Setup by means of «tLoader PRIME»application
1. Disconnect FACP main and alternative power (if connected).
2. Connect FACP to PC with USB-miniUSB cable (fig. 1, pos. 1).
3. Run the «tLoader PRIME»application and setup main settings:
3.1 Zone types:
-automatic detectors:
•without verification
•verification Type A
•verification Type B
•verification Type C
-manual call points;
-input.
3.2 Outputs:
-assign required zones to sounders
-assign required zones to relays
3.3 Device assigning: Using M-Z(f) –if you need to increase numbers of zones, using M-Z(f)
module.
3.4 Users –configuring user options:
-add user;
-remove user;
-name, access code, authorities.
3.5 Scripts –creating the scripts for outputs operations
3.6 General settings:
-Delays for outputs activation
-Reset time
-Restart sounders with new fire
-Grounding control
-Day/Night mode (alert mode depending on the time of the day)
4. Press the button “Loading settings in device”.
5. Disconnect USB-miniUSB cable from FACP.
6. Connect FACP main and alternative power.
7. Set up actual time and date:
-press the button on FACP panel (fig.1, pos. 3);
-enter access code (default - 1111);
-by means of arrows and select menu item «10: Time and date»;
-enter time and day in the following format “HH:MM DD/MM/YY”, (where HH are hours, MM
are minutes, DD are days, MM are months, YY are years);
-press buttons to confirm changes and to exit from menu.