Thomas Research Products LBU7-M Manual

Emergency LED Battery Pack Installation,
Operation, and Service Instructions
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following.
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. Do not join converter connection until installation is complete and AC power is supplied to the emergency
driver.
2. This product is for use with an emergency LED lighting load and supplies 7 W of constant output power to
LED lamps rated from 15-56 Vdc. Operates emergency LED load in the emergency mode for a
minimum of 90 minutes.
3. Make sure all connections are in accordance with the NEC and any local regulations.
4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and converter
connector from the emergency driver before servicing.
5. This emergency driver is suitable for factory or field installation.
6. Do not use outdoors. This product is suitable for use in damp locations where the ambient temperature is
7. An unswitched AC power source is required (120-277 VAC, 50/60 Hz).
8. Do not install near gas or electric heaters.
9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable.
Contact Thomas Research Products for information on service.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
13. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel
SAVE THESE INSTRUCTIONS
WARNING - This product contains chemicals known to the State of California to cause cancer,
birth defects, and/or other reproductive harm. Thoroughly wash hands after installing, cleaning, or
otherwise touching this product.
CAUTION: DISCONNECT POWER DURING INSTALLATION AND BEFORE SERVICING.
READ ALL INSTRUCTIONS COMPLETELY BEFORE STARTING INSTALLATION.
SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
ALBALBEC-16121200912/20/161
4 3
D
C
B
A
4 3
2 1
D
C
B
A
12
REV DATE RECORD DESN CHCK
SHT 1
1 SHTS
--- ---
93079821
93079821
1
ILL-PLD10M
ALB 12/20/16
ALB 12/20/16
---
ALB 12/20/16
NTS
REV.DRAWING NO.SIZESCALE
PART NO.FINISH:MATERIAL:
This document containsconfidential and proprietary information ofDual
Lite. Receipt or possession ofthis document does not convey any rights to
reproduce or disclose itscontents, or to make, use , or sell anything it may
disclose. Reproduction, disclosure, or use of the document or its contents,
without the specific written authorization of Dual Lite, may violate the
intellectual propertyrights of Dual Lite.
DIMENSIONS IN INCHES
DIMENSIONS IN [ ] IN MM
CONFORMS TO ASME Y14.5M
DO NOT SCALE PRINT
DRAWN BY:
THIRD ANGLE PROJECTION
CHECKED BY:
ENGINEERING:
CATALOG NO.
CRITICAL DIMENSIONS
C
UNSPECIFIED TOLERANCES: INCHES
X.XX=
u
0.12
FRACTIONS=
u
1/32 ANGULAR TOLERANCE=
u
1
v
THIS ILL IS USED ON INSTRUCTION SHEET 93078192
LBU7-M / LBU7-M2
INSTALLER:
P/N:93057557 LBU7-M2 CLASS 2 OUTPUT
0°C minimum, +55°C maximum. Product is not suitable for heated air outlets and wet
or hazardous locations.
E491125
P/N:93057556 LBU7-M

