Toky AI808P Series User manual

Page 01 KKAI808PE01-A/0-20130904
AI808P
AI808P Series Intelligent Temperature Controller User Manual
Features:
TC / RTD / Analog signal universal input;
With display, alarm, adjusting and communication function;
Advanced Fuzzy algorithm & Two Degrees
of Freedom PID Arithmetic;
Optional control output, modularization design;
Good anti-interference;
Up to 50 programmable segments control;
Color bar display
AI808 Series Intelligent Temperature Controller (with 50 programmable segment control)
1. Model
Safe Caution
Please comply with the below important points.
Warning
Notice
An accident may happen if the operation does not comply with the instruction.
An operation that does not comply with the instruction may lead to product damage.
For your safty, please read following content carefully before you are using our temperature controller!
The instruction of the symbol in the manual is as below.
An accident danger may happen in a special condition.
Please read the manual carefully before you use the temperature controller.
Warning
1. A safty protection equipment must be installed or please contact with us for the relative information if the product is used under
the circumstance such as nuclear control, medical treatment equipment, automobile, train, airplane, aviation and equipment etc..
Otherwise, it may cause serious loss, fire or person injury.
2. A panel must be installed, otherwise it may cause creepage (leakage).
3. Do not touch wire connectors when the power is on, otherwise you may get an electric shock.
4. Do not dismantle or modify the product. If you have to do so, please contact with us first. Otherwise it may cause electric shock
and fire.
5. Please check the connection number while you connect the power supply wire or input signal, otherwise it may cause fire.
Caution
1. This product cannot be used outdoors. Otherwise the working life of the product will become shorter, or an electric shock accident
may happen.
2. When you connect wire to the power input connectors or signal input connectors, the moment of the No.20 AWG (0.50 mm2)
screw tweaked to the connector is 0.74n.m - 0.9n.m. Otherwise the connectors may be damaged or get fire.
3. Please comply with the rated specification. Otherwise it may cause electric shock or fire, and damage the product.
4. Do not use water or oil base cleaner to clean the product. Otherwise it may cause electric shock or fire and damage the product.
5. This product should be avoid working under the circumstance that is flammable, explosive, moist, under sunshine, heat radiation
and vibration. Otherwise it may cause explosion.
6. In this unit it must not have dust or deposit, otherwise it may cause fire or mechanical malfunction.
7. Do not use gasoline, chemical solvent to clean the cover of the product because such solvent can damage it. Please use some soft
cloth with water or alcohol to clean the plastic cover.
Dimension: 4: 48Wx48H 6: 48Wx96H 7: 72Wx72H 8: 96Wx48H 9: 96Wx96H
16 80W×160H 80 160W×80H
Output function: R: Relay S: Logic (SSR) D: Current (4-20mA)
Alarm function: B: One Alarm Output C: Two Alarm Output
(One more alarm will be added when the heating & cooling control is not used)
Signal input: 10: One signal input without communication
18: One signal input with RS485 communication (please indicate when order)

