DESCRIPTION
Model 26 True RMS Voltage Monitor has a display
that shows the voltage with an accuracy of +/- 0.5%.
The display is updated every second and re-initialized
every 30 seconds.
This unit has a user selectable relay option for High-Low
or DPDT. It can also be user-selected to energize on
fault or de-energize on fault. The user can select
automatic or manual restart on the Model 26. The SG
version of the Model 26 has silver with gold flash
contacts for low current applications
Model 26 True RMS Voltage Monitor can be either
calibrated using a True RMS Voltmeter or can be
restored to factory defaults in the field.
User selectable relay operation
options
Low or High Trip with independent
delays or disabled
User programmable
Can be restored to factory settings
or calibrated using a True RMS
Voltmeter in the field
Model 26SG has silver with gold
flash contacts for low current.
MODEL 26
True RMS Voltage
Monitor
TIME MARK is a division of
Telephone: Main (918) 438-1220
Sales (800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet: http://www.time-mark.com
Page 1 of 4 11/2012
© 2012 TIME MARK CORPORATION
11440 E as t P i n e S t r ee t
Tu l sa, Ok l aho m a 74 1 1 6
SPECIFICATIONS
Model 26 and 26SG
Start-up Delay 5 secs. Min. or Automatic reset delay setting
(to allow for solid lock)
Output Contacts SPDT x 2 10 Amps @ 240VAC
Repeat Accuracy ± 0.5 % (fixed conditions)
Reset Type Manual or Automatic
Expected Relay Life Mech: 10 million operations
Elec: 100,000 min. at rated load
Operating Temp -20°F to +130°F
Humidity Tolerance 0-97% w/o condensation
Enclosure Material Lexan 920
Polycarbonate
UL 94 V-0 1.5 mm
Mounting DIN Rail 35mm
Weight 8.5 oz.
UL SPECIFICATIONS
Model 26 and 26SG
Input
Voltage (VAC) 80-550 Volts
Amps 1mA
Frequency 50/60Hz (400Hz optional with jumper)
DC Power 24 Volts, 2 watts
Output 240V AC, 10A, Resistive
120V AC, 4A, General Use
240V AC, 2A, General Use
C300, Pilot Duty
INSTALLATION AND SETUP
Controls:
Rotary encoder with switch. Pressing the
encoder switch will display the set points.
Pressing the encoder switch for more than 5
seconds will enter the setup mode. Pressing
switch displays the next menu item. Holding down
the switch during setup mode will sequence
through menus with 1 second intervals. Rotating
the knob clockwise increases the value and
counter-clockwise will decrease value.
For non-value options, rotating the knob either
way will change the options on the display.
Setup Options:
(Press encoder for at least 5 seconds to enter
setup)
High Voltage: (Factory—Enabled, Set point =
550V, Delay = 5S)
Enable/Disable:
(*If disabled set point and delay are skipped)
Set Point Range:
Low setpoint + 1% to 550V in 0.5V steps
High Trip Delay:
0 to 20.0 seconds in 0.1Sec steps
Low Voltage: (Factory—Enabled, Set point =
80V, Delay = 5S)
Enable/Disable:
(*If disabled set point and delay are skipped)
Set Point Range:
80 to High Setpoint -1% in 0.5V steps
Low Trip Delay:
0 to 20.0 seconds in 0.1Sec steps
TIME MARK is a division of
Telephone: Main (918) 438-1220
Sales (800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet: http://www.time-mark.com
Page 2 of 4 11/2012
© 2012 TIME MARK CORPORATION
11440 E as t P i n e S t r ee t
Tu l sa, Ok l aho m a 74 1 1 6
MODEL 26 True RMS Voltage Monitor
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 26.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
TYPICAL APPLICATION—MONITOR AND CONTROL
TYPICAL APPLICATION—MONITOR AND ALARMS
A/C VOLTAGE
N L
LOW HIGH
NO C NC | NO C NC
24VDC MANUAL
RESET
INSTALLATION AND SETUP (Continued)
Relay Operation: (Factory = HI-LO)
Voltage High/Low Option:
Separate High/Low Relays
DPDT
Other faults DPDT
Relay Operation on Fault: (Factory - De-energize on
fault)
De-energize on fault
Energize on fault
Hysteresis set
Restart: (Factory - Automatic)
Automatic or Manual (in Manual rotating the knob or
closing an external switch will reset the unit)
Automatic Restart Delay Range: (Factory - 5S)
0 to 300.0 Seconds in 0.1Sec steps
Exit from Setup Options:
Repeat Setup:
Press encoder to begin setup from beginning. ( H i g h
Enable)
Exit & No Save:
Press encoder to exit setup. Any changes have been
discarded.
Exit & Save:
Press encoder to exit setup and save changes. U n i t
will begin using new settings.
TIME MARK is a division of
Telephone: Main (918) 438-1220
Sales (800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet: http://www.time-mark.com
Page 3 of 4 11/2012
© 2012 TIME MARK CORPORATION
11440 E as t P i n e S t r ee t
Tu l sa, Ok l aho m a 74 1 1 6
MODEL 26 True RMS Voltage Monitor
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 26.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
INSTALLATION AND SETUP (Continued)
Start Up Delay:
5 Seconds Minimum or Automatic Restart Delay s e t t i n g
(to allow for solid lock).
OPTIONAL 400HZ FREQUENCY SETUP
To change the Model 26 from the factory default 50/60Hz
frequency to 400Hz, simply remove the blank cover plate
(without holes) and move the jumper from 50/60Hz to
400Hz . Replace the cover plate when completed.
UNIT FIELD RESTORE FACTORY SETTINGS
AND RECALIBRATION
1) From a powered down condition. Apply the AC voltage
first.
2) Press and hold the Encoder switch while applying the
DC power to the unit. As soon as the splash screen
appears release the button. The display will show “No
Rest Fac”. Rotate encoder to change option to “Yes” to
restore factory settings. Press the Encoder switch.
3) The display will show the voltage. Place a meter
between the AC input terminals. Rotate encoder to
change the reading on the display to be what is on the
meter. When readings within +/- 0.5V press the
Encoder switch.
4) The unit will return to normal operation.
TIME MARK is a division of
Telephone: Main (918) 438-1220
Sales (800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet: http://www.time-mark.com
Page 4 of 4 11/2012
© 2012 TIME MARK CORPORATION
11440 E as t P i n e S t r ee t
Tu l sa, Ok l aho m a 74 1 1 6
MODEL 26 True RMS Voltage Monitor
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 26.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
WARRANTY
This product is warranted to be free from defects in
materials and workmanship for one year. Should this
device fail to operate, we will repair it for one year from the
date of manufacture. For complete warranty details, see
the Terms and Conditions of Sales page in the front
section of the Time Mark catalog or contact Time Mark at
1-800-862-2875.
DIMENSIONS