CAUTION: SUPPLY AC POWER TO THE EMERGENCY DRIVER BEFORE JOINING EITHER
CONVERTER CONNECTOR RED WIRES
INSTALLATION
1/2" DIA.
THRU HOLE
SUPPLIED NUT
SMALL
BUSHING
SUPPLIED TEST SWITCH/
INDICATOR LIGHT
TY-WRAP
SW INDICATOR
LARGE
BUSHING
PLASTIC
TUBE
SW INDICATOR
PLASTIC
TUBE
LARGE
BUSHING
EM DRIVER
SMALL
BUSHING
SW LEADS
TIE WRAP
7/8" DIA THRU
HOLE
BALLAST
CHANNEL
COVER
FIXTURE
DIFFUSER
LENS
93071446
ILLUSTRATION 2
ILLUSTRATION 1
93071446
93071446
ILLUSTRATION 3
TY-WRAP
UL SWITCH
COVER
UL SWITCH
COVER
1/2" DIA.
THRU HOLE
SUPPLIED NUT
SMALL
BUSHING
SUPPLIED TEST SWITCH/
INDICATOR LIGHT
TY-WRAP
SW INDICATOR
LARGE
BUSHING
PLASTIC
TUBE
SW INDICATOR
PLASTIC
TUBE
LARGE
BUSHING
EM DRIVER
SMALL
BUSHING
SW LEADS
TIE WRAP
7/8" DIA THRU
HOLE
BALLAST
CHANNEL
COVER
FIXTURE
DIFFUSER
LENS
93071446
ILLUSTRATION 2
ILLUSTRATION 1
93071446
93071446
ILLUSTRATION 3
TY-WRAP
UL SWITCH
COVER
UL SWITCH
COVER
Installation of this Emergency LED Driver will vary based on the luminaire type, however, generally follow these steps.
Step 1. Disconnect AC power to the LED lighting fixture. Remove lens and ballast channel cover from LED fixture if applicable. (see illustrations 2 & 4)
Step 2. Using the 2 supplied screws, mount the LED emergency driver. The lighting fixture instructions might provide suggestions on the driver mounting location
Step 3. Test switch/indicator light can be mounted directly to a xture surface thru a 1/2 inch diameter hole. Once nut is tightened, slip UL switch cover over wires,
pushing cover against xture surface completely covering switch, then afx ty-wrap over wires against cover to secure. Switch should be visible once xture is installed.
(see illustration 1 & 4)
Step 4. Test switch/indicator light can also be installed onto a driver channel cover through a 7/8 inch diameter hole (see illustrations 2 & 3.) Trim plastic tube to desired length,
afx UL switch cover as shown and place into tube. Afx both the small bushing and the large bushing onto the plastic tube as shown. Connect tie wrap onto wires,
tighten and insert into channel. Switch should be visible once xture is installed.
This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage driven LED
replacements for fluorescent lamps and others. There are 5 checks to determine if your luminaire is eligible for use with this LED
battery pack.
1. Ensure the LED load's rated power is greater than or equal to the power output of this emergency LED driver (7W). This is to ensure that this emergency product will not
produce more power than the LED load can handle, thus ensuring that the LED load will not be damaged when the system is in the emergency mode.
2. Verify that the forward voltage of the luminaire's LED array is within the limits of this emergency LED driver. The forward voltage of the LED array is commonly designated as
Vf and should be found on the luminaire marking's, in the luminaire specications, or imprinted directly on the LED arrays. If multiple LED arrays are to be driven, verify
that the total forward voltage is within the limits of this product. Using a voltage meter, it may be possible to directly measure the voltage across the LED array when
operating from the AC driver.
3. Ensure the output current of the LED driver does not exceed 1.6 Amps. This is the current into the blue wire.
4. Ensure the LED fixture’s rated efficacy is equal to or greater than 65 lm / watt. This is to ensure that the LED fixture can be mounted at or below the maximum rated
mounting height of 25.8 ft.
5. Ensure there will be sufficient light output in the end application. Estimate the emergency egress lighting illumination levels by doing the following:
a. Find the efficacy of the LED lighting fixture. Luminaire efficacy information can be found at the Design Lights Consortium website (http://www. designlights.org),
Energy Star - Certified Products - product finder website (http://www.energystar.gov/productfinder/) or given by the luminaire manufacturer on product catalog
specification sheets. The LED fixture efficacy will be given in lumens per watt (lm/w).
b. Lumens can be calculated by multiplying the output power of the emergency LED driver (7W) by the efficacy of the LED load.
In many cases the actual lumen output in emergency mode will be greater than this calculation gives, however it will provide a good estimate for beginning the lighting
design of the system.
Lumens In Emergency Mode = Lumens Per Watt of Fixture * Output Power of Chosen Product
(LUMENS) = (LM/W) * W
c. Using the results of this calculation and industry standard lighting design tools, calculate the anticipated illumination levels in the path of egress.
NOTE: This product has been designed to reliably interface with a wide selection of LED loads and is
electrically compatible with every simple LED array that meets criteria 1-5 above. However, compatibility
cannot be guaranteed with all current and future LED systems. Compatibility testing of the end-use system
is suggested. Please contact the factory with any questions.
NOTE: After installation, it will be necessary to measure the egress lighting illumination levels to ensure it
complies with national, state, and local code requirements.

