Thermokon JOY HC AO2DO User manual

JOY HC AO2DO | HC 3AO
Room Regulator (from Version 2.6.x)
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 www.thermokon.com email@thermokon.com
JOY_HC_Datasheet_en © 2023
Datasheet
Subject to technical alteration
Issue date: 01.05.2023 • A125
»APPLICATION
JOY HC AO2DO (85..260 V ~)
Room thermostat in an appealing design for heating/cooling (230 V) and controlling a 6-way valve. Used for individual control of temperature in
commercial and residential buildings. The device combines a modern design with a 2,5” touch surface, which enables the single room controller to
be used intuitively. 3 time channels with 4 periods of time can be configured via the menu. This device is suitable for a flush mount box.
JOY HC 3AO (24 V ~/=)
Modern design, flush mounting room thermostat. Used for individual control of temperature in commercial, industrial and residential buildings. It is
tailored for two-pipe and four-pipe units with two-wire electric valves and controlling a 6-way valve. The device combines a modern design with a
2,5” LCD and a touch-sensitive surface, 3 time program options each with 4 time periods options.
»SECURITY ADVICE – CAUTION
The installation and assembly of electrical equipment should only be performed by authorized personnel.
The product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not be used
in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health o
r life or result in danger to
human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
CAUTION! Risk of electric shock due to live components within the enclosure, especially devices with mains voltage supply
(usually between 90..265 V).
Please comply with:
•Local laws, health & safety regulations, technical standards and regulations
•Condition of the device at the time of installation, to ensure safe installation
•This data sheet and installation manual

Page 2 / 8 Issue date: 01.05.2023
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 www.thermokon.com email@thermokon.com
JOY_HC_Datasheet_en © 2023
»PRODUCT TESTING AND CERTIFICATION
Declaration of conformity
The declaration of conformity of the products can be found on our website https://www.thermokon.de/
»NOTES ON DISPOSAL
As a component of a large-
scale fixed installation, Thermokon products are intended to be used permanently as part of a building or a
structure at a pre-defined and dedicated location, hence the Waste Electrical and Electronic Act (WEEE) is not applicable. However,
most of the products may contain valuable materials that should be recycled and not disposed of as domestic waste.
Please note the
relevant regulations for local disposal.
»MOUNTING ADVISE ROOM SENSORS
The Accuracy of the room sensors are influenced by the technical specifications as well as the positioning and the installation type.
During Assembly:
•Seal mounting box (if present).
•Installation type, air draught, heat source, radiation heat or direct sunlight can affect the measurement.
•Bulding material specific properties of the installation place (brick-, concrete-, partition wall, cavity wall, …) can affect the measurement.
(e.g.: Concrete accepts room temperature variation slower than cavity walls)
Assembly not recommendet in…
•Air draught (e.g.: close to windows / doors / fans …)
•Near heating sources,
•Direct sunlight
•Niches / between furniture / …
»MOUNTING ADVICE JOY
Plasterboard boxes shall be covered by wall paper or paint to avoid that the plasterboard box's front rim will be partially visible underneath JOY.
Maybe consider using white plasterboard boxes (i.e. Kaiser 9063-77).
»APPLICATION NOTICE
Software
Software-description on https://www.thermokon.de/
MicroSD-Card
Data storage device for Update, Upgrade or configuration
- FAT-filesystem required
- NTFS and exFAT filesystems are not supported!
Bootloader
A MicroSD-card Bootloader for loading applications (Update, Upgrade) or configurations is integrated in the device.
active bootlader = ring illumination blinks (1 sec. cycle), display is not triggered!
Firmware
Update
- Remove upper part, insert a microSD-card with valid Update file, mount upper part.
- Valid update file is recognized and the update process is started (ring illumination blinks in a 300ms cycle)
- New application is started automatically after Update (approx. 20-30 sec.).
- Remove upper part, to remove MicroSD-card from the device!
Device
Configuration
- Remove upper part, insert a microSD-card with device configuration file, mount upper part.
- Configuration file is recognized and the device is configured.
- Device ready for operation.
- Remove upper part, to remove MicroSD-card from the device!
The parameters for the display, set point and the controller can only be changed via the configuration software.
»NOTES ON THE UPDATE FUNCTION
An update of the device software is only possible within the version main numbers.
3.0.2 ► 3.0.11
2.6.6 ► 2.3.0
2.x ► 3.x
2.x ► 1.x
»CONFIGURATION VIA UCONFIG | MICRO SD-CARD
Configuration software:
uConfig | Windows 10 is required to use the uConfig configuration software
The JOY room thermostat can be parameterised using the uConfig configuration software. An SD card is used to transfer the
created configuration file to the device.
The installer for the configuration software can be found in the Download-
Section on our website. The installer retrieves all
necessary files and plug-ins from our web server. In this version an update function is integrated in the software.
Download-Section

