Titus STE-8001 User manual

STE-8001 and STE-8201 sensors
Installation Guide

STE-8001 and STE-8201 sensors
2
Contents
Section 1
Introduction to STE-8000 sensors
Specifications ........................................................................................................................6
Safety considerations ..........................................................................................................8
Section 2
Installing STE-8000 sensors
Planning for motion sensing ..............................................................................................9
Rough-in preparation ........................................................................................................ 10
Installing the sensors .........................................................................................................10
Maintenance ....................................................................................................................... 11
Section 3
User functions
Operating the STE-8000 .................................................................................................... 13
Changing setpoints ............................................................................................................ 14
Section 4
Commissioning functions
Enter the commissioning mode ....................................................................................... 16
Setting up network communications .............................................................................. 17
Balancing airflow ............................................................................................................... 18
Setting commissioning setpoints ..................................................................................... 21
Commissioning airflow setpoints ................................................................................... 24
Box options ......................................................................................................................... 27
Advanced options .............................................................................................................. 31

3
SECTION 1
Introduction to STE-8000 sensors
Models STE-8001 and STE-8201 are wall-mounted, temperature sensor for use
with Titus BAC-8000 series VAV controllers. Key features include the following:
Integrated operator interface ready to use with BAC-8000 series VAV
controllers
Large LCD display
Simple three-button interface
Continuously displays temperature and time
Separate password protection for user and commissioning functions
Use as a service tool to set up BAC-8000 series VAV controllers
Optional motion sensor to detect space occupancy
Note
The STE-8000 series sensors will display time if the controller to which they are
attached have been synchronized with system time within the previous 24
hours.
Illustration 1-1 STE-8001 and STE-8201
STE-8001 STE-8201
This section provides a description of the Titus STE-8001 and STE-8201 wall
sensors. It also introdeces safety information. Review this material before
installing or operating the sensors.

Introduction to STE-8000 sensors
Specifications
4
Specifications
Display Multifunctional LCD
1.88 x 1.25 in. (48 x 32 mm)
Compatibility BAC-8000 series VAV controllers
Controller Connection
Connector type Eight-wire RJ-45 modular jack
Cable type and length Standard Ethernet cable up to 75 feet (22.9 meters)
PowerSupplied by connected controller
Mounting Surface mount directly to any flat surface or to a
2 x 4 inch or 4 x 4 inch handy-box. Mounting on a
4 x 4 inch box requires a mounting backplate.
Weight 2.8 ounces (80 grams)
Material Flame retardant plastic
Accessories
Mounting backplate HMO-1161W
GasketHPO-116
Replacement Allen screwsHPO-0044 (package of 10)
Environmental Limits
Operating Temperature 34° to 125° F (1.1 to 51.6° C)
Shipping –40° to 140° F (–40°C to 60° C)
Humidity 0 to 95% relative humidity
non-condensing

STE-8001 and STE-8201 sensorsIntroduction to STE-8000 sensors
Specifications
5
Motion sensor range Model STE-8201 only
Detector type Passive infrared
Range 33 feet (10 meters). See diagrams
Dimensions
ABCDEF
3.25 in. 5.16 in. 2.58 in. 3.25 in. 0.87 in. 1.07 in.
83 mm 116 mm 66 mm 83 mm 22 mm 27 mm
Top view Side view
C
B
A
D
E
F

Introduction to STE-8000 sensors
Safety considerations
6
Models
Temperature sensor only STE-8001
Temperature and motion STE-8201
Safety
considerations
Danger
Danger represents the most severe hazard alert. Bodily harm or death will
occur if danger guidelines are not followed.
Warning
Warning represents hazards that could result in severe injury or death.
Caution
Caution indicates potential personal injury or equipment or property damage
if instructions are not followed.
Note
Notes provide additional information that is important.
Detail
Provides programing tips and shortcuts that may save time.
Titus assumes the responsibility for providing you a safe product and safety
guidelines during its use. Safety means protection to all individuals who
install, operate, and service the equipment as well as protection of the equipment
itself. To promote safety, we use hazard alert labeling in this manual. Follow
the associated guidelines to avoid hazards.