Mounting Height: This product meets or exceeds the NFPA minimum light
requirements with all loads, down to the smallest rated lamp load, at heights up to
25.8ft (7.8m). Many factors influence emergency illumination levels, such as the lamp
load selected, luminaire design, and environmental factors, therefore end use
verification is necessary. For installations where the attached luminaire is mounted at
heights greater then 25.8ft (7.8m), the level of illumination must be measured in the
end application to ensure the requirements of NFPA 101 and local codes are
satisfied.
WIRING
Step 5. Select correct wiring diagram to connect the emergency driver to the LED load, AC LED driver and Switch. Make sure all connections are in accordance with the National
Electrical Code and any local regulations.
Step 6. Install the labels “CAUTION” & “STATUS” in a visible location (see illustration 4).
Step 7. After installation is complete, supply AC power to the emergency ballast and join the invertor connector.
Step 8. At this point, power should be connected to both the AC driver and the emergency driver, and the charging indicator light should illuminate indicating the battery is
charging.
Step 9. A short-term discharge test may be conducted after the emergency ballast has been charged for one hour.
Step 10. Charge for 24 hours before conducting a long-term discharge test. Refer to “Operation” section below
Note: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required.
The emergency ballast must be fed from the same branch circuit as the AC ballast.
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
1/2" DIA.
THRU HOLE
SUPPLIED NUT
SUPPLIED TEST SWITCH/
INDICATOR LIGHT
SW INDICATOR
PLASTIC
TUBE
LARGE
BUSHING
EM DRIVER
SMALL
BUSHING
SW LEADS
TIE WRAP
7/8" DIA THRU
HOLE
BALLAST
CHANNEL
COVER
FIXTURE
DIFFUSER
LENS
93071446
ILLUSTRATION 2
ILLUSTRATION 1
93071446
TY-WRAP
UL SWITCH
COVER
ALBALBEC-1601270034/28/161
4 3
D
C
B
A
4 3
2 1
D
C
B
A
12
REV DATE RECORD DESN CHCK
SHT 1
1 SHTS
------
93071433
93071433
1
ILL-DIA WIRING EV10
ALB 04/28/16
ALB 4/28/16
---
ALB 4/28/16
NTS
REV.DRAWING NO.SIZESCALE
PART NO.FINISH:MATERIAL:
This document contains confidential and proprietary information of Dual
Lite. Receipt or possession of this document does not convey any rights to
reproduce or disclose its contents, or to make, use , or sell anything it may
disclose. Reproduction, disclosure, or use of the document or its contents,
without the specific written authorization of Dual Lite, may violate the
intellectual property rights of Dual Lite.
DIMENSIONS IN INCHES
DIMENSIONS IN [ ] IN MM
CONFORMS TO ASME Y14.5M
DO NOT SCALE PRINT
DRAWN BY:
THIRD ANGLE PROJECTION
CHECKED BY:
ENGINEERING:
CATALOG NO.
CRITICAL DIMENSIONS
C
UNSPECIFIED TOLERANCES: INCHES
X.XX=
0.12
FRACTIONS=
1/32 ANGULAR TOLERANCE=
1
RED
RED
WHT/RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
