TFT XFIH-E11A Programming manual

TASK FORCE TIPS, Inc. 2800 E. Evans Ave., Valparaiso, IN 46383-6940 USA
800-348-2686 • 219-462-6161 • Fax 219-464-7155
INSTRUCTIONS FOR INSTALLATION, SAFE OPERATION AND MAINTENANCE
MANUAL: Remote Control
HURRICANE RC MONITOR
Read instruction manual before use. Operation of this device without understanding the manual
and receiving proper training is a misuse of this equipment. A person who has not read and
understood all operating and safety instructions is not qualified to operate the Hurricane RC
monitor.
DANGER
This instruction manual is intended to familiarize installers,
firefighters and maintenance personnel with the installation,
operation, servicing, and safety procedures associated with
the Hurricane RC Monitor.
This manual should be kept available to all operating and
maintenance personnel.
Model XFIH-E11A Monitor
Shown With
Model M-ERP-NJ Nozzle
Maximum recommended inlet
pressure is 200 psi. (14 bar)
MADE IN USA • www.tft.com
©Copyright Task Force Tips, Inc. 2004-2007
®
LIX-300 August 17, 2007 Rev08
The member companies of FEMSA that provide emergency response
equipment and services want responders to know and understand the
following:
1. Firefighting and Emergency Response are inherently dangerous
activities requiring proper training in their hazards and the use of extreme
caution at all times.
2. It is your responsibility to read and understand any user's instructions,
including purpose and limitations, provided with any piece of equipment
you may be called upon to use.
3. It is your responsibility to know that you have been properly trained in
Firefighting and /or Emergency Response and in the use, precautions,
and care of any equipment you may be called upon to use.
4. It is your responsibility to be in proper physical condition and to maintain
the personal skill level required to operate any equipment you may be
called upon to use.
5. It is your responsibility to know that your equipment is in operable
condition and has been maintained in accordance with the
manufacturer’s instructions.
6. Failure to follow these guidelines may result in death, burns or other
severe injury.
DANGER
PERSONAL RESPONSIBILITY CODE
Fire and Emergency Manufacturers and Services Association, Inc.
P.O. Box 147, Lynnfield, MA 01940 • www.FEMSA.org
FEMSA

3.1 SPECIFICATIONS ......................................3-4
3.1.1 MECHANICAL SPECIFICATIONS
3.1.2 ELECTRICAL SPECIFICATIONS
3.2 PART IDENTIFICATION AND MODELS .......................4
3.3 INLETS AND OUTLETS..................................5-6
3.3.1 INLET FLANGE SIZE SPECIFICATIONS
3.4 OVERALL DIMENSIONS ..................................6
3.4.1 OVERALL HEIGHT INCREASE FOR INLET FITTINGS
3.5 ELECTRICAL CONTROLS .................................7
3.5.1 MOTOR CONTROL BOARD (MCB) AUTO CONFIGURE
3.5.2 MOTOR CURRENT LIMITING
3.5.3 MOTOR SOFT STOPS
3.5.4 MOTOR SLOW/FAST SPEED
3.5.5 COMMUNICATION PROTOCOL
3.5.6 OSCILLATE AND STOW FEATURES
3.5.7 SMART STREAM TECHNOLOGY
4.1 STRUCTURAL REQUIREMENTS FOR MONITOR MOUNTING ....7
4.2 INLET FITTINGS or EXTEND-A-GUN RC INSTALLATION ......8-9
4.3 NOZZLE CONNECTION ..................................10
4.4 HORIZONTAL ROTATION TRAVEL STOPS ................10-11
4.5 PRESSURE GAGE PORT.................................11
4.6 AUTOMATIC DRAIN .....................................11
5.1 PRIMARY MONITOR OPERATOR STATION ..................14
5.1.1 MOUNTING
5.1.2 ELECTRICAL WIRING
5.1.3 INPUT SIGNAL CONFIGURATION
5.1.4 PANEL MOUNT OPERATOR STATION
5.2 TETHER MONITOR OPERATOR STATION ...................16
5.2.1 HOLSTER MOUNTING
5.2.2 RECEPTACLE MOUNTING
5.2.3 ELECTRICAL WIRING
5.3 WIRELESS MONITOR OPERATOR STATION ..............17-18
5.3.1 MOUNTING STORAGE BRACKET
5.3.2 INSTALLING RADIO
5.3.3 TEACHING ID CODE
5.3.4 CHANGING BATTERIES
5.4 JOYSTICK MONITOR OPERATOR STATION...............18-19
5.4.1 MOUNTING
5.4.2 ELECTRICAL WIRING
5.4.2.1 WIRING TO A COMMUNICATION INTERFACE BOX
5.5 TOGGLE SWITCH MONITOR OPERATOR STATION ...........20
5.5.1 ENCLOSURE MOUNTING
5.5.2 ELECTRICAL WIRING
5.6 COMMUNICATION INTERFACE BOX.....................20-21
5.6.1 ENCLOSURE MOUNTING
5.6.2 ELECTRICAL WIRING
5.6.3 INPUT SIGNAL CONFIGURATION
5.7 MONITOR POSITION DISPLAY ............................22
5.8 REMOTE AUXILIARY INTERFACE BOX ...................22-23
5.10 HURRICANE RC AERIAL TRUCK INSTALLATION ............23-26
5.10.1 ELECTRONICS ENCLOSURE MOUNTING
5.10.2 ELECTRICAL WIRING
5.10.2.1 LADDER INSTALLATION ELECTRICAL WIRING
5.10.2.2 PLATFORM INSTALLATION ELECTRICAL WIRING
5.11
6.1 MANUAL OVERRIDE HANDWHEELS .........................26
6.2 ELECTRICAL MODEL ...................................26-29
6.2.1 OPERATOR STATIONS
6.2.1.1 MONITOR MOUNTED OPERATOR STATION
6.2.1.2 PANEL MOUNT OPERATOR STATION
6.2.1.3 TETHER OPERATOR STATION
6.2.1.4 WIRELESS OPERATOR STATION
6.2.1.5 JOYSTICK OPERATOR STATION
6.2.1.6 TOGGLE SWITCH OPERATOR STATION
6.2.2 MASTER OVERRIDE FEATURE
6.2.3 STOW FEATURE
6.2.3.1 PROGRAMMING
6.2.3.2 STOW PROGRAMMING EXAMPLE
6.2.4 OSCILLATE FEATURE
6.2.4.1 PROGRAMMING
6.2.4.2 OSCILLATE PROGRAM RETAIN FEATURE
6.2.5 OPERATOR STATION PANELS
6.3 RECOMMENDED MONITOR STOWING POSITION ..............29
6.5 FLOWS & PRESSURES .................................29-33
6.5.1 STACKED TIPS FLOW AND REACH
6.5.2 AUTOMATIC NOZZLES
6.5.3 HURRICANE RC MONITOR FRICTION LOSS
6.6 STREAM STRAIGHTENERS ................................33
6.6.1 STREAM STRAIGHTENERS WITH STACKED TIP NOZZLES
6.6.2 STREAM STRAIGHTENERS WITH FOG NOZZLES
8.1 LUBRICATION............................................35
8.1.1 ELEVATION CONTROL WORM GEAR
8.1.2 HORIZONTAL ROTATION WORM GEAR
8.2 PERFORMANCE TESTING .................................35
9.1 HURRICANE RC MONITOR ASSEMBLY ....................36-37
9.2 ELEVATION CHAIN DRIVE ASSEMBLY........................38
9.3 GEAR MOTOR ASSEMBLY .................................38
9.4 MONITOR CONTROL BOX ASSEMBLY........................39
1.0 MEANING OF SAFETY SIGNAL WORDS ........................3
2.0 SAFETY ...................................................3
3.0 GENERAL INFORMATION ....................................3
4.0 INSTALLATION 7-8
5.0 ELECTRICAL CONTROLS INSTALLATION......................12
6.0 OPERATION ..............................................26-33
7.0 TROUBLESHOOTING ......................................34-35
8.0 MAINTENANCE AND INSPECTION ..............................35
9.0 EXPLODED VIEW DRAWINGS AND PARTS LIST ................36-39
10.0 WARRANTY.........................................Back Cover
5.9 CONNECTING MONITOR CABLE DIRECTLY TO PROTECTED POWER
SUPPLY 23
ELECTRICAL NOZZLE ACTUATOR WIRING ...................26
6.4 AUTOMATIC DRAIN .......................................29
.....................................
Table of Contents
2

