
X45 AIR COMPRESSOR
PRESSURE MEASURING &
SETTING PROCEDURE
Test Procedure
Proheat has an improved Air compressor pressure settings
procedure based on supply voltage to the heater.
1. Run heater until warm to the touch. This ensures the heater
components are up to normal operating temperature.
2. Switch heater off.
3.
Install the calibrated Pressure Gauge Tool PK0060 in-line as
shown in Figure A.
Calibrate gauge before each use see
www.proheat.com/PDFs/990614.pdf
NOTICE
Altitude Correction is needed above
3000 Feet (see inset on charts).
DO NOT adjust air pressure when
above 6000 Feet.
NOTICE
Remove Pressure Gauge when finished
with measuring & setting procedure.
NOTICE
HOSE TO NOZZLE
AIR INLET
PRESSURE
GAUGE TOOL
PK0060
4. Locate the rubber boot on the positive end of the ignition coil
and peel it back to expose the positive terminal.
5. Select the DC Volts range of a multimeter and connect as per
Figure B. The positive lead of the multimeter should be
attached to the positive coil lead. The negative lead of the
multimeter should be attached to the heater chassis at the
PROHEAT ground boss.
6. With the heater running in full output (flame on and ignition is
off) read the voltage and refer to the 12 or 24 volt chart
(Figure C and D) for the correct Air Pressure Reading.
7. The reading must be within the range of the shaded area as
shown in Figures C and D.
Figure A. Pressure Gauge Tool PK0060.
Shock hazard due to high secondary
coil voltage.
WARNING
© 2011 Teleflex Canada Limited Partnership 3831 No. 6 Road, Richmond, B.C. Canada V6V 1P6 Fax: 604-270-7172 Web: www.proheat.com
SERVICE BULLETIN
Copy Part# SB0060, Rev. A, 04/2011 Page 1 of 3
THERMAL SYSTEMS