Issue date: 01.05.2023 Page 3 / 8
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 www.thermokon.com email@thermokon.com
JOY_HC_Datasheet_en © 2023
»TECHNICAL DATA
»JOY HC AO2DO | HC 3AO
Measuring values temperature, humidity (optional)
Measuring range temp 0..+50 °C
Accuracy temperature ±1 K (typ. at 21 °C)
Measuring range humidity
(optional)
0..100% rH non-condensing
Accuracy humidity
(optional)
±2% between 10..90% rH (typ. at 21 °C)
Control functions setpoint adjustment +0..+50 °C
Display LCD 60x44 mm, 240x160 px, white backlighting
Functions integrated PI- and 2-point-/ 3-point-controllers, 2nd control loop: 2-point controller
Enclosure PC, glass, optional black or white
Protection IP30 according to EN 60529
Connection electrical Terminal 1..8
terminal block max. 1,5 mm²
Terminal 9..12
terminal block max. 1.0 mm²
Ambient condition 0..+50 °C, max. 85% rH non-condensing
Weight 195 g
Mounting flush mounted with standard EU box (Ø=60 mm)
»JOY HC AO2DO
Output voltage 0..10 V =, max. load 5 mA (for 6-way valves)
Output switch contact 2x normally open contacts (heating/cooling), 240 V max. load 500 mA
Power supply 85..260 V ~
Power consumption max. 3 VA (260 V ~)
Inputs DI1
input for NTC 10 K or floating
contact
DI2
digital input for non-floating
contact (230 V ~)
DI3
digital input for floating contact
»JOY HC 3AO
Output voltage 3x 0..10 V, max. load 5 mA, 6-way valve control, heating & cooling)
Power supply 24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumption max. 2,5 W (24 V =)
Inputs DI 1
1 input for NTC10K or floating contact
DI 2 | DI 3
2 inputs for floating contact