This manual suits for next models

2

Other TIME MARK Measuring Instrument manuals

TIME MARK 2629 User manual

TIME MARK

TIME MARK 2629 User manual

TIME MARK 25 User manual

TIME MARK

TIME MARK 25 User manual

Popular Measuring Instrument manuals by other brands

PASCO PS-3237 quick start guide

PASCO

PASCO PS-3237 quick start guide

SANKO SWT-7000 III instruction manual

SANKO

SANKO SWT-7000 III instruction manual

wtw Cond 7310 operating manual

wtw

wtw Cond 7310 operating manual

Spectrum Technologies LIGHTSCOUT 3415A product manual

Spectrum Technologies

Spectrum Technologies LIGHTSCOUT 3415A product manual

IMC SPARTAN Instruction book

IMC

IMC SPARTAN Instruction book

forlong PM834 user manual

forlong

forlong PM834 user manual

Toro Precision Soil Sensor quick start guide

Toro

Toro Precision Soil Sensor quick start guide

Nimrof AT550 Technical user guide

Nimrof

Nimrof AT550 Technical user guide

KROHNE OPTISWIRL 4200 Supplementary instructions

KROHNE

KROHNE OPTISWIRL 4200 Supplementary instructions

THORLABS PM160T user manual

THORLABS

THORLABS PM160T user manual

Thermo Scientific TSQ 8000 Evo user guide

Thermo Scientific

Thermo Scientific TSQ 8000 Evo user guide

Fluidwell E115-P user manual

Fluidwell

Fluidwell E115-P user manual

Beckhoff KM3701 Documentation

Beckhoff

Beckhoff KM3701 Documentation

Swann AMI Turbitrace Operator's manual

Swann

Swann AMI Turbitrace Operator's manual

Armada Pro30 operating manual

Armada

Armada Pro30 operating manual

Bante Instruments TB200 user manual

Bante Instruments

Bante Instruments TB200 user manual

Trace2O METALYSER DELUXE HM2000 instruction manual

Trace2O

Trace2O METALYSER DELUXE HM2000 instruction manual

Bierer HP72-DCXL operating instructions

Bierer

Bierer HP72-DCXL operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.