CAUTION The electric Hurricane RC may be remotely operated. The electric drives are current limited but
may still produce enough force to cause injury. Keep hands and fingers away from pinch points on
the monitor.
CAUTION
CAUTION
CAUTION
Do not use the manual override handwheels while the electric controls are in operation. The
electric drives produce enough torque to cause injury.
Maximum pressure is 200 psi (14 bar). Damage or injury may result if the monitor is operated
beyond these limits.
1.0 MEANING OF SAFETY SIGNAL WORDS
A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with a
particular hazard. Per ANSI standard Z535.4-1998, the definitions of the three signal words are as follows:
DANGER
CAUTION
WARNING
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death
or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury.
The stream exiting a monitor is very powerful and capable of causing injury and property damage.
Make sure the monitor is securely attached to the base and pointing in a safe direction before water
to the monitor is turned on. Use care in directing the stream.
Injury can result from an inadequately supported monitor. The monitor mount must be capable of
supporting 1500 lbs (700 kg) of nozzle reaction force.
2.0 SAFETY
3.0 GENERAL INFORMATION
WARNING
The operation of this monitor can be dangerous. The following must be observed at all times.
The Task Force Tips’ HURRICANE RC is an electric remote monitor, with a single low-profile waterway discharge. It has high flow and
low friction loss characteristics. Capable of flowing 1250 gpm (4500 l/min) while maintaining a FULL 450° of rotational travel (225° either
side of center position). Maximum operating pressure is 200 psi (14 bar). Field changeable horizontal rotation stops at 45°, 90° and 135°
either side of center position. Elevation range is 90° above horizontal and 45° below. Designed for field changeable 12 or 24 VDC
operation. The Hurricane RC comes with a factory installed control panel mounted on the monitor for controlling horizontal rotation,
elevation and nozzle pattern. See Task Force Tips’ Price List and Product Specifications for additional control stations. Unit comes with
30 feet of ultra-flexing robotic cable, enclosed in a unique wire guide, already wired to the monitor so installation effort is minimized.
Large handwheels are provided on the horizontal rotation and elevation drive for manual override. TFT's Master Stream 1250 nozzle
plugs into the factory installed nozzle power wire. All electrical components affecting water tightness are a minimum of NEMA 4 (IP65).
Motors and control boxes are factory tested for water tightness. Available with various inlet adapters for flanges and thread fittings. Inlet
also made for direct connection to TFT's Extend-A-Gun RC3 or RC4. Standard outlet is 2-½” National Hose male (65mm). Other outlets
are available (see figure 3.3). A threaded port (0.25” NPT) (6.4mm) is provided for pressure gauge. The monitor is made from hardcoat
anodizedANSI 356.0-T6 aluminum and silver powder coat finish inside and out.
3
3.1 SPECIFICATIONS
Weight 39 lbs 17.7 kg
Min. Flow Area 7.07 in 45.6 cm - 3” inlets
Max Flow 1250 gpm 4500 l/min
Max Operating Pressure 200 psi 14 bar
Materials Used ANSI 356.0-T6 Aluminum, Stainless, Nylon
22
3.1.1 MECHANICAL SPECIFICATIONS
On many vehicle installations the monitor is the highest point on the apparatus. Often it is critical that the monitor be properly stowed
before driving to avoid damage to overhead obstructions such as door openings. In these cases the use of a switch wired into the
apparatus "door open" circuit is highly recommended. The switch should be wired to give a "door open" signal if the monitor is not in the
stowed position. Due to the variety of possible mountings and nozzles, it is the installer's responsibility to supply the appropriate switch

Nominal Operating voltage: 12 or 24 VDC
(field changeable)
Motor current: Nominal* Limit
Elevation motor: 6 amps 15 amps
Horizontal rotation motor: 6 amps 10 amps
Nozzle motor: 1 amp 5 amps
*with rated water pressure applied
At rest current: .25 amps
Recommended fuse or circuit breaker size: 15 amps @ 12 volts, 7.5 amps @ 24 volts
Operating temperature range: -30°F to +120°F (-34°C to +49°C)
Environmental Rating: All components designed to meet minimum rating of NEMA 4 (IP65).
3.2 PART IDENTIFICATION AND MODELS
The Hurricane RC Monitor as shown in Figure 3.2 along with the names of some various parts and controls.
FIG 3.2
Part Identification
4
3.1.2 ELECTRICAL SPECIFICATIONS
BUILT IN
STREAM
STRAIGHTENER
ELEVATION DRIVE
HOUSING (SECT. 9.2)
HORIZONTAL
ROTATION TRAVEL
STOPS 5 PLACES
(SECT. 4.4)
AUTOMATIC
DRAIN
(SECT. 4.6 & 6.4)
OUTLET
(FIGURE 3.3)
GREASE ZERK
(SECT. 8.1)
PRODUCT NAME LABEL
WITH SERIAL# & MODEL #
POWER CABLE
ELEVATION
MOTOR (SECT. 9.3)
WIRE SKIRT/CABLE GUIDE
(SECT. 9.1)
INLET
(FIGURE 3.3)
STRAIGHT BACK
REFERENCE MARK
(SECT. 4.2)
PORT FOR
PRESSURE GAGE
(SECT. 4.5)
HORIZONTAL
ROTATION
HANDWHEEL
(SECT. 6.1)
ELEVATION
HANDWHEEL
(SECT. 6.1)
CONTROL STATION BOX
WITH CONTROL BUTTONS
(SEE SECT. 6.2.1.1)
GREASE ZERK
(SECT. 8.1)
HORIZONTAL
MOTOR
(SECT. 9.3)
Handheld Unit Batteries
Transmitting Power
Operating Range
Operating Frequency
Four (AA) Batteries, Lithium Recommended
100mW 50mW
500 ft (152m)
Agency Approvals
FCC.......................OUR9XSTREAM .......OUR24XSTREAM
Industry Canada (IC).........4214A-9XSTREAM ........4214A-12.008
Europe ..........................N/A..................ETSI
YE-RF-900, 900 MHz YE-RF-2400, 2.4 GHz
900 MHz
(902-928 MHz)
2.4GHz
(2.4000-2.4835 GHz)
Wireless Operator Station (YE-RF-##)