Page 4 / 8 Issue date: 01.05.2023
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 www.thermokon.com email@thermokon.com
JOY_HC_Datasheet_en © 2023
»FUNCTION DESCRIPTION – CONTROLLER
JOY HC AO2DO (85..260 V ~) JOY HC 3AO (24 V ~/=)
PI controller (PWM) &
2-point/3-point controller
(configurable)
PI controller (0..10 V)
6WV (PI-controller 0..10 V) (all types)
The manipulated variable is output as a proportional control signal at the output for the 6-way valve. The type of valve used is set via the
configuration software. You can choose from 2..10 V / 2..10 V INV (Belimo), 0..10 V DN15 / DN15 INV, DN20 / DN20 INV (Sauter). There is also
the possibility of a freely parameterizable 6-way valve (generic 6WV).
Heating/ cooling with 2-point-/ 3-point-controller (only HC AO2DO)
In the case of temperature control, the 2-point controller only knows the switching states heating ON and heating OFF. The 3-point controller also
knows the switching state of cooling. Two - and three-point controller work with a hysteresis.
Heating/ cooling with PI-controller (PWM) (only HC AO2DO)
The time response of the PI control loop depends on the control parameters xp for the proportional area and tn for the reset time of the integral
range. In case of an error, the P portion immediately changes the position value proportionally to the error variable, while the integral portion
takes effect after a certain time.
The resulting actuating variable is output as a pulse-width-modulated signal directly to the outputs.
Heating/ cooling with PI-controller (0..10 V) (only HC 3AO)
The time response of the PI control loop depends on the control parameters xp for the proportional area and tn for the reset time of the integral
range. In case of an error variable, the P portion immediately changes the position value proportionally to the error variable, while the integral
portion takes effect after a certain time.
The resulting manipulated variable is output as an analogue 0..10 V signal directly to the outputs.
»DISPLAY
Value Screen
internal sensor values
external sensor values
(configurable)
(additional humidity value optionally configurable)
Header (value/ symbol display)
Time, weekday, date, ECO symbol (mode dependent)
Alarm symbol (higher priority than ECO-Symbol)
Footer (symbol display)
Symbols for heating/cooling
mode, occupancy, window
contact, etc.
The symbol „Timechannel active“
is only shown when a time
channel is active.
Occu-
pancy
Window contact/
dew point
Heating/
Cooling
Time-
channel
active

Issue date: 01.05.2023 Page 5 / 8
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 www.thermokon.com email@thermokon.com
JOY_HC_Datasheet_en © 2023
»FUNCTION DESCRIPTION – BUTTONS
On the touch surface, there are adjustment options for setpoint and fan speed regulation.
While pressing these buttons, the white ring-LED of the Power-button lights up for visual feedback.
Setpoint change (setpoint range
± 3 °C, default, configurable).
Power button for Standbymode,
or Presence key*
*If the key is used as a
presence key at the same time,
the key must be pressed for at
least 3s, in all other cases a
short press is sufficient.
3 seconds without any interaction, the display returns back to main screen.
Standby mode (not compatible with Keycard-switch function)
In standby mode the display and all outputs are switched off (controller deactivated). The frost and heat protection monitoring remains active.
Navigation Parametermenu
(up, down, left, right)
Open submenu (right)
In header left to leave the submenu
Confirmation
»DIAGNOSTICS MENU
To access the diagnostics menu, select the header in the startscreen of the parameter menu, and press the ENTER key. Here you will find various
information, such as device type, software version, state of the inputs and outputs and controller state (current manipulated variable).
»CONFIGURATION
»Parametermenu
Access to Parametermenu:
Press buttons for 3 seconds simultaneously
If no entry is made for 8 minutes, the parameter menu is left automatically.