Page 02 KKAI808PE01-A/0-20130904
1
1
1
1
1
1
Model Alarm (Note 3)
No
No
No
RS485 (Modbus RTU)
RS485 (Modbus RTU)
RS485 (Modbus RTU)
Communication
OUT1 (Note 1) OUT2 (Note 2)
2. Model Illustration
Relay output
Relay output
Relay output
Relay output
Relay output
Relay output
Relay output
SSR output
4-20mA current output
Relay output
SSR output
4-20mA current output
Ambient humidity 45-85%RH
Ambient temperature 0-50
Total current 30mA 220VAC
Power supply AC/DC 100-240V
1) Whole controller parameters
Measurement accuracy ±0.3%FS±3digits 25
Control mode ON/OFF control PID heating control PID cooling control PID heating & cooling control
Communication function RS485 communication interface, MODBUS protocol
Panel protection level IP65
Temperature excursion 0.01%FS/
Between the connectors of power supply to relay output, power supply to signal input, relay output to
signal input 2000VDC; Between the low voltage signal isolated with each other 600VDC.
3. Main Technical Parameters
Dielectric strength
AI808P-4-RB10
AI808P-4-SB10
AI808P-4-DB10
AI808P-4-RB18
AI808P-4-SB18
AI808P-4-DB18
AI808P- RC10
AI808P- SC10
AI808P- DC10
AI808P- RC18
AI808P- SC18
AI808P- DC18
2
2
2
2
2
2
Model Alarm (Note 3)
No
No
No
RS485 (Modbus RTU)
RS485 (Modbus RTU)
RS485 (Modbus RTU)
Communication
OUT1 (Note 1) OUT2 (Note 2)
Relay output
Relay output
Relay output
Relay output
Relay output
Relay output
Relay output
SSR output
4-20mA current output
Relay output
SSR output
4-20mA current output
OUT2: Can be workable just under heating-cooling control(OT=3); under other control mode,
worked as alarm 3 (For size:48*48 worked as alarm 2)
Relay output capacity: 1A/250V AC.
OUT3: Alarm 3:
Relay output capacity: 1A/250V AC
Note:
OUT1: 4-20mA current output, load capacity: 600 max.
Relay output capacity: 3A/250V AC
SSR output capacity: 30mA/24V DC

Page 03 KKAI808PE01-A/0-20130904
Signal Input type Measuring range Resolution Input impedance
K type thermocouple
J type thermocouple
E type thermocouple
T type thermocouple
B type thermocouple
R type thermocouple
S type thermocouple
N type thermocouple
Reserved
PT100
JPT100
CU50
CU100
Linear voltage
Linear current
Linear voltage
Linear resistance
-50 1300
-50 1200
-50 1000
-50 400
600 1800
-10 1700
-10 1600
-50 1200
-199.9 850.0
-199.9 500.0
-50.0 150.0
-50.0 150.0
0 50mV
420mA
010V
0400
1
1
1
1
1
1
1
1
0.1
0.1
0.1
0.1
0.01%FS
0.01%FS
0.01%FS
0.01%FS
100K
100K
100K
100K
100K
100K
100K
100K
0.2mA)
0.2mA)
0.2mA)
0.2mA)
100K
<110
100K
0.2mA)
2) Input parameter table
4. Panel indication
SV Value or Parameter Code
PV Value or Parameter Code
AL1:AL1 Indicating Light
OUT2:OUT2 Indicating Light
AL2:AL2 Indicating Light
SET Function Key
OUT1:OUT1 Indicating Light
Shift Function Key
No
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Increase Key
Decrease Key
AL3:AL3 Indicating Light
AT: Auto-turning Indicating Light
Control Output Indicating Color Bar
(AI808P-4 without color bar display)
5. Panel Key Operation
1 key In normal display status, press key to show setting menu, press key for a few seconds
to show advanced setting menu.
2 key press key to make the parameters to flicker the parameters can be changed.
3 , key to change parameters in setting status, after each operation, press key to confirm the modify.
4 In advanced setting menu, press key for a few seconds to quit the menu and back to normal display status.
5 In normal display status, press key for 3 second to start Auto-tuning function at this moment AT indicating
lamp turns on.
(6) In normal display status, press Key to enter into programmable setting menu, press Key to enter into
programmable parameter setting menu.

