IS---0766
IS---650/675 ETP (1)
October 2007
Page 1 of 3
Installation Instructions
650/675 ETP (1)
Elbow Tap Plug
CONTENTS: Tap Plug, Lubricant (DO NOT SUBSTITUTE), Stud (if applicable), Installation Instructions.
The 650/675 ETP has a voltage rating of 15kV (8.3kV line---to---ground and 14.4kV line---to---line) and is designed to provide a
200 ampere loadbreak tap at system voltage as indicated on the ETP. A yellow band provides indication of full seating. This
product is identified by a white band.
WARNING: THE AVAILABLE FAULT CURRENT MUST BE LIMITED TO 10,000 AMPERES WHEN USING
THIS PRODUCT.
WARNING: THE FOLLOWING RATINGS APPLY TO THIS PRODUCT:
600 Ampere Deadbreak Interface: 650ETP(1)---600 ampere load current and 25,000 amperes short
circuit current for 10 cycles.
675ETP(1)---900 ampere load current and 25,000 amperes short
circuit current for 10 cycles.
200 Ampere Loadbreak Interface: 200 amperes load current and 10,000 amperes fault---close current.
For higher short circuit current: 1) this interface must only be operated
de---energized; and 2) elbows used for taps or grounding must be
adequately secured such as with a bail.
DANGER
All apparatus must be de--energized during installation
or removal of part(s). For loadbreak products follow
operating instructions. All deadbreak connectors must
be de--energized before operating. All 200A deadbreak
connectors must be mechanically secured with bails
when connected.
All apparatus must be installed and operated in
accordance with individual user, local, and national
work rules. These instructions do not attempt to
provide for every possible contingency.
Do not touch or move energized products.
Excess distortion of the assembled product may result
in its failure.
Inspect parts for damage, rating and compatibility with
mating parts.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
IMPORTANT
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
STEP 1
Prepare cable using spade contact and install elbow as de-
scribed in the (K)650LR or 750LR installation instructions.
Before making first crimp on spade contact, align it on
the cable so that the spade lies flat on the apparatus
bushing contact.
Apparatus
Bushing
Spade
Contact
CORRECT POSITION WRONG POSITION
Cable
IS---0766
IS---650/675 ETP (1)
October 2007
Printed in U.S.A.