7
SECTION 2
Installing STE-8000 sensors
This section provides important instructions and guidelines for
installing the STE-8000 series sensors. Carefully review this
information before installing the controllers.
Installing the sensors includes the following topics that are covered in this
section.
Planning for motion sensing on page 9
Rough-in preparation on page 10
Installing the sensors on page 10
Maintenance on page 11
Planning for
motion sensing For STE-8201 only—Mount the STE-8201 sensor on a wall that will have an
unobstructed view of the typical traffic in the coverage area. When choosing a
location, do not install the sensor in the following areas.
Behind curtains or other obstructions
In locations that will expose it to sunlight or heat sources
Near a heating/cooling duct.
For details on the coverage pattern, see Specifications on page 6.
The effective detection range is approximately 10 meters or 33 feet. Factors that
may reduce the range include:
The difference between the surface temperature of the object and the
background temperature of the room is too small.
Object movement in a direct line toward the sensor.
Very slow or very fast object movement.
Obstructions as shown in the illustration Typical motion sensing coverage area
on page 9.
Illustration 2-1 Typical motion sensing coverage area

Installing STE-8000 sensors
Rough-in preparation
8
False detections may be triggered by:
The temperature inside the detection range suddenly changes because of
the entry of cold or warm air from an air-conditioning or heating unit.
The sensor being directly exposed to sunlight, an incandescent light, or
other source of far-infrared rays.
Small animal movement.
Rough-in
preparation Complete rough-in wiring at each sensor location prior to sensor installation.
This includes the following.
Routing the connecting cable from the sensor to a controller.
If required, install the appropriate backplate. See Accessories on page 6for
model numbers.
Connect the STE-8000 series sensor to a controller with a standard Ethernet cable
with RJ-45 connectors on each end. Maximum cable length is 75 feet (22.9
meters). Plenum-rated preassembled cables are recommended.
Installing the
sensors To install the sensor on a backplate, do the following:
1. Turn the Allen screws in the base of the NetSensor clockwise until they
clear the cover. Swing the sensor away from the mounting base to remove
it.
2. Route the Ethernet cable through the mounting base.
3. Fasten the mounting base directly to a 2 x 4 inch outlet box or a backplate
with the Allen screws toward the floor.
Illustration 2-2 Sensor mounting details
Connecting cable
Maximum 75 feet
or 22.9 meters
Allen
screws
Mounting
base
Illustration 2-3 Mounting screws
Turn clockwise to
remove from base.

STE-8001 and STE-8201 sensorsInstalling STE-8000 sensors
Maintenance
9
4. Insert the Ethernet cable coming from the base into the sensor.
5. Place the top of the sensor over the top of the mounting base and swing it
down over the Allen screw brackets. Be careful not to pinch any wiring.
6. Back the Allen screws out of the brackets until they engage the sensor cover
and hold it in place.
Maintenance Remove dust as necessary from holes in top and bottom. Clean the display with
soft, damp cloth and mild soap.

10
SECTION 3
User functions
This section covers topics for the end user in a facility.
User functions are limited to changing the occupied temperature setpoints from
the STE-8000.
Operating the
STE-8000 The functions are accessible through an STE-8000 series sensor. The functions are
entered or changed using the buttons and display on the front of the STE-8000.
Pressing either the up button or down button changes a selection,
setting, or value.
Pressing the setpoint button saves the setting or value. Typically saving
an entry also advances to the next display.
Note
The STE-8000 series sensors will display time if the controller to which they are
attached have been synchronized with system time within the previous 24
hours.
Illustration 3-1 The STE-8000 series display and buttons
LCD display with
temperature and time
UP and down
buttons
Setpoint button
Motion sensor
(STE-8201 only)

User functions
Changing setpoints
11
Changing
setpoints To enter or change the occupied setpoints you will need a Level 1 password.
Enter occupied setpoints
Procedure Steps STE display
Starting displayStart from the temperature display.
Enter the level one
password
1. Press the button.
2. Press the or buttons to change
the first digit.
3. Press the button to select the next
digit. Repeat for all four digits.
4.
Note: If a Level 1 password has not
previously been entered, the display
will change to the occupied cooling
setpoint display after Step 1.
Set the occupied
cooling setpoint 1. Press the or buttons to change
the cooling setpoint temperature. The
setpoint changes in increments of 0.5
degrees.
2. Press the button to save the value.
The display advances to set the
heating setpoint.
Set the occupied
heating setpoint 1. Press the or buttons to change
the heating setpoint temperature.
The setpoint changes in increments
of 0.5 degrees.
2. Press the button to save the value.
The display returns to the
temperature display.