AC DRIVER (-)
AC DRIVER (+)
BLACK
WHITE
LBU7-M/M2
EM LED
DRIVER
LED LOAD
AC DRIVER
HOT
COMMON
VIOLET (+)
BROWN (-)
WALL SW
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
RED
RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
PLD10M
EM LED
DRIVER
LED LOAD
HOT
COMMON
VIOLET (+)
BROWN (-)
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
CAP
RED
RED
WHT/RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
AC DRIVER (-)
AC DRIVER (+)
SW 1
WHITE
PLD10M
EM LED
DRIVER
LED LOAD
AC DRIVER
HOT
COMMON
VIOLET (+)
BROWN (-)
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
AC DRIVER (-)
AC DRIVER (+)
LINE 1
LINE 2
HOT
SW 2
EMERGENCY BACK-UP ONLY
EMERGENCY BACK-UP & AC DRIVER
EMERGENCY BACK-UP, AC DRIVER
AND DIMMING
THIS ILL IS ON INSTRUCTION SHEET93070924.
ALBALBEC-1601270034/28/161
4 3
D
C
B
A
4 3
2 1
D
C
B
A
12
REV DATE RECORD DESN CHCK
SHT 1
1 SHTS
------
93071433
93071433
1
ILL-DIA WIRING EV10
ALB 04/28/16
ALB 4/28/16
---
ALB 4/28/16
NTS
REV.DRAWING NO.SIZESCALE
PART NO.FINISH:MATERIAL:
This document contains confidential and proprietary information of Dual
Lite. Receipt or possession of this document does not convey any rights to
reproduce or disclose its contents, or to make, use , or sell anything it may
disclose. Reproduction, disclosure, or use of the document or its contents,
without the specific written authorization of Dual Lite, may violate the
intellectual property rights of Dual Lite.
DIMENSIONS IN INCHES
DIMENSIONS IN [ ] IN MM
CONFORMS TO ASME Y14.5M
DO NOT SCALE PRINT
DRAWN BY:
THIRD ANGLE PROJECTION
CHECKED BY:
ENGINEERING:
CATALOG NO.
CRITICAL DIMENSIONS
C
UNSPECIFIED TOLERANCES: INCHES
X.XX=
0.12
FRACTIONS=
1/32 ANGULAR TOLERANCE=
1
RED
RED
WHT/RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
AC DRIVER (-)
AC DRIVER (+)
BLACK
WHITE
PLD10M
EM LED
DRIVER
LED LOAD
AC DRIVER
HOT
COMMON
VIOLET (+)
BROWN (-)
WALL SW
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
RED
RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
PLD10M
EM LED
DRIVER
LED LOAD
HOT
COMMON
VIOLET (+)
BROWN (-)
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
CAP
RED
RED
WHT/RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
AC DRIVER (-)
AC DRIVER (+)
SW 1
WHITE
LBU7-M/M2
EM LED
DRIVER
LED LOAD
AC DRIVER
HOT
COMMON
VIOLET (+)
BROWN (-)
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
AC DRIVER (-)
AC DRIVER (+)
LINE 1
LINE 2
HOT
SW 2
EMERGENCY BACK-UP ONLY
EMERGENCY BACK-UP & AC DRIVER
EMERGENCY BACK-UP, AC DRIVER
AND STEP DIMMING
THIS ILL IS ON INSTRUCTION SHEET93070924.
MOUNT LBU7-M
UNIT ON TOP OF
LED FIXTURE
SWITCH
INDICATOR
"CAUTION"
LABEL
"STATUS"
LABEL
LED MTG PLATE
(LENS NOT SHOWN)
TYPICAL LED
LIGHTING
FIXTURE
ILLUSTRATION 4
SMALL
BUSHING
TY-WRAP
SW INDICATOR
LARGE
BUSHING
PLASTIC
TUBE
93071446
ILLUSTRATION 3
UL SWITCH
COVER
PURPLE
0-10V Dimming Leads (optional)
GRAY

