© 2007 D541 - 08/07 2 of 24
Table of Contents
Table of Contents............................................................2
Display and DIP Switches ..............................................2
Dip Switches ...........................................................2
Access Levels .........................................................3
Display and Symbols Description............................3
User Interface .........................................................4
Setup ..............................................................................5
View Menu .............................................................5
Adjust Menu............................................................6
Scene Menu............................................................8
Schedule Menu.......................................................9
Miscellaneous Menu ..............................................9
Thermostat Operation .................................................. 11
Auxiliary Sensors ................................................. 11
Mode of Operation ............................................... 11
Adjusting the Temperature ...................................12
Cycles Per Hour ................................................... 13
Heating Terminal Units .........................................13
Heating Operation ................................................ 14
Cool Groups .........................................................15
Setting the Schedule.............................................15
Optimum Start / Stop ...........................................15
Scenes .................................................................16
Away Hold ............................................................ 17
Offset ................................................................... 17
Units of Temperature ............................................ 17
Backlight .............................................................. 17
tN4 Address ......................................................... 17
Pump Exercising ................................................... 17
Error Messages ............................................................18
Cleaning the Thermostat .............................................24
Warranty.......................................................................24
Display and DIP Switches
Dip Switches
tN4 System Control (DIP Switch #2)
A tN4 System Control is a control, not a thermostat, that
the 541 thermostat connects to through the tN4 bus. All
tN4 compatible Outdoor Reset Modules are tN4 System
Controls.
• If the thermostat is connected to a tN4 System Control,
set the tN4 System Control DIP switch to tN4 System
Control (down position).
• If the thermostat is not connected to a tN4 System
Control, set the tN4 System Control DIP switch to None
(up position).
Lock/Unlock (DIP Switch #1)
Use the Lock/Unlock DIP switch to lock or unlock the
Access Level of the 541.
• To unlock the Access Level, set the DIP switch to the
unlocked (down) position.
• To lock the Access Level, set the DIP switch to the locked
(up) position. Once locked, a padlock is displayed in the
lower right corner of the display and the Access Level
cannot be changed.
Note: The tN4 System Control’s Lock/Unlock DIP switch
overrides the Lock/Unlock DIP switch on the 541. Set
the tN4 System Control’s Lock/Unlock DIP switch to the
Unlock position before Access Levels can be changed on
the thermostat.