3.3 INLETS AND OUTLETS
The standard Hurricane RC Monitor inlet is CODE-RLF for direct connection to TFT's Extend-A-Gun RC3. Monitor inlet CODE-RPF is
available for direct connection to Extend-A-Gun RC4. The standard outlet is 2-½”-6 National Hose male. Various other inlet and outlet
fittings are available as shown in Figure 3.3.
5
FIG 3.3
Inlets And Outlets
2.5"-7.5 NH
(65mm) MALE
2.5"-11 BSP
(65mm) MALE
2.5"-11.5 NPSH
(65mm) MALE
SPECIAL
THREADS
CODE-RLF FEMALE
or
CODE-RPF FEMALE
3.0" NPT FEMALE (Y4440NL)
or
4.0" NPT FEMALE (Y4450NP)
EXTEND-A-GUN RC3
or
EXTEND-A-GUN RC4
3.0"ANSI 150 (Y4410A)
or
4.0"ANSI 150 (Y4415A)
or
DN80, PN16 (Y4423A)
or
DN100, PN16 (Y4425A)
FLANGE
3.0"BSP MALE (Y4420A)
or
4.0"BSP MALE (Y4430A)

3.4 OVERALL DIMENSIONS
6
FIG 3.4
Overall Dimensions
3.4.1 OVERALL HEIGHT INCREASE FOR INLET FITTINGS
MODEL INLET FITTING TYPE ADDITIONAL HEIGHT OVERALL HEIGHT
XFIH-E1*A
XFIH-E2*A
XFIH-E4*A
XFIH-E5*A
XFIH-E6*A
XFIH-E7*A
XFIH-E8*A
XFIH-E9*A
3” ANSI 125/150 .75” 16.18”
(metric DN8 PN20) 20 mm 412 mm
4” ANSI 150 .94” 16.37”
(metric DN100 PN20) 23 mm 415 mm
metric DN80, PN16 2.80” 18.23”
22 mm 414 mm
metric DN100, PN16 2.80” 18.23”
22 mm 414 mm
3” NPT Female 2.00” 14.43”
51 mm 443 mm
4” NPT Female 1.75” 17.18”
45 mm 436 mm
3” BSP Male 2.30” 17.73”
58 mm 450 mm
4” BSP Male 2.30” 17.73”
58 mm 450 mm
* The second to last digit in the model number refers to exit thread size and type.
3.3.1 INLET FLANGE SIZE SPECIFICATIONS
MODEL FITS FLANGE OUTSIDE THICKNESS BOLT HOLE
HOLES BOLTS
XFIH-E1*A 3” ANSI 125/150 7.5” .75" 6.0" 4 5/8" 76-80 FT-LBF
(metric DN8 PN20) 190mm 20mm 152.5mm 4 M16 100-110 Newton Meters
XFIH-E2*A 4" ANSI 150 9.0" .94" 7.5" 8 5/8"
NO. BOLT SIZE OF TORQUE ON BOLTS
DIAMETER CIRCLE
76-80 FT-LBF
(metric DN100 PN20) 230mm 23mm 190.2mm 8 M16 100-110 Newton Meters
XFIH-E4*A metric DN80, PN16 200 mm 22 mm 160 mm 8 16 mm 100-110 Newton Meters
XFIH-E5*A metric DN100, PN16 220mm 22 mm 180 mm 8 16 mm 100-110 Newton Meters
* The second to last digit in the model number refers to exit thread size and type.
SHOWN
WITHOUT
INLET FITTING
(SEE TABLE
IN SECT. 3.4.1
FOR
ADDITIONAL
HEIGHTS)
16.24
[413MM]
15.43
[392MM]
5.50
[140 MM]
10.74
[273MM] 5.89
[150MM]
3.64
[93MM]
V
E
R
T
I
C
A
L
R
A
N
G
E
O
F
M
O
T
I
O
N
A
B
O
V
E
4
5
D
E
G
.
B
E
L
O
W
9
0
D
E
G
.