Page 04 KKAI808PE01-A/0-20130904
6. Operation Sequence
Measuring status
Power on & Reset
Alarm 1
Alarm 2
Alarm 3
PV bias
value
Manual / auto
shift menu
Password lock
Control mode
OUT1 control
cycle
Cooling prportional
coefficient
effective when OT=3
Output function
setting menu
OUT2 control cycle
effective when OT=3
Heating cooling
control dead area
effective when OT=3
Alarm 1 hysteresis
Setting menu
Alarm 1 mode
Alarm 2 hysteresis
Alarm 2 mode
Alarm 3 hysteresis
Alarm 3 mode
Lower limit
of control
output
Upper limit
of control
output
Input signal
mode
Lower limit
of input signal
Upper limit
of input signal
Decimal point (Not effective
for TC / RTD input
Fliter constant
Lower limit of transmit current output
Upper limit of transmit current output
Baud rate
Meter
communication
address
Press SET
for a few
seconds
Press SET key for a few seconds
Proportional coefficient
Integral time
Derivative time
On/Off control
hysteresis
(effective when OT=0)
Press SET key for a few seconds
Press SET key
for a few seconds
Input function
setting menu Communication
setting menu
Change between celsius and fahrenheit
7. Program segment control setting
SET+ Start or stop the program
segment control
Program segment
setting menu
Power on & Reset
Measuring status
Operation Status, for
three types STOP, RUN
and HOLD can be choosed
Program segment control setting method
1) There are total 50 programmable segments. For each segment, there are 2 settable parameters: SV , ST .
2) SV value is the object control value of a segment, for example, if SV 01 is 200, the object control value of
this segment is 200
3) ST value is the control mode parameter of a segment.
When ST setting value is -51, it means it has finished this time’s programmable segment control, reset to single setting
value control mode (refer to example onw)
When ST setting value is -50 -1 it means the current segment will jump to the appointed segment, for example,
if ST -45 it means the current segment will jump to segment no.45 directly, after the control of this
segment is finished.
When ST setting value is 0 it means the program segment will jump to the next segment automatically when the
temperature get to
When ST setting value is 1 1440, unit is Minute, it means when runing within this segment, it will reach the setting value with average
speed; The meter will stop this segment’s operation when this segment’s ST value countdown to 0, if the ST value has already come to 0, but PV
measuring value does not meet with SV setting value, the program will not leave this segment until SV=PV. For example: SV =200
ST =10 the temperature is 30 ,the program will still runing in this segment for 10 minutes and the temperature will rise 17 per minute.
STEP Programmable
setting
SV Program
setting value
ST refer to the
illustration in the following
Press Key to enter into
programmable parameter
setting menu
programmable parameter
setting menu

Page 05 KKAI808PE01-A/0-20130904
Parameter name egnargnitteSnoitacidnI Ex-factory setting
Setting menu
Measured value amendment
OUT2 control cycle ( setting range can )
Dead area for heating & cooling control
Alarm hysteresis 1
Alarm mode 1
Alarm hysteresis 2
Alarm mode 2
Alarm hysteresis 3
Alarm mode 3
8. Menu Parameter
Manual / auto setting: 0 Manual 1: half-auto
Output function setting menu
Integral time
Control mode. 0 ON/OFF control 1 Heating control
Start Auto-tuning manually
2: auto Start Auto-tuning automatically after power on
Alarm 1 setting value
Alarm 2 setting value
Alarm 3 setting value
2Cooling control 3 Heating & cooling control
Proportional coefficient (P=0: ON / OFF control)
ON/OFF control hysteresis
Derivative time
OUT1 control cycle: Current output is 0;
Cooling proportional coefficient
1
1
1
1
1
1
1
SSR output is 1; the setting range of SSR output can
4) In normal display status, press key for a few seconds to show the parameter setting menu of
program segment control.
5) In normal display status, press key for a few seconds to enter into status setting value of program
segment control. You can choose RUN, STOP and HOLD three status in this segment.
Example Here is a control process with below requirement, the relevant setting is on the right side:
1) Temperature raise to 300 SV01=300 ST01=0;
2) Temperature raise from 300 to 500 (raise 10 degrees/ min) SV02=500 ST02=20
3) Temperature falls to 150 SV03=150 ST03=0;
4) Temperature is keep at 150 for 60 minute, and then SV04=150 ST04=60
Program jumps to No.10 segment ST05= -10
6) Temperature falls to 25 at No.10 segment SV10=25 ST10=0;
7) Program control stops running at No.11 segment.
exit the segment and control the temeprature according
to the SV (SV10=25)setting value ST11=-51;
0001, prohibit to modify SV; 0010, prohibit to modify Menu parameter;
0011, prohibit to modify SV and Menu;
Input function setting menu
Communication setting menu
Lower limit of control output
Upper limit of control output
Input signal type Please refer to input signal table
Lower display limit of input signal
Upper display limit of input signal
Decimal point setting. Only effective for analog signal input
Filter constant
Lower limit display for transmit current output
(with current transmit output can workable)
Baud rate
Meter communication address
Please refer to input signal table
Please refer to input signal table
0: unit of celsius, 1: unit of fahrenheit
Higher limit display for transmit current output
(with current transmit output can workable)

