
Web: www.tinker-rasor.com E-mail: Info@tinker-rasor.com
–1 –
CORROSION MITIGATION INSTRUMENTATION
P. O. BOX 1667 SAN BERNARDINO,CA 92402 TEL:(909) 890-0700 FAX:(909) 890-0736
PRODUCT INSTRUCTIONS
The dry film thickness should not exceed 20 mils when electrical holiday testing is done with the
low voltage Model M/1 Holiday Detector. Film thickness should be determined with a non-
destructive dry film thickness gauge to make sure limits are not exceeded.
Special Note: Ordinary tap water will generally suffice to dampen the sponge electrode,
provided the protective coating thickness does not exceed 10 mils. The factory
recommended practice is to use a wetting agent at all times, regardless of coating
thickness to 20 mils.
Check battery voltage. This can be done by shorting the terminals of the holiday detector. If a
steady, level audible signal is heard, the battery voltage is OK. If the audible signal starts to
attenuate while testing, REPLACE battery. Note: A battery output voltage drop of over 10% also
indicates weak battery.
HOLIDAY DETECTOR ASSEMBLY
Assemble the Holiday Detector by connecting the wire leading from the handle to one terminal of
the detector and the plain end of the ground wire to the other detector terminal. Connect the
saturated (see below) electrode by means of the metal clamp on the end of wand handle.
ELECTRICAL TESTING PROCEDURES
The sponge electrode should contain sufficient amount of wetting solution to assure moisture
penetration from the sponge electrode into any defect that may be present in the protective
coating. Excess wetting solution should be squeezed out of the sponge electrode.
Attach ground wire directly to the bare structure (substrate) under test. On coated steel
structures the ground wire must be directly connected to the bare metal.
On coated concrete structures the ground wire should be connected directly to the reinforcing
steel embedded in the concrete. If rebar is not present, a ground connection to the concrete can
be made by placing the bare end of the ground wire against the bare concrete surface and
anchor it down with a burlap bag filled with damp sand.
The ground wire can be checked quickly for proper connection by contacting the wetted sponge
electrode to the bare structure and observing an audible signal, indicating correct electrical
continuity of the holiday detector circuit.
The rate of inspection speed of the sponge electrode over the protective coated surface should
not exceed sixty (60) linear feet per minute. Using a double stroke of the sponge electrode over
each area assures better inspection coverage with less likelihood of any missed areas.
CALIBRATION
Factory calibration on Model M/1 Holiday Detectors are set at 700 micro-amperes (+/- 10) of
current flow to complete the circuit for the audible signal to indicate a coating holiday on metal
substrates. For coatings on concrete substrates, the Model M/1 must be adjusted for current flow
of 500 micro-amperes (+/- 10%).