7
3.5 ELECTRICAL CONTROLS
The electric Hurricane RC monitor is controlled by a very powerful, state-of-the-art electronics system. The key components of the
system are the motor control boards and a communication board. Each motor control board has its own microprocessor and a
sophisticated motor control chip. The communication board also has a microprocessor, which handles the interface to the operator
stations. All the components on these boards are solid state; there are no relays or electro-mechanical devices to wear out over time.
The hardware and software have been designed with several key features:
3.5.1 MOTOR CONTROL BOARD (MCB) AUTO CONFIGURE
Each monitor has three MCBs, one for each motor, which controls motor movement and direction for horizontal rotation, elevation, and
nozzle pattern. In the unlikely event of a MCB failure, the failed board can be removed and one of the other two remaining MCBs can be
moved into that position. This MCB will then auto configure itself to take over the control of that axis, so that the monitor can continue to
be used, with two of the three motors. This is also a helpful benefit when troubleshooting and requires fewer spare parts to be stocked.
3.5.2 MOTOR CURRENT LIMITING
The microprocessor on the MCB continuously monitors the motor current. As the motor reaches an end stop or if there is an obstruction,
the motor current rises very quickly and the motor control chip automatically shuts down the motor in a few milliseconds. This eliminates
the need for any type of external limit switches and the associated wiring. The microprocessor also locks the operator from moving in the
stopped direction again, until the operator first moves in the opposite direction.
3.5.3 MOTOR SOFT STOPS
The horizontal and vertical motors are equipped with feedback encoders, which allow the microprocessor to know the motor position at
all times. The first time a motor reaches an end stop or strikes an obstruction, the microprocessor sets a new soft stop position just
before the end stop. From that point on, when the axis approaches the stop, the MCB automatically slows down the motor until the end
stop is reached. This significantly reduces the wear on the motor, gearbox, and external gears.
3.5.4 MOTOR SLOW/FAST SPEED
When an operator presses one of the buttons, the associated motor starts in slow speed mode so that the operator can accurately
control the water stream. After approximately 1-2 seconds the motor automatically ramps up to a fast speed, for quickly moving into
position. When quickly changing directions, monitor retains speed from prior move. If low speed is selected, monitor does not ramp to
high speed but remains in slow speed.
3.5.5 COMMUNICATION PROTOCOL
The communication from the monitor to the operator stations is performed over two wires using RS-485 serial protocol. Multiple
operator stations can be added with only two wires for power and two wires for the RS-485 protocol between each station.
4.1 STRUCTURAL REQUIREMENTS FOR MONITOR MOUNTING
The structure that the Hurricane RC Monitor is mounted to must withstand
the internal pressure of the monitor as well as shear and bending forces due
to nozzle reaction. Nozzle reaction can be as high as 1,050 lbs (480 kg) (1250
gpm at 200 psi).
For flanged connections, the use of flat flanges without raised faces is
recommended. Use a full-face gasket as defined in SME 16.21 or ISO 7483.
Tighten flange bolts in an alternating sequence as shown in figure 4.1.
Tighten to 76-80 ft-lb (100-110 Newton-Meters).
4.0 INSTALLATION
Injury can result from an inadequately supported monitor. The monitor mount must be capable of
supporting the nozzle reaction force which can be as high as 1500 lbs (700 kg). Flanges and pipe
made from plastic are inadequate for monitor mounting and must not be used. This monitor is not
recommended for portable use.
WARNING
FIG 4.1 - Flange Bolt Tightening Sequence
Tighten sequentially each bolt three times.
1
2
3 4
1
2
3
5
6
7
8
4
3.5.6 OSCILLATE AND STOW FEATURES
The OSCILLATE feature allows the user to program up to 65 points of continuous movement of the horizontal and vertical axes. The
OSCILLATE pattern can be programmed from any operator station that has the OSC button.
The STOW feature allows the user to move the monitor, with one touch of a button, to a safe position before moving the fire truck. The
monitor will always move to two end stops to verify the correct position. During the programming procedure, the user has the ability to
select which axis moves first. This is helpful to avoid lights, hoses, obstructions, etc. The user can program up to 10 points of movement
to reach the final STOW position. The STOW pattern can be programmed from any operator station that has the STOW button.
See section 6.2.3 and 6.2.4 for programming instructions.
3.5.7 SMART STREAM TECHNOLOGY
This technology, only available with TFT RC nozzles, utilizes a position encoder in the nozzle actuator to give the user greater control on
the stream pattern, especially at FOG position. Nozzles equipped with a FLUSH position are programmed to stop and pause at full FOG
position when moving towards the FLUSH position, preventing unwanted water flow. A second press on the button will cause the nozzle
shaper to continue to move to FLUSH position for removing debris from the nozzle.

8
4.2 INLET FITTINGS OR EXTEND-A-GUN RC INSTALLATION
The Hurricane RC Monitor is available with various inlet fittings as shown in figure 3.3. The Hurricane RC Monitor also connects directly
to TFT's Extend-A-Gun RC3 or RC4. The fittings and Extend-A-Gun RC are attached to the monitor by means of a threaded joint with an
o-ring seal. Once in the proper orientation, the threaded joint is locked from rotation by two ¼-28 button head cap screws as shown in
figure 4.2A. This makes for easy removal of the monitor, since the large threads of the joint are not tightened and do not have any thread
locking compounds on them. It is best to install the inlet fitting or Extend-A-Gun RC to the apparatus and than install the monitor to the
inlet fitting or Extend-A-Gun RC. This gives more room to install the bolts in the case of flanged fittings. Referring to figures 4.2A and
4.2B, the installation sequence is as follows:
1) Install inlet adapter or Extend-A-Gun RC to apparatus.
• Mount so that 180 degree apart threaded cross holes will give desired direction relative to the “Straight Back Reference Mark”
when the monitor is installed.
2) Screw monitor onto inlet adapter or Extend-A-Gun RC until threaded joint bottoms out.
• Do not use pipe dope or Loctite on the inlet base threads. These threads are sealed with an o-ring. The use of thread locking
compounds will make removal difficult.
3) Unscrew monitor slightly until a pair of 90 degrees apart slots line up with the 180 degrees apart threaded cross holes in the inlet
adapter or Extend-A-Gun RC.
• Orient monitor so that the Straight Back Reference Mark is facing the desired direction.
• Slots will line up with threaded cross holes every 90 degrees of rotation.
• Monitor may be unscrewed up to one full turn from the bottomed out position.
4) Install ¼-28 by ½ long button head cap screws and washers in the two threaded cross holes.
FIG 4.2A
3” Inlet Fitting Connection
(This view shown without power cable guide for purposes of illustration.)
90 DEGREE
APART SLOTS
180 DEGREE APART
THREADED HOLES
INLET BASE
INLET FITTING MOUNTED TO APPARATUS
3.0" ANSI 150 SHOWN, OTHERS SIMILAR
1/4-28 X 1/2LONG
BUTTON HEAD CAP SCREW
2 PLACES
(TFT# VT25Y28BH504)
WASHER 2 PLACES
(TFT# VW687X281-50)
STRAIGHT BACK
REFERENCE MARK

9
FIG 4.2B
Possible Extend-A-Gun RC Mounting Orientations
The Extend-A-Gun RC manual override knob may be mounted
in any one of four possible orientations (90 degrees apart).
The Extend-A-Gun manual override knob may be mounted in any of four possible orientations (90 degrees apart) relative to the Straight
Ahead Reference Mark on the monitor.
NOTE: Hurricane RC monitor, for use with Extend-A-Gun RC, comes with the wire installed in a nylon tube. The nylon tubing gives the
wire additional stiffness so it better follows as the Extend-A-Gun RC extends or retracts.A fitting is also supplied and is to be used where
the nylon tubing and wire pass though the deck.
STRAIGHT BACK
REFERENCE MARK
(SEE FIGURE 4.2A)
MANUAL OVERRIDE
KNOB ON
EXTEND-A-GUN
1-1/4 TURNS
APPROX. 34 IN.
1 TURN
APPROX. 33 IN.
3/4 TURNS
APPROX. 33 IN.
1-1/2 TURNS
APPROX. 37 IN.