Page 06 KKAI808PE01-A/0-20130904
10. Connection Drawing
Model AI808P-6/AI808P-8
Accuracy
±
0.3%FS±3digits 25
Temperature excursion: 0.01%FS/
AI808P Series Temperature Adjustor
Model AI808P-9
Accuracy
±
0.3%FS±3digits 25
Temperature excursion: 0.01%FS/
AI808P Series Temperature Adjustor
Model
Alarm code Alarm mode Alarm output (AL1, AL2 is independent with each other
9. Apperance & Mounting Dimension
Alarm function table
Panel size
Side face size Mounting size
0
1
2
3
AL
SV
SV-AL SV
SV+AL
AL
HY
HY
HY
HY
Alarm PV AL
Cancel PV AL-HY
Alarm PV AL
Cancel PV AL+HY
Alarm PV AL+SV
Cancel PV SV+AL-HY
Alarm PV SV-AL
Cancel PV SV-AL+HY
Absolute upper limit alarm
Absolute Lower limit alarm
Upper Limit deviation alarm
Lower Limit deviation alarm
Temperature Raise
Temperature decrease
Temperature Raise
Temperature decrease
Formula
AI808P-4
AI808P-6
AI808P-7
AI808P-8
AI808P-9
AI808P-80
AI808P-16
Unit mm
48
48
72
96
96
160
80
AH(Min)
G
B C D E F
J
48
96
72
48
96
80
160
97.5
97.5
97.5
97.5
97.5
96
96
6.5
9
9
9
9
13
13
91
88.5
88.5
88.5
88.5
83
83
45.5
45
67.5
90
92
155.5
76
25
25
25
25
25
30
30
45.5
90
67.5
45
92
76
155.5
45
89.5
67
44.5
91.5
75.5
155
K
(Min)
25
25
25
25
25
30
30
A
B
C
E
D
F
G
K
J+0.5
-0
+0.5
-0 H

Page 07 KKAI808PE01-A/0-20130904
11. Simple Problem Shooting
Display Message
Display HHHH
Display LLLL
Shooting Method
Input disconnect or over upper limit, please check input signal, FH value and ambient working temperature.
Input disconnect or under lower limit, please check input signal, FL value and ambient working temperature.
11.Communication
AI808P series adjustor follow Modbus RTU communication protocol, and it can run RS485 half-duplex communication.Read
function code is 0x03, write function code is 0x10, 16-bit CRC checking is applied. The coulometer can not return error message.
Start bit Data bit Stop bit Check bit
1 8
2
None
Data Frame flag:
1. Read Multiple Registers
For example: The host computer read the float number AL1 (The value of Alarm 1 is 15.4).The address code of AL1 is 0x0000,
for AL1 is float number (4bits), it will occupy 2 data register. Reference IEEE-574 standard the hexadecimal 16 result of the
decimal float number is
0x41766666
.
Request from the host computer (Read Multiple Registers)
1 2 3 4 5 6 7 8
Unit Address Function code
Start
Address Hi
Start
Address Lo
Data
length Hi
Data
length Lo CRC code Lo CRC code Hi
0x01 0x03 0x00 0x00
0x04 0xE5 0xC9
0x02
Model AI808P-16/AI808P-80
Accuracy 0.3%FS±3digits 25
Temperature excursion: 0.01%FS/
AI808P Series Temperature Adjustor
Note: If there is any change, please subject to the drawing on the meter!
Model AI808P-4
Accuracy 0.3%FS±3digits 25
Temperature excursion: 0.01%FS/
AI808P Series Temperature Adjustor
Model AI808P-7
Accuracy 0.3%FS±3digits 25
Temperature excursion: 0.01%FS/
AI808P Series Temperature Adjustor

