat 1 Relay.
(Rh - W)
Use these terminals as a switch to operate the first stage
of heating.
If a Zone Manager is used:
Connect W on the thermostat to W on the proper zone
of the Zone Manager.
If a Zone Manager is not used:
Determine if the factory jumper must be cut.
When the factory jumper is not cut, W is a powered
output that is internally connected to R.
When the factory jumper is cut, Rh W is an isolated
switch. No power is available from these terminals.
Heat 1 Relay Terminals 3 - 5
Wire 24V (ac) to terminals C and R.
If a Zone Manager is used:
Connect C on the thermostat to C on the proper zone
of the Zone Manager.
Connect R on the thermostat to R on the proper zone
of the Zone Manager.
If a 24 V(ac) transformer is used:
Connect C on the thermostat to C on the transformer.
Connect R on the thermostat to R on the transformer.
Power (24 V (ac)) Terminals 2, 3
Note: This connection is polarity sensitive.
Wiring the Thermostat:
The auxiliary sensors are connected to the thermostat on
terminals Com, S1 and S2.
• Connect sensor 1 to terminals S1 and Com.
• Connect sensor 2 to terminals S2 and Com.
Do not apply power to terminals 6 - 8, permanent
damage to the sensors and/ or thermostat will result!
Auxiliary Sensors Terminals 6 - 8
Do Not Apply Power
Thermostat
Universal
Sensor
Outdoor
Sensor
To various tekmar
sensors
8S2
7S1
6Com
tN4 C RW
Thermostat
Zone Manager
tN4 C R Rh W
12345
Thermostat
Zone Manager
or other tN4
thermostat
tN4 C R Rh W
12345
tN4 C RW
*Factory installed jumper
connects terminals R to Rh
(to isolate W relay, cut jumper)
Thermostat
Zone Manager
tN4 C R Rh W
12345
tN4 C RW