OPERATION
MAINTENANCE
During normal operation AC power is applied, the charging red indicator light is illuminated, indicating that the battery is being
charged. When power fails, the emergency LED driver automatically switches to emergency power (internal battery), operating
the LED load for a minimum of 90 minutes. When AC power is restored, the emergency driver returns to the charging mode (red
LED on). The unit also has a visual indication of unit malfunction when their is a “Charger Fault” with the red LED blinking three
times with a 3 second pause between the 3 blink group.
All steel, aluminum and thermoplastic parts are recyclable.
NOTICE: Emergency units contain rechargeable batteries
which must be recycled or disposed of properly.
Ni-Cd
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to
ensure that it is working.
The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. The LED load should
operate at reduced illumination.
3. Conduct a 90-minute discharge test once a year. The LED load should operate at reduced illumination for at least
90 minutes.
*REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL*
Recycling Information
NOTE: For short term testing of the emergency function, the battery must be charged for at least one hour. The
emergency driver must be charged for at least 24 hours before conducting a long term test.
ALBALBEC-1601270034/28/161
4 3
D
C
B
A
4 3
2 1
D
C
B
A
12
REV DATE RECORD DESN CHCK
SHT 1
1 SHTS
------
93071433
93071433
1
ILL-DIA WIRING EV10
ALB 04/28/16
ALB 4/28/16
---
ALB 4/28/16
NTS
REV.DRAWING NO.SIZESCALE
PART NO.FINISH:MATERIAL:
This document contains confidential and proprietary information of Dual
Lite. Receipt or possession of this document does not convey any rights to
reproduce or disclose its contents, or to make, use , or sell anything it may
disclose. Reproduction, disclosure, or use of the document or its contents,
without the specific written authorization of Dual Lite, may violate the
intellectual property rights of Dual Lite.
DIMENSIONS IN INCHES
DIMENSIONS IN [ ] IN MM
CONFORMS TO ASME Y14.5M
DO NOT SCALE PRINT
DRAWN BY:
THIRD ANGLE PROJECTION
CHECKED BY:
ENGINEERING:
CATALOG NO.
CRITICAL DIMENSIONS
C
UNSPECIFIED TOLERANCES: INCHES
X.XX=
0.12
FRACTIONS=
1/32 ANGULAR TOLERANCE=
1
RED
RED
WHT/RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
AC DRIVER (-)
AC DRIVER (+)
BLACK
WHITE
PLD10M
EM LED
DRIVER
LED LOAD
AC DRIVER
HOT
COMMON
VIOLET (+)
BROWN (-)
WALL SW
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
RED
RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
LBU7-M/M2
EM LED
DRIVER
LED LOAD
HOT
COMMON
VIOLET (+)
BROWN (-)
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
CAP
RED
RED
WHT/RED
BLACK
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
AC DRIVER (-)
AC DRIVER (+)
SW 1
WHITE
PLD10M
EM LED
DRIVER
LED LOAD
AC DRIVER
HOT
COMMON
VIOLET (+)
BROWN (-)
CONVERTER BATTERY CONN.
TEST SW/LED INDICATOR
AC DRIVER (-)
AC DRIVER (+)
LINE 1
LINE 2
HOT
SW 2
EMERGENCY BACK-UP ONLY
EMERGENCY BACK-UP & AC DRIVEREMERGENCY BACK-UP, AC DRIVER
AND DIMMING
THIS ILL IS ON INSTRUCTION SHEET93070924.
ALBALBEC-16121200912/20/161
4 3
D
C
B
A
4 3
2 1
D
C
B
A
12
REV DATE RECORD DESN CHCK
SHT 1
1 SHTS
--- ---
93079827
93079827
1
ILL-GROUND WIRE PLD10M
ALB 12/20/16
ALB 12/20/16
---
ALB 12/20/16
NTS
REV.DRAWING NO.SIZESCALE
PART NO.FINISH:MATERIAL:
This document contains confidential and proprietary information of Dual
Lite. Receipt or possession of this document does not convey any rights to
reproduce or disclose its contents, or to make, use , or sell anything it may
disclose. Reproduction, disclosure, or use of the document or its contents,
without the specific written authorization of Dual Lite, may violate the
intellectual property rights of Dual Lite.
DIMENSIONS IN INCHES
DIMENSIONS IN [ ] IN MM
CONFORMS TO ASME Y14.5M
DO NOT SCALE PRINT
DRAWN BY:
THIRD ANGLE PROJECTION
CHECKED BY:
ENGINEERING:
CATALOG NO.
CRITICAL DIMENSIONS
C
UNSPECIFIED TOLERANCES: INCHES
X.XX=
u
0.12
FRACTIONS=
u
1/32 ANGULAR TOLERANCE=
u
1
v
THIS ILL IS USED ON INSTRUCTION SHEET 93078192
GROUND WIRE
SCREW SEM
NUT KEP
GROUND WIRE INSTALLATION
Thomas Research Products • 1225 Bowes Rd • Elgin, IL 60123 • T 847-515-3057 • F 847-515-3047 • www.trpssl.com
© 2018 Thomas Research Products REV D 2/8/18
N14687
This manual suits for next models
1
Popular Security Sensor manuals by other brands

Clas Ohlson
Clas Ohlson SH98RF quick start guide

Sontay
Sontay OC-C-M quick start guide

Powerfix Profi
Powerfix Profi IAN 40111 Operation and safety notes

STEINEL
STEINEL IS 1 quick start guide

Theben
Theben thePiccola P360-100 DE user manual

Buhler
Buhler BCM-W Assembly, installation and operation instructions