Page 08 KKAI808PE01-A/0-20130904
Correct answer from slave unit (Read Multiple Registers)
2 3 4 5 6 7 8 9
code
Function Data byte No. Data1
Hi byte
Data1
Lo byte
Data2
Hi byte
Data2
Lo byte
CRC
Code Lo
CRC
Code Hi
0x03 0x04
0x41 0x76 0x66 0x66 0xE2 0xF4
1
Address
0x01
2. Write Multiple Registers
For example: The host computer write the float number (setting value 600) ,
The address code for SV is 0x0000, for SV is float number (4bits), it will occupy 2 data register. Reference IEEE-574
standard the hexadecimal 16 result of the
decimal float number is
0x41766666
.
Request from the host computer (Write Multiple Registers)
12345678 9
Unit
address
Unit
address
Function
Code
Function
Code
0x01
10 11 12 13
Data
Length Hi
Data
Length Hi
Data
Length Lo
Data
Length Lo
Data
Length
CRC
Lo
CRC
Lo
Start
address Hi
Start address
8 Hi
Start address
8 Lo
Start
address Lo
0x10 61x020x000x0 0x04 0xFD
Data 1
Hi
Data 1
Lo
Data 2
Hi
Data 2
Lo
CRC
Hi
CRC
Hi
0x00 0x00 0x44 0x00 0x00 0xFC
Correct answer from slave unit (Read Multiple Registers)
123456 7 8
0x01 0x10 0x00 0x00 0x00 0x02 0x41 0xC8
AI808P Series table reference address
Code Number of Variable Data
Length
Read & Write
allow Remark
0
2
4
6
8
10
12
14
16
18
0x0000
0x0002
0x0004
0x0006
0x0008
0x000A
0x000C
0x000E
0x0010
0x0012
0x0014
0x0016
0x0018
0x001A
0x001C
0x001E
0x0020
0x0022
0x0024
0x0026
Setting Value SV
Alarm value AL1
Alarm value AL2
Alarm value AL3
Correct value PS
Proportion rate P
Integral time I
Differentia lD
ON/OFF Control Hysteresis HY
Heating & cooling dead district DB
Alarm 1 Hysteresis HY1
Alarm 2 Hysteresis HY2
Alarm 2 Hysteresis HY3
Control output Lo OLL
Control output Hi OLH
Display Lo FL
Display Hi FH
Analog Lo Value
Analog Hi Value
Measuring Value
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
Reference
address
20
22
24
26
28
30
32
34
36
38

Page 09 KKAI808PE01-A/0-20130904
Code Number of Variable Data
Length
Read & Write
allow Remark
0x0028
0x002A
0x002C
0x002E
0x0030
Lock LCK
Control output OT
Heating control Turn CT
Cooling proportion C_P
1
1
1
1
1
R
R
R
R
R
0x0032
0x0034
0x0036
0x0038
0x003A
0x003C
0x003E
0x0040
0x0042
Cooling control Turn C_CT
Alarm 1 mode AD1
Alarm 2 mode AD2
Alarm 2 mode AD2
Input signal select INP
Decimal DP
Filter FT
Baud rate BAD
Address ADD
1
1
1
1
1
1
1
1
1
R
R
R
R
R
R
R
R
R
Note1
Note1
Note1
Note2
Note3
Reference
address
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
0x0044
0x0046
0x0048
0x004A
Programmable Value STEP
1R
The 1 section setting value SV1 2R/W
The 1 section status setting value ST1 2R/W
The 2 section setting value SV2
The 2 section status setting value ST2
The 3 section setting value SV3
The 3 section status setting value ST3
The 4 section setting value SV4
The 4 section status setting value ST4
The 5 section setting value SV5
The 5 section status setting value ST5
The 6 section setting value SV6
The 7 section setting value SV7
The 8 section setting value SV8
The 6 section status setting value ST6
The 7 section status setting value ST7
The 8 section status setting value ST8
The 9 section status setting value ST9
The 10 section status setting value ST10
The 11 section status setting value ST11
The 9 section setting value SV9
The 10 section setting value SV10
The 11 section setting value SV11
The 12 section setting value SV12
The 13 section setting value SV13
The 12 section status setting value ST12
0x004C
0x004E
0x0050
0x0052
0x0054
0x0056
0x0058
0x005A
0x005C
0x005E
0x0060
0x0062
0x0064
0x0066
0x0068
0x006A
0x006C
0x006E
0x0070
0x0072
0x0074
0x0076
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
2R/W
Auto/Manual free change