Page 6 / 8 Issue date: 01.05.2023
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 www.thermokon.com email@thermokon.com
JOY_HC_Datasheet_en © 2023
»MENU → TIME CHANNELS
In the Time Channels menu, setpoint and timer can be set. Up to 3 time channels with 4 time periods each can
be parameterized. The time channels are prioritised. Channel 3 has the highest priority. After selecting the line
of the time channel to
be edited, the next submenu is called up with the "Right" key. It is possible to set any
time period within one week in the first two lines with the "Left" (-
)/ "Right"(+) keys. In addition, the ECO mode
is available in the menu sections. In ECO mode, the
dead zone between heating and cooling is automatically
set to the ECO dead zone configured in the "General Settings" menu (default: 10 K).
»MENU → INPUTS
Up to 3 inputs are configurable for functions such as windows contact, dew point, occupancy, change-over or
external sensor option.
The overview of possible combinations can be found in the software specification of the JOY.
Sensor (NTC10K)
The value of an external sensor will be shown if connected and configured accordingly. In this case, the room thermostat
controls according to the external sensor. Alternatively, an external temperature sensor can be used at the universal input
to protect floor heating. If a configured temperature is exceeded, the heating sequence is suspended.
Change-Over DI
Which controller is active depends on the state of the Change-Over contact. (Factory default: contact open heating controller
active, contact closed cooling controller active). The terminals 4 and 5 are used as outputs for heating rsp. cooling.
Change-Over
Sensor
The Change-Over Sensor is used for switching between heating and cooling mode automatically. If the temperature is below
22 ° C, the controller is in cooling mode. If it is above 25 ° C, it is a heating mode.
If an input is configured as a change-over, the room thermostat is automatically in 2-
pipe operating mode and both outputs
(terminals 4 and 5) are used as outputs for heating rsp. cooling.
Window
contact/Energy
hold off
If a window contact is enabled via the digital input, the reference will switch to a setback set point (Heat SP/Cool SP).
Dewpoint
An active dewpoint contact locks the cooling controller.
Occupancy
If occupancy-function is active, the symbol will be displayed automatically. In state of “unoccupied” the heating set point is
reduced by 2K (default setting) rsp. the cooling set point raised by 2K.
Keycard-Switch
When the card is not inserted, the device is switched in sleep mode. Operation of the keys is locked, the display is switched
off and the controller adjusts to the nominal values of the "unoccupied"-State.
Alarm contact
An alarm symbol can be shown in the header of the display. The backlight flashes when the alarm is active. This symbol is
in the same position as the ECO symbol. The alarm symbol has a higher priority and overwrites the ECO symbol!
»MENU → TIME/DATE
Time, Date and display format can be configured in the menu settings. The room thermostat is equipped with
a real-time clock so that it automatically adjusts for daylight-
saving time. This function can be disabled in the
datetime settings.
»MENU → SENSOR SETTINGS
Offset correction for internal and external sensor value.
The temperature display can also be changed from °C to °F.

Issue date: 01.05.2023 Page 7 / 8
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 www.thermokon.com email@thermokon.com
JOY_HC_Datasheet_en © 2023
»MENU → COMMON SETTINGS
Common device settings:
Brightness
Valve protection
ECO deadband
Language
Factory setting (reset)
Brightness
Configuration of the LCD brightness/ LED ring brightness during button
operation/ usage.
Valve protection
A valve protection function actuates the heating and
cooling valves
regularly to prevent locking during non-usage times.
The function is executed fridays
at 11.00 (heating valve) and 11.15
(cooling valve).
The corresponding valve is triggered for 5 minutes, if not
activated during the last 96 hours.
ECO deadband
The dead band can be adjusted (default 10.0 K)
* further information in the software specification file
Factory setting
By selecting “Factory setting”, the room thermostat will be reset and
restore the device to factory default settings.
»CONNECTION PLAN
JOY HC AO2DO (85..260 V ~)
JOY HC 3AO (24 V ~/=)
1 GND (6-way valve)
1 Digital Input 2
2 0..10 V (6-way valve)
2 6-way valve (0..10 V)
3 Cooling (0..10 V)
4 Cooling
4 Heating (0..10 V)
5 Heating
5 GND DI2
6 Digital Input 2 (230V)
6 GND
7 L
7 24 V = (±10%) or 24 V ~ (±10%)
8 N
8 GND
9 Digital Input 1 (or NTC10K)
9 Digital Input 1 (or NTC10K)
10 GND DI 1
10 GND DI 1
11 Digital Input 3
11 Digital Input 33
12 GND DI 3
12 GND DI 3
Note: Parallel connection of the potential-loaded inputs is not permitted!
If the operating mode (change-over DI) of several devices is to be switched together by one contact, the potential-free 230V input must be used
(DI2, only possible with the 230V version). It must be ensured that the same phase is used for jointly switched devices.

Page 8 / 8 Issue date: 01.05.2023
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax:-400 www.thermokon.com email@thermokon.com
JOY_HC_Datasheet_en © 2023
»DIMENSIONS (MM)
»ACCESSORIES (OPTIONAL)
Frame for surface mounting JOY pure white Item No. 760201
Frame for surface mounting JOY black Item No. 760951
Decorative frame pure white for JOY Item No. 681452
Decorative frame black for JOY Item No. 740951
MicroSD card 2GB Item No. 500098