4.3 NOZZLE CONNECTION
The Hurricane RC monitor outlet thread types are as shown in figure 3.3. The nozzle is simply screwed onto the Hurricane RC monitor's
exit threads. Insure that the nozzle's coupling does not make contact with the elevation drive housing when the monitor is in its highest
elevation position.
For nozzles with electric pattern control, a waterproof connector wire is provided at the bottom outlet of the Hurricane RC's control
station box. This wire attaches directly to TFT's electric Masterstream 1250 nozzle. The electric actuator box of nozzle must be oriented
to the top side of nozzle for the connection wire to extend 90° above horizontal and 45° below elevation movement. (see figure 4.3 and
refer to Sections 5.12 and 6.6.2 for properly attaching female to male connectors). Any other nozzle should have the corresponding
male electrical connector installed and long enough wire to extend of the
nozzle.
90° above horizontal and 45° below elevation movement
DO NOT CUT OFF THE FEMALE CONNECTOR ON THE MONITOR. THIS CONNECTOR IS MOLDED ONTO THE WIRE
AND MUST REMAIN ON TO MAINTAIN THE WATER TIGHTNESS OF THE ELECTRICAL SYSTEM.
CAUTION The nozzle threads must match the threads on the Hurricane RC in both size and type.
Mismatched or damaged threads may cause the nozzle to leak or uncouple under pressure and
could cause injury.
CAUTION Do not connect aluminum to brass or brass to aluminum. Dissimilar metals coupled together can
cause galvanic corrosion that will freeze the threaded joint or cause complete loss of thread
engagement. If dissimilar metals must be coupled together, the effects of corrosion can be greatly
delayed by various coatings on the metal such as powder paint, hard anodizing or silicone grease.
FIG 4.3
Correct ER Nozzle Install Orientation
CAUTION:
TFT's Master Stream 1250 ER Nozzle
Electric Actuator Box must be on the Top
Side for its Edge to line up with Monitor
Waterway Top Body as shown.
4.4 HORIZONTAL ROTATION TRAVEL STOPS
The range of Horizontal (left-right) travel for the Hurricane RC monitor is limited to 450 degrees or 225 degrees from either side of a
nozzle discharge position. Horizontal (left-right) travel stop bolts may be installed in the monitor to limit travel as shown in figure 4.4A and
4.4B. Note that left and right are relative to the “Straight Back Reference Mark” shown in figure 4.4A, and refer to the operator's position
behind the monitor, opposite the nozzle's discharge direction. Also, Figure 4.4A shows the range of travel for the various stop bolt
locations along with installation notes as shown in Figure 4.4B.
10

11
FIG 4.4A
Horizontal Travel Limits
FIG 4.4B
Horizontal Travel Stop Bolt Locations
4.5 PRESSURE GAUGE PORT
There is a ¼” NPT female threaded hole located behind the elevation hand wheel for the installation of a pressure gauge if desired. This
hole has a pipe plug installed from the factory. Unscrew the pipe plug and install the gauge using pipe sealant. Make sure that the gauge
does not interfere with the handwheel.
4.6 AUTOMATIC DRAIN
There is an automatic drain on the Hurricane RC installed from factory, that will empty the water from the low point of the lower bend to
prevent freezing (Figure 3.2). The valve closes when the internal pressure is approximately 5 psi (0.3 bar) or above and opens when the
internal pressure is below 5 psi (0.3 bar). Refer to Section 6.4 for disabling the automatic drain if desired.
Asecondary drain valve should be installed on the monitor's inlet piping to drain water in the riser.
45
90
RIGHT
RIGHT
Pry out plastic plug and
install Stop Bolt(s)
to obtain desired
travel limits.
(TFT# Y4145)
135 LEFT AND RIGHT
(ONLY ONE STOP BOLT
NEEDED FOR THIS
TRAVEL LIMIT)
90 LEFT
45 LEFT
STRAIGHT BACK
REFERENCE MARK
°
°
°
°
°

12
5.0 ELECTRICAL CONTROLS INSTALLATION
The electric RC monitor is supplied with a monitor mounted operator station. The wiring on the monitor and for this operator station is
factory installed. The assembly is supplied with a 30-foot length of cable for connection to the operator control stations as shown in
Figure 5.0 or directly to a protected voltage supply. This cable has 4-conductors which supply power and the communications from the
operator stations to the monitor. To complete the installation, the installer will need to mount and wire the selected operator stations. The
power supply for the monitor will need to be connected to a protected circuit from the truck's power distribution center. Refer to the
specifications section 3.2.1 for nominal current draw.
For installations where the customer would like to turn off the voltage to the monitor independent of the truck master switch, the installer
needs to install a SPST (single-pole single-throw) toggle switch. Install this toggle switch in a location that can quickly be accessed
before using the RC monitor. The toggle switch needs to be wired between the protected voltage supply and the red wire feeding the RC
monitor.
Good mechanical connections on the wires are absolutely necessary and should be checked periodically. Poor electrical
connections can cause power loss to the electric RC monitor and be a fire hazard.
Careful selection of wiring is critical to avoid excessive voltage drop.
Be careful to route cables in a protected area away from high heat sources.
Use grommets whenever wires pass through holes to prevent damage due to snags, abrasions, etc.
Secure cables close to control box with plastic wire ties or cable clamps to relieve stress on the cables.
Disconnect power before installing or servicing the electrical components. The RC monitor control boxes and motors are not rated
as ignition proof, explosion proof, or intrinsically safe.
!
!
!
!
!
!
The electric motors and other components are ignition sources. The electric drives should be
operated only in areas where there is adequate ventilation and no hazard of flammable vapor
buildup.
WARNING
11/32” nut driver
20mm open-end box wrench
17mm open-end box wrench
5/32” drill bit
25/32” drill bit
#2 Phillips screwdriver
Small flat blade screwdriver
Wire cutter/stripper
Terminal crimping tool
Utility knife
Recommended Tool List
IMPORTANT!!
When mechanical installation and electrical connections are complete, perform the following test to verify voltage supply is adequate
and the current limiting feature is functioning.
1) Apply power to monitor control box.
2) Press LEFT or RIGHT button and hold until monitor reaches its stop position. Continue to hold button down.
3) Once movement is stopped, manually turn override knob in opposite direction while continuing to hold button down. If knob
can be turned, then voltage supply is adequate. If knob cannot be turned and motor continues to operate, then the voltage
supply or wiring is not adequate. Check connections and voltage connection point, rewire if necessary. NOTE: Override
knob will only turn in one direction.
6.2.1 OPERATOR STATIONS
6.2.1.1 MONITOR MOUNTED OPERATOR STATION
6.2.1.2 PANEL MOUNT OPERATOR STATION (Y4E-RP)
6.2.1.3 TETHER OPERATOR STATION (Y4E-CT-##)
6.2.1.4 WIRELESS OPERATOR STATION (YE-RF-##)
6.2.1.5 JOYSTICK OPERATOR STATION (Y4E-JS)
6.2.1.6 TOGGLE SWITCH OPERATOR STATION (Y4E-TS)
IMPORTANT
Review these sections and decide on locations before starting
installation process.