Page 10 KKAI808PE01-A/0-20130904
The 14 section setting value SV14
The 15 section setting value SV15
The 16 section setting value SV16
The 13 section status setting value ST13
The 14 section status setting value ST14
The 15 section status setting value ST15
The 16 section status setting value ST16
The 17 section status setting value ST17
The 18 section status setting value ST18
The 19 section status setting value ST19
The 20 section status setting value ST20
The 21 section status setting value ST21
The 22 section status setting value ST22
The 23 section status setting value ST23
The 24 section status setting value ST24
The 25 section status setting value ST25
The 26 section status setting value ST26
The 17 section setting value SV17
The 18 section setting value SV18
The 19 section setting value SV19
The 20 section setting value SV20
The 21 section setting value SV21
The 22 section setting value SV22
The 23 section setting value SV23
The 24 section setting value SV24
The 25 section setting value SV25
The 26 section setting value SV26
The 36 section setting value SV36
Code
Data
Length
Remark
Reference
address
Read & Write
allow
Variable Name
The 27 section status setting value ST27
The 27 section setting value SV27
The 28 section status setting value ST28
The 28 section setting value SV28
The 29 section status setting value ST29
The 29 section setting value SV29
The 30 section status setting value ST30
The 30 section setting value SV30
The 31 section status setting value ST31
The 31 section setting value SV31
The 32 section status setting value ST32
The 32 section setting value SV32
The 33 section status setting value ST33
The33 section setting value SV33
The 34 section status setting value ST34
The 34 section setting value SV34
The 35 section status setting value ST35
The 35 section setting value SV35
The 36 section status setting value ST36
The 37 section setting value SV37

Page 11 KKAI808PE01-A/0-20130904
Note
Note
program Section Operating Status
Output Alarm Status
The 37 section status setting value ST37
The 38 section status setting value ST38
The 38 section setting value SV38
The 39 section status setting value ST39
The 39 section setting value SV39
The 40 section status setting value ST40
The 40 section setting value SV40
The 41 section status setting value ST41
The 41 section setting value SV41
The 42 section status setting value ST42
The 42 section setting value SV42
The 43 section status setting value ST43
The 43 section setting value SV43
The 44 section status setting value ST44
The 44 section setting value SV44
The 45 section status setting value ST45
The 45 section setting value SV45
The 46 section status setting value ST46
The 46 section setting value SV46
The 47 section status setting value ST47
The 47section setting value SV47
The 48 section status setting value ST48
The 49 section status setting value ST49
The 49 section setting value SV49
The 50 section status setting value ST50
The 50 section setting value SV50
The 48 section setting value SV48
Code
Data
Length
Remark
Reference
address
Read & Write
allow
Variable Name
R Read only R/W Read/Write
Parameter setting range , please refering to products user’s manual
Note 1 Alarm Mode
Note 2 Input Signal (please refer to input parameter table)
Note 3
Data value
Baud rate BAD 4.8K 9.6K
01
Upper Alarm Lower Alarm
Upper deviation alarm
Lower deviation alarm
Alarm Mode
Corresponding values
Note 4: Operating Status
Operating Status
Corresponding values
Note 5: Output Alarm Status ( 1 means ON, 0 means OFF)
Parameter bits
Control Status

Page 12 KKAI808PE01-A/0-20130904
unsigned int Get_CRC(uchar *pBuf, uchar num)
{
unsigned i,j;
unsigned int wCrc = 0xFFFF;
for(i=0; i<num; i++)
{
wCrc ^= (unsigned int)(pBuf[i]);
for(j=0; j<8; j++)
{
if(wCrc & 1){wCrc >>= 1; wCrc ^= 0xA001; }
else
wCrc >>= 1;
}
}
return wCrc;
}
16 digit CRC verify program
This manual suits for next models
6
Table of contents
Other Toky Temperature Controllers manuals