12
SECTION 4
Commissioning functions
This topics in this section are advanced topics for control technicians
and engineers.
The commissioning functions that are accessible through an STE-8000 series
sensor are values and settings that are entered during the installation and
commissioning of a VAV terminal unit. Typically these functions do not change
after the installation and commissioning process.
To set up the commissioning functions, you will need the following:
Information about the VAV terminal unit including the configuration for
fans and reheat
The installation and operation manual supplied with the controller to
which the STE-8000 series sensor is connected.
The building automation system plans.
Users may change the occupied heating and cooling setpoints without accessing
the commissioning functions. This procedure is covered in User functions on
page 13.
Note
The instructions for commissioning functions cover all of the functions that an
STE-8000 sensor can set up in the BAC-8000 series of controllers. Not all
functions are available on every model of controller. Consult the installation
and operation manual supplied with the controller to verify the functions and
options that are available.

Commissioning functions
Enter the commissioning mode
13
Enter the
commissioning
mode For access to the commissioning functions you will need a Level 2 password.
If the controller has not been previously set up, no password is required.
A new Level 2 password can be entered in the advanced commissioning
functions. See the topic Advanced options on page 31.
Enter the commissioning mode
Procedure Steps STE display
Starting display Start from the temperature display.
Enter the
commissioning
password
1. Press the and buttons together
and hold them down until the
display changes to .
2. Press the or button to change
the first digit.
3. Press the button to select the next
digit. Repeat for all four digits.
4. When the button is pushed for the
fourth correct digit, the display
changes to .
Note: If a Level 2 password has not
previously been entered the display
will change to the display after
Step 1.
Select a
commissioning
function
Access to the commissioning
functions always start at the
display.

STE-8001 and STE-8201 sensors Commissioning functions
Setting up network communications
14
Setting up
network
communications Set the network communication settings before placing a controller on the
network. Setting network settings requires entering the Level 2 password which
is described in the topic Enter the commissioning mode on page 16.
Procedure to set up network communications
Procedure Steps STE display
Starting display 1. Start at the temperature display.
2. Enter the Level 2 password. The
display changes to the .
Select the
display
Press the button. The display changes
to .
Enter the device
instance.
1. Press the or buttons to change
the first digit.
2. Press the button to select the next
digit. Repeat for all seven digits.
3. When the button is pressed for the
last digit, the display changes to .
Enter the MAC
address.
1. Press the or buttons to change
the MAC address.
2. Press the button to save the
selected MAC address.
The display changes to .
Enter the baud 1. Press the or buttons to select a
new baud.
2. Press the button is save the
selected baud.
The display returns to .
Advance or exit 1. Press the or buttons to select
one of the following:
•or options
•to return to the temperature
display.
2. Press the button to select the next
function.

Commissioning functions
Balancing airflow
15
Balancing airflow The airflow balancing method described in this section requires a flow hood or
other accurate method to measure airflow. The airflow balancing procedure
requires entering the Level 2 password which is described in the topic Enter the
commissioning mode on page 16.
The airflow balancing procedure
Procedure Steps STE display
Starting display 1. Start at the temperature display.
2. Enter the Level 2 password. The
display changes to the .
Select the
display
1. From the display, press the
or buttons to show the
display.
2. Press the button to select .
The display advances to .
3. Press the button to select .
Measure and enter
the actual
maximum primary
airflow
The display begins flashing
and also displays the actual airflow
at the bottom.
1. Wait for the maximum airflow value
to stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the button to advance to the
entry display. stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the button to save the
measured airflow. The display
changes to .