13
FIRE FIGHTING EQUIPMENTFIRE FIGHTING EQUIPMENT
TASK FORCE TIPSTASK FORCE TIPS
800-348-2686800-348-2686
FOG
POWER
www.tft.comwww.tft.com
STRAIGHT
STREAM
Read manual before use.Read manual before use.
WARNINGWARNING
Y5700
OSC STOW
AUX1 AUX2
FIRE FIGHTING EQUIPMENTFIRE FIGHTING EQUIPMENT
TASK FORCE TIPSTASK FORCE TIPS
800-348-2686800-348-2686
FOG
POWER
www.tft.comwww.tft.com
STRAIGHTSTRAIGHT
STREAM
Read manual before use.Read manual before use.
WARNING
Y5700
OSC STOW
AUX1 AUX2
INSTALLER SUPPLIED
TERMINAL BOX
POSITION DISPLAY
(sec 5.7)
RED RED
BLACK BLACK
BLUE BLUE
WHITE WHITE
RED
BLACK
TYPICAL TERMINAL BOX
CONNECTIONS
BLUE
WHITE
MULTIPLE OPERATOR STATIONS MAY BE INSTALLED. ALL
COMMUNICATION PAIRS (BLUE & WHITE) AND POWER
PAIRS (RED & BLACK) MUST BE CONNECTED IN TERMINAL
BOX OR ANOTHER OPERATOR STATION.
REMOTE AUX FUNCTION
RELAY INTERFACE
(sec 5.8)
-or-
MONITOR MOUNTED
OPERATOR STATION
Fig 5.0 Electrical Components
(non-aerial installation)
INSTALLER SUPPLIED
POWER CABLE
**See Note
COMMUNICATION
INTERFACE BOX
(sec 5.6)
TETHER
OPERATOR STATION
(sec 5.2)
PANEL MOUNT
OPER. STATION
(sec 5.1)
WIRELESS
OPERATOR STATION
(sec 5.3)
NO WIRING REQUIRED
Recommended Cable Gauge
Max Length* Gauge
40 ft (12m) 14AWG
65 ft (20m) 12AWG
80 ft (24m) 2-14AWG
105 ft (32m) 10AWG
130 ft (40m) 2-12AWG
*Based on 12 volt nominal truck power
**Note
To avoid excessive voltage drop at monitor operator
station, do not lengthen factory supplied monitor
cable. Power cable selection is critical.
Voltage supplied to TERMINAL BOX should not fall
below 13 volts when monitor is in operation.
*2/C—14, 2/C—20 CABLE
INSTALLER SUPPLIED
AUXILIARY FUNCTIONS:
WATER VALVE
LIGHTS
JOYSTICK
OPERATOR STATION
(sec 5.4)
INSTALLER SUPPLIED INPUTS:
CANBUS
TOGGLE SWITCH
JOYSTICK
*
*
*
*
*
*
2/C—14, 2/C—20
30 ft (9m) maximum
TOGGLE SWITCH
OPERATOR STATION
(sec 5.5)

5.1 PANEL MONITOR OPERATOR STATION (Y4E-RP)
This operator station allows the monitor to be controlled from a remote location. The installer will need to mount the operator station and
connect the cable to the monitor and power. The enclosure is designed to be recess mounted in a panel.
This operator station has extra power and communication terminal blocks available and can be used as a central location for terminating
wires. In this type of installation the monitor cable, the power cable, and possibly other operator station cables could be installed into
this operator station. On the back of this enclosure are extra strain relief fittings.
In many installations this operator station will also include the wiring connections for the joystick, Canbus output module or installer
supplied toggle switches. A terminal block is available for “UP, DOWN, LEFT, RIGHT, FOG, SS, STOW” inputs. The circuit board in this
operator station is factory configured to accept ground input signals but can be field changed to accept +12/24 volt DC input signals.
5.1.1 MOUNTING
Select proper operator location. Panel space required will be 5-5/8” x 8” (142 x 200mm). A depth of 3-1/2” (89mm) will be required
behind the panel. Additional space will be required where the cables exit the back of the enclosure. Refer to Figure 5.1.1 for cutout
dimensions.
Fig 5.1.1
Panel Mount Operator Station Cutout Dimensions
5.1.2 ELECTRICAL WIRING
See figure 5.0 for typical connections. The 4-conductor cable from the operator station needs to be connected to power (red & black)
and to the communication link (blue & white) from the monitor. Refer to Figure 5.1.2 for typical cable preparation. Be sure to tighten all
terminal block screws securely.
Fig 5.1.2
Typical Cable Preparation
5-1/8
(130 mm)
7-7/16
(190 mm)
14
TIGHTEN DOME NUT
TO 37 IN-LBS (4.2 N-M)
STRIP 1/4" (6mm)
OF INSULATION
REMOVE 6" (150mm) OF
JACKET AND TEFLON TAPE
1/8" (3mm) OF CABLE JACKET
PAST FITTING NOTE:
CABLE IS GEL FILLED TO PREVENT MOISTURE WICKING
INTO ENCLOSURE. GEL IS NON-HAZARDOUS AND
SHOULD BE WIPED OFF CONDUCTORS WITH RAG.

5.1.3 INPUTS SIGNAL CONFIGURATION
Figure 5.1.3
Panel Mount Operator Station
The Panel Mount Operator Station is shipped from the factory configured to accept , but can be field changed to
accept . To change the configuration:
1. Remove lid from enclosure.
2. Locate DIP switches on communication board.
3. Slide DIP switch #4 to the OFF position to select GROUND inputs or slide to the ON position to select VOLTAGE inputs.
4. Replace lid. Verify rubber seal is clean and undamaged. Verify that no wires are caught between lid and box.
ground input signals
+12/24 volt DC input signals
VOLTAGE
INPUTS
GROUND
INPUTS
5.1.4 PANEL MOUNT OPERATOR STATION WITH AT STOW RELAY (Y4E-RP)
The Panel Mount Operator Station provides feedback for the user that the monitor is in the AT STOWED position. The Operator station
contains a circuit board that is equipped with a relay that is energized when the monitor is in use and de-energized when the monitor
reaches its final STOW location. The contact rating of the relay is 1 amp @ 30VDC for resistive loads and 0.2 amps @ 30VDC for
inductive loads.
The AT STOW relay has one Form-C contact (common, normally open, normally closed) that can be used. The
figure above shows the terminal blocks available for user wiring.
Figure 5.1.4
Relay / Terminal Location
AT STOW RELAY
USER TERMINALS
15

