Page 4 TST300v2_R1.6 – December 2018
9. Factory default sengs
Disconnect the sensor from the bus (switch o the power supply).
Press and hold “cong” buon. Don’t release the buon, connecng the sensor to the bus
(switch on the power supply).
The “status” LED will be ON for 3 seconds and aer this will ash for 7 seconds. Aer the 10-th
second the LED will be ON.
Release the buon. The sensor will restart with factory default sengs.
10. Firmware update
The rmware of the sensor can be updated with Teracom controller which supports
MODBUS RTU or MBRTU-Cong soware. For more details ask your dealer.
11. Modbus address table
Register name R/W FC
PDU
Address
(Decimal)
Logical
address
(Decimal)
Oset
(Decimal Data size Default Valid values
RS-485 address R/W 03/06 10 40011 40001 16-bit Integer 1 1-247
Baud rate * R/W 03/06 11 40012 40001 16-bit Integer 19200 2400, 4800, 9600,
19200, 38400, 57600
Parity, data, stop
bits *
R/W 03/06 12 40013 40001 16-bit Integer 1 1=E81, 2=O81, 3=N81
Bytes order R/W 03/06 13 40014 40001 16-bit Integer 1 1= MSW, LSW
2= LSW, MSW
Temperature
(Measured)
R 03 100 40101 40001 32-bit Float
Temperature
Dimension
R 03 104 40105 40001 4 bytes UTF-8
ID 64-49 bits R 03 108 40109 40001 16-bit Integer
ID 48-33 bits R 03 109 40110 40001 16-bit Integer
ID 32-17 bits R 03 110 40111 40001 16-bit Integer
ID 16-1 bits R 03 111 40112 40001 16-bit Integer
Sub-family number R 03 112 40113 40001 16-bit Integer
FW version R 03 113 40114 40001 16-bit Integer
Vendor URL R 03 300 40301 40001 64 bytes UTF-8 teracomsystems.com
Test value (oang
point, MSW rst)
R 03 332 40333 40001 32-bit Float -9.9(0xC11E6666)
LSW - Least signicant word (bits 15 … 0);
MSW - Most signicant word (bits 31 … 16)
PDU address - Actual address bytes used in a Modbus Protocol Data unit
A “NaN” value is returned for unavailable oang-point values (e.g. in case of measurement error)
* The sengs will take eect aer restart of the sensor by power on reset.