Electrical work must be carried out by a
qualied electrician in accordance with local
supply authority regulations and the wiring
diagram.
UNITS WITH ELECTRIC HEAT
If electric elements have been included
(factory tted), a 24 hour power supply
is required to power the fan run-on timer.
Recommended external circuit breaker size
for a unit factory tted with electric elements
is 125 A/ph.
This electric heat kit includes both auto
(90°C) and manual (120°C) high temp.
safety thermostats. If the manual high temp.
safety t/stat requires resetting and the auto
high temp. safety t/stat does not reset, then
the latter needs to be replaced.
FAN SPEED
The fan motor is tted with a factory set
(mid position) adjustable pitch pulley. One
revolution of adjustment is equal to 7%
change in air volume ow rate.
To change the fan speed loosen the motor
mounting plate hold down screws, loosen
the pulley grub screws and turn the pulley
ange the desired amount. The pulley
adjustment is locked by tightening the grub
screws in the keyways.
When setting air ows ensure that the
pulleys are in alignment. Tension the belt by
adjusting the motor mounting plate.
Note: Do not operate the fan without
resistance (duct system) connected. Motor
will overload if fan is operated in a free blow
situation.
COMMISSIONING
1. Check that the thermostat is
correctly wired and set at the desired
temperature.
2. Check that the air lter (if tted) is clean.
3. Check that the fan runs freely without
vibration.
4. Check the indoor unit's fan belt tension
after 20 mins of operation and adjust if
necessary.
5. Check the airow at each air outlet
(diffuser) and adjust if necessary.
6. Check the tightness of all electrical
connections and sign the check label.
7. Check condensate drain for free
drainage.
8. If unit is installed outdoors, touch up any
paintwork damage to prevent corrosion.
MAINTENANCE
Weekly For First Four Weeks
1. Check air lter (if tted); vacuum clean as
necessary.
2. Check condensate drain for free
drainage.
Monthly
Check air lter (if tted); vacuum clean as
necessary.
Six Monthly
1. Check condensate drain for free
drainage.
2. Check heat exchanger coil; vacuum or
brush clean as necessary.
3. Check the tightness of the fan, motor
mountings, pulley and belt tension.
4. Check that fan motor is free running.
5. Check tightness of electrical connections.
5. Check air supply at diffuser outlets.
Yearly
1. Check fan shaft bearings and lubricate
with a lithium base grease.
2. If unit is installed outdoors, touch up any
paintwork damage to prevent corrosion.
NOTE
The manufacturer reserves the right to
change specications at any time without
notice or obligation. Certied dimensions
available on request.
This pamphlet replaces the previous issue
no. 2529 dated 06/15.
Wiring revsions C/C/D/E respectively.