5.2.1 HOLSTER MOUNTING
Select proper location for mounting holster, preferably inside a storage compartment. Panel space required will be 6.5” x 8.0” (165 x
203mm). Refer to Figure 5.2.1for hole dimensions. Holster can be used as template.
Fig 5.2.1 Tether Operator Station Holster Hole Dimensions
Material Use Material Use
Thickness Drill Thickness Drill
5/64-3/32 .206 5.2 #5 3/32 .213 5.4 #3
1/8 .213 5.4 #3 1/8 .221 5.6 #2
3/16 .221 5.6 #2 3/16 .228 5.8 #1
Inches mm Inches mm
ALUMINUM STEEL
Hole Size Chart For Self Tapping Screws
Hole Size Hole Size
5 3/4"
(146 mm)
2 7/8"
(73 mm)
7 1/4"
(184 mm)
5.2.2 RECEPTACLE MOUNTING
Select proper location for mounting receptacle. Receptacle is 1-1/4” x 1-1/4” and ½” deep. (32 mm x 32 mm x 13 mm) Allow extra room
behind receptacle for wires. Refer to Figure 5.2.2 for hole dimensions.
Fig 5.2.2
Tether Operator Station
Receptacle Hole Dimensions
Drill (4) .098”
(#40) Holes
7/8”
(22 mm)
7/8”
(22 mm)
25/32”
(20 mm)
HOLE LAYOUT
MOUNT RECEPTACLE WITH
#4 SELF-TAPPING SCREWS.
TIGHTEN SECURELY. INSTALL
CHAIN CONNECTOR
UNDER SCREW HEAD
Y5310 TETHER RECEPTACLE
Y5320 CLOSURE CAP
16
5.2.3 ELECTRICAL WIRING
See figure 5.0 for typical connections. The 4-conductor cable from the receptacle needs to be connected to power (red & black) and to
the communication link (blue & white) from the monitor. Refer to Figure 5.1.2 for typical cable preparation.
Drill (3) Pilot Holes
(refer to hole size chart)
Mount Holster With (3)
1/4-20 Self-Tapping Screws.
Tighten Securely.
This operator station will have a factory installed 4-conductor cable, which will act as a tether, with a plug on the end. The installer will
need to mount the holster and receptacle.
The holster is supplied with(3) 1/4-20 stainless steel self-tapping screws. Make sure the material beneath the bracket is substantial and
thick enough to hold self-tapping screws. Make sure the area on the back side of the mounting surface is clear of obstructions. We
recommend a minimum thickness of 3/32" (.093" - 2.4 mm) in aluminum and 5/64 (.078"-2mm) in steel See the chart in Figure 5.2.1 to
determine the correct pilot hole size.
5.2 TETHER MONITOR OPERATOR STATION (Y4E-CT-##)

17
5.3 WIRELESS MONITOR OPERATOR STATION (YE-RF-##)
The storage bracket is supplied with (3) 1/4-20 stainless steel self-tapping screws. Make sure the material beneath the bracket is
substantial and thick enough to hold self-tapping screws. Make sure the area on the backside of the mounting surface is clear of
obstructions. We recommend a minimum thickness of 3/32" (.093" - 2.4 mm) in aluminum and 5/64 (.078"-2mm) in steel. See the chart
in Figure 5.3.1 to determine the correct pilot hole size.
Select proper location for mounting storage bracket. Panel space required will be 6.0“ x 11.2“ (152 x 285mm). Refer to Figure 5.3.1 for
hole dimensions. Bracket can be used as a template. Be sure spring is in position.
5.3.1 MOUNTING STORAGE BRACKET
Fig 5.3.1 Wireless Operator Station
Storage Bracket Hole Dimensions
Material Hole Size Use Material Hole Size Use
Thickness Inches mm Drill Thickness Inches mm Drill
5/64-3/32 .206 5.2 #5 3/32 .213 5.4 #3
1/8 .213 5.4 #3 1/8 .221 5.6 #2
3/16 .221 5.6 #2 3/16 .228 5.8 #1
ALUMINUM STEEL
Hole Size Chart For Self Tapping Screws
5"
[127mm]
6"
[152mm]
Drill (3) Pilot Holes
(refer to hole size chart)
Mount Bracket with (3)
1/4-20 Self-Tapping Screws.
Tighten Securely.
Spring
5.3.2 INSTALLING RADIO
1) Turn off power and remove lid from monitor control box. Be careful
to open lid slowly as lid will be connected to communication board
by a flat cable.
2) Unplug connector with blue & white wires and remove the small
communication board on the far left.
3) Attach antenna connector to radio board with the cable in the
orientation. (Fig 5.3.2a) Note, in some RC monitors, cable tie may
need to be cut to attach antenna.
4) Plug radio board into communication board. (Fig 5.3.2b) Be careful
to line up pins.
5) Plug communication board/radio board into main board. Press
down to seat securely.
6) Insert connector with blue & white wires into communication board.
7) Replace lid onto box. Be sure to guide flat cable down onto motor
boards and to not pinch any wires between lid and box.
8) Tighten lid screws equally in a criss-cross pattern.
The YE-RF-## Wireless Operator Station is supplied with a radio board that needs to be installed in the monitor control box and a
storage bracket.
Fig 5.3.2a
Fig 5.3.2b