STE-8001 and STE-8201 sensors Commissioning functions
Balancing airflow
16
Measure and enter
the actual
minimum primary
airflow
The display begins flashing
and also displays the actual airflow
at the bottom.
1. Wait for the maximum airflow value
to stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the button to advance to the
entry display. stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the button to save the
measured airflow. The display
advances to .
Advance or exit 1. Press the or buttons to select
one of the following:
•to balance the secondary VAV
for dual duct systems
•to choose another
commissioning function
•to return to the temperature
display.
2. Press the button to select the next
function.
Measure and enter
the actual
maximum
secondary airflow
The display begins flashing
and also displays the actual airflow
at the bottom.
1. Wait for the maximum airflow value
to stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the button to advance to the
entry display. stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the button to save the
measured airflow. The display
advances to .
The airflow balancing procedure
Procedure Steps STE display

Commissioning functions
Balancing airflow
17
Measure and enter
the actual
minimum
secondary airflow
The display begins flashing
and also displays the actual airflow
at the bottom.
1. Wait for the minimum airflow value
to stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the button to advance to the
entry display. stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the button to save the
measured airflow. The display
advances to .
Advance or exit 1. Press the or buttons to select
one of the following
•to balance the primary VAV
for dual duct systems
•to choose another
commissioning function
•to return to the temperature
display.
2. Press the button to select the next
function.
The airflow balancing procedure
Procedure Steps STE display

STE-8001 and STE-8201 sensors Commissioning functions
Setting commissioning setpoints
18
Setting
commissioning
setpoints The commissioning setpoints set the operational parameters and limits for the
VAV terminal unit. Setting configuration setpoints requires entering a Level 2
password which is described in the topic Enter the commissioning mode on
page 16.
Procedure to set the commissioning setpoints
Procedure Steps STE display
Starting displayEnter the Level 2 password. The display
changes to the .
Select the setpoint
display.
1. From the display, press the
or buttons to show the
display.
2. Press the button to select the
options. The display changes to
.
3. Press the button to select the
options.
Set the minimum
cooling setpoint 1. Press the or buttons to set the
minimum cooling setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the maximum
heating setpoint 1. Press the or buttons to set the
maximum heating setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.

Commissioning functions
Setting commissioning setpoints
19
Set the occupied
cooling setpoint 1. Press the or buttons to set the
occupied cooling setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Note: This setpoint can also be changed as
described in the section User functions on
page 13.
Set the occupied
heating setpoint 1. Press the or buttons to set the
occupied heating setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Note: This setpoint can also be changed as
described in the section User functions on
page 13.
Set the unoccupied
cooling setpoint 1. Press the or buttons to set the
unoccupied cooling setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the unoccupied
heating setpoint 1. Press the or buttons to set the
unoccupied heating setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the supply air
temperature
changeover setpoint
1. Press the or buttons to set the
changeover setpoint. The setpoint
will change in 1° increments.
2. Press the button to save the
setpoint and advance to the next
function.
Procedure to set the commissioning setpoints (Continued)
Procedure Steps STE display

STE-8001 and STE-8201 sensors Commissioning functions
Setting commissioning setpoints
20
Set the minimum
temperature
differential
setpoint
1. Press the or buttons to set the
differential setpoint. The setpoint
will change in 1° increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the standby
differential
setpoint
1. Press the or buttons to set the
standby differential setpoint. The
setpoint will change in 1° increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the supply
exhaust offset
1. Press the or buttons to set the
supply exhaust offset setpoint. The
setpoint will change in 1%
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the supply
exhaustdifferential
pressure setpoint
1. Press the or buttons to set the
supply exhaust differential pressure
setpoint.The setpoint will change in
increments of 0.01 inches of water.
2. Press the button to save the
setpoint and advance to the next
function.
Set the CO2
setpoint.
1. Press the or buttons to change
CO2 setpoint. The setpoint changes
increments for 1 part per million.
2. Press the button to save the
setpoint and complete the setpoint
changes.
The display returns to .
Advance or exit 1. Press the or buttons to select
one of the following:
•, , or options
•to choose another
commissioning function
•to return to the temperature
display.
2. Press the button to select the next
function.
Procedure to set the commissioning setpoints (Continued)
Procedure Steps STE display
Table of contents
Other Titus Accessories manuals