18
*SMART STREAM
1)
2)
NOZZLE STOPS AT FULL FOG
PRESS AGAIN FOR FLUSH
®
TASK FORCE TIPS
FIRE FIGHTING EQUIPMENT
Where New Ideas Flow™ • 800-348-2686 • www.tft.com Y5336
OSCILLATE PATTERN PROGRAMMING:
1)
2)
3)
4)
5)
Move monitor to starting point of pattern.
Press & hold OSC button until LED blinks. LED will continue to blink in program mode.
Move monitor to 2nd point, press OSC button. LED will blink rapidly to acknowledge position.
Repeat until pattern is complete.
Press & hold OSC button until LED turns off.
NOTE: PATTERN WILL BE CLEARED UPON POWER LOSS.
TO OSCILLATE:
Pattern must be programmed first.)
Press & release OSC button.
(
TO STOW:
Press & release STOW button.
(Programmable, refer to manual.)
STRAIGHT
STREAM
FOG
THEN FLUSH*
5.4 JOYSTICK MONITOR OPERATOR STATION (Y4E-JS)
5.4.1 MOUNTING
This operator station allows the monitor to be controlled by a joystick. The installer will need to mount the joystick control and connect the
cable to a receptacle or terminal box with power and communication connections. The joystick control needs to be mounted in a
weatherproof location, for example, inside the cab of the truck.
Select proper weatherproof operating location. Joystick control box requires 4 ¾” x 4 ¾” x 4” (121mm x 121mm x 102mm) of space and
the joystick extends 6 ¼” (159mm) above the control box. Threaded mounting holes are located on the bottom of the joystick control box.
Refer to Figure 5.4.1.1 for hole layout.
Fig 5.4.1.1
Joystick Operator Station Hole Dimensions
5.3.3 TEACHING ID CODE:
Every monitor has a unique ID code that must be “taught or transferred” to the handheld unit. This unique ID code allows multiple
monitors to be used in one location without interference. Perform the following procedure to teach the handheld unit.
-Press POWER button to turn on electronics.
-Press and hold both LEFT & RIGHT buttons for 5 seconds.
-Continue to press LEFT & RIGHT buttons and then press UP button for 2 seconds.
-Release buttons. OSC & STOW lights will flash rapidly to indicate that the unit is in teach mode.
On Handheld Unit:
On Monitor Control Box:
-Apply power to monitor.
-Press and hold both LEFT & RIGHT buttons for 5 seconds.
-Continue to press LEFT & RIGHT buttons and then press UP button for 2 seconds.
-Release buttons. OSC & STOW lights will flash rapidly to indicate that the unit is in teach mode.
-OSC & STOW lights on handheld unit will stop flashing after ID code is transferred.
-Press DOWN button on monitor control box to exit teach mode.
-Cycle power off and back on to monitor.
NOTE: When the operator station is purchased at the same time as RC monitor,
handheld unit will be pre-taught at factory.
5.3.4 CHANGING BATTERIES:
Four (AA) Batteries, Lithium Recommended
-Remove two (2) screws on backside of handheld unit and slide bottom half of rubber bumper off enclosure.
-Replace batteries verifying that polarity is correct.
-Replace rubber bumper and retaining screws.
CAUTION Properly dispose of old batteries. Do not puncture, incinerate, or disassemble batteries.
Do not mix battery types.
5.4.2 ELECTRICAL WIRING
This operator station will have a factory installed 4-conductor cable with a plug on the end. The installer will need to mount the mating
receptacle (YE-RECEP-4) in a suitable location. Refer to Sections 5.2.2 and 5.2.3 for proper receptacle installation and wiring.
When a Valve Kit is used (YE-VK-PH), the receptacle is provided on the valve interface enclosure and is pre-wired to the control system.
NOTE: THE JOYSTICK TRIGGER IS FACTORY WIRED TO THE AUX2 CONNECTION. FOR TRIGGER-CONTROLLED VALVE
OPERATION, THE VALVE INTERFACE RELAYS MUST BE CONFIGURED FOR AUX2.
Fig 5.4.1.2
Joystick Instruction Label
Install joystick instruction label nearby for quick operation reference.
3-5/16"
(84mm)
4"
(102mm)
MOUNT ENCLOSURE
WITH (2) 1/4-20 FASTENERS.
TIGHTEN SECURELY.

19
5.5 TOGGLE SWITCH MONITOR OPERATOR STATION (Y4E-TS)
This operator station allows the monitor to be controlled by three toggle switches. The installer will need to mount the operator station
and connect the cable to the monitor and power.
5.5.1 ENCLOSURE MOUNTING
Select proper operator location. Enclosure is designed to be surface mounted and the size is 5” x 3 1/8” (127 x 80mm). Height to top of
switches is 3 1/8” (80mm). Refer to Figure 5.5.1 for mounting hole dimensions.
4-1/2"
(113 mm)
2"
(51 mm)
Figure 5.5.1
Toggle Switch Operator Station Hole Dimensions
5.5.2 ELECTRICAL WIRING
See figure 5.0 for typical connections. The 4-conductor cable from the operator station needs to be connected to power (red & black)
and to the communication link (blue & white) from the monitor. Refer to Figure 5.1.2 for typical cable preparation
MOUNT ENCLOSURE
WITH (2) 1/4-20 FASTENERS.
TIGHTEN SECURELY.
5.6 COMMUNICATION INTERFACE BOX (Y4E-COMM)
This Communication Interface Box converts discrete input signals into serial communications for controlling the monitor. The discrete
input signals can be from a joystick, toggle switches, relay contacts or Canbus output module. The interface box accepts +12/24 VDC
signals, but can be field changed to accept ground signals. The installer will need to mount the interface box and connect the cable to the
monitor and power.
5.6.1 ENCLOSURE MOUNTING
Select proper enclosure location. Enclosure is designed to be surface mounted and the size is 5” x 3 1/8” (127 x 80mm). Height of
enclosure is 2 3/8” (60mm). Refer to Figure 5.5.1 for mounting hole dimensions.
5.6.2 ELECTRICAL WIRING
See figure 5.0 for typical connections. The 4-conductor cable from the communication interface box needs to be connected to power
(red & black) and to the communication link (blue & white) from the monitor. Refer to Figure 5.1.2 for typical cable preparation.
See figure 5.6.2 for connecting INPUTS cable.
UP
DOWN
LEFT
RIGHT
FOG
STREAM
(-) BLACK
(+) RED
WHITE
BLUE
YELLOW
BROWN
GREEN
ORANGE
BLACK
RED
Function Interface Box
Cable Color
Figure 5.6.2
Communication Interface
Wire Color/Function

20
5.6.3 INPUTS SIGNAL CONFIGURATION
Figure 5.6.3
Communication Interface Box
The Communication Interface Box is shipped from the factory configured to accept +12/24 volt DC input signals, but can be field
changed to accept ground input signals. To change the configuration:
1. Remove lid from enclosure.
2. Locate DIP switches on communication board.
3. Slide DIP switch #4 to the OFF position to select GROUND inputs or slide to the ON position to select VOLTAGE inputs.
4. Replace lid. Verify rubber seal is clean and undamaged. Verify that no wires are caught between lid and box.
5.6.4 COMMUNICATION INTERFACE BOX WITH AT STOW RELAY (Y4E-COMM)
The Communication Interface Box provides feedback for the user that the monitor is in the AT STOWED position. The Interface Box
contains a circuit board that is equipped with a relay that is energized when the monitor is in use and de-energized when the monitor
reaches its final STOW location. The contact rating of the relay is 1 amp @ 30VDC for resistive loads and 0.2 amps @ 30VDC for
inductive loads.
The AT STOW relay has one Form-C contact (common, normally open, normally closed) that can be used. The
figure above shows the terminal blocks available for user wiring.
Figure 5.6.4
Relay / Terminal Location
AT STOW RELAY
USER TERMINALS
VOLTAGE
INPUTS
GROUND
INPUTS
Table of contents
Other TFT Monitor manuals