TorqSense SGR510 Series User manual

SGR510/520 SERIES
TRANSDUCER
USER MANUAL
CAUTION
This instruction manual should be read carefully and the
safety instructions observed before installing or operating
the equipment related to this manual.
Apollo Park, Ironstone Lane, Wroxton, Banbury
Oxon, OX15 6AY
Tel: +44 (0)1869 238400 Fax: +44 (0)1869 238401
Email: info@sensors.co.uk Web: www.sensors.co.uk

Sensor Technology 2022 Page 2 SGR4384V (Rev 3)
While every precaution has been exercised in the compilation of this document to ensure the
accuracy of its contents, Sensor Technology Ltd, assumes no responsibility for any errors or
omissions. Additionally, no liability is assumed for any damages that may result from the use of
the information contained in this document.
Copyright
Copyright 2022 Sensor Technology Ltd. All rights Reserved.
Copying or reproducing of all or any part of the contents of this manual is strictly prohibited
without the express permission of Sensor Technology.
Trademarks
TorqSense is a registered trademark of Sensor Technology Ltd.
TorqView is a trademark of Sensor Technology Ltd.
LabVIEW is a trademark of National Instruments Corporation.
National Instruments is a trademark of National Instruments Corporation.
Windows is a registered trademark of Microsoft Corporation.
Lifetime Warranty
Sensor Technology Ltd’s standard range of products are warranted against manufacturing
defects and component failure for two years from date of purchase, subject to fair wear and
tear and return for the first year's free of charge annual re-calibration. This warranty is extended
indefinitely if the equipment is returned to Sensor Technology, or its distributor, for annual re-
calibration, when software and hardware updates, if required, will be carried out free of charge.
Standard range means those products as described in the company's product data sheets.

Sensor Technology 2022 Page 3 SGR4384V (Rev 3)
Table of Contents
Getting Started ............................................................................................... 4
Introduction .................................................................................................. 4
Hardware Revisions ..................................................................................... 4
Unpacking the transducer ............................................................................ 5
Mechanical Installation ................................................................................. 6
Operating Principles ..................................................................................... 7
Operation ........................................................................................................ 8
Powering the transducer .............................................................................. 8
Using the transducer .................................................................................... 8
Built In Test (BIT) ......................................................................................... 9
Normal Operation ....................................................................................... 10
Peak Mode..............................................................................................10
Analog Scaling........................................................................................10
Warning Signals ......................................................................................... 11
Error Signals ............................................................................................... 13
Peak Input .................................................................................................. 13
Analog Output.........................................................................................13
Peak Reset.............................................................................................13
Analog Outputs ........................................................................................... 14
Data Assignments...................................................................................14
Voltage/Current Assignments.................................................................16
Fail Output .................................................................................................. 17
Limit Output ................................................................................................ 18
Zeroing the transducer ............................................................................... 19
Electrical Signal......................................................................................19
Digital Command....................................................................................20
Resetting transducer to factory default ....................................................... 20
Examples of reading/collecting data ........................................................... 21
Optional Accessories .................................................................................. 22
Analog Lead ............................................................................................... 22
Digital Lead (SGR520/540 series ONLY) ................................................... 22
Digital Adaptor Lead (SGR520/540 series ONLY) ...................................... 22
AC Mains Adaptor Power Supply (PSU) .................................................... 22
Additional Related Products and Transducer Resources ........................ 22
Transducer Display ETD ............................................................................ 22
Transducer Signal Breakout Unit (SBU) ..................................................... 22
TorqView (SGR520/540 series ONLY) ....................................................... 22
Transducer Control Program (SGR520/540 series ONLY) ......................... 22
Transducer Communication Protocol (SGR520/540 series ONLY) ............ 22
Transducer DLL Programmers Guide (SGR520/540 series ONLY) ........... 22
Leads ............................................................................................................ 23
Analog Lead - Pin Out ................................................................................ 23
Digital Lead - Pin Out (SGR520/540 Series ONLY) ................................... 24
Transducer Connections ............................................................................. 25
Analog ........................................................................................................ 25
Digital ......................................................................................................... 25
Declaration of Conformity ........................................................................... 26

Sensor Technology 2022 Page 4 SGR4384V (Rev 3)
Getting Started
Introduction
The SGR Torque Transducer provides a method of precisely measuring bi-
directional rotary or static torque. It can also be fitted with a speed sensor for monitoring in
dynamic applications, enabling direct measurements of transmitted power.
The SGR series transducers require no external instrumentation and has its own built in test
capability. Its compact size makes it ideal for use in applications where there is little space for
any extra equipment. Analog voltage outputs are standard, with current outputs available as
an option. The SGR520/540 series can also be connected to a PC via USB (optional) or RS232
so that its configuration can be changed, or by using TorqView to display torque, speed and
power.
Hardware Revisions
The SGR series transducers use two different hardware revisions. The two hardware revisions
are very similar in functionality, but one major difference is a third analog channel (MK4). The
two revisions can be identified by the Firmware Version, which is shown on the product label,
affixed to the transducer.
Firmware Revision Hardware Designation
5 or lower MK3
6 or greater MK4

Sensor Technology 2022 Page 5 SGR4384V (Rev 3)
Unpacking the transducer
The following standard components are included:
1 x SGR Series Transducer
1 x SGR Electronics Module (Only if SGR530/540 ordered).
1 x User Manual.
1 x Calibration Certificate.
Additional components for SGR520/540 series:
1 x TorqView program installation USB flash drive, SGR Configuration Software,
Manuals & Appendices in PDF format, USB driver.
The following items may also be included:
12pin Lumberg (female) and/or 12pin Lumberg (male).
1 x 2.5m Analog Lead - 15 way ‘D’ type connector (female) to 12pin Lumberg (female).
1 x 2.5m Digital Lead - 15 way ‘D’ type connector (male) to 12pin Lumberg (male).
(SGR520/540 series transducer ONLY).
1 x Digital Adaptor Lead (DC Jack with USB and/or RS232 connections, depending on
options requested) (SGR520/540 series transducer ONLY).
1 x Transducer Display ETD
1 x AC Mains Adaptor Power Supply.
1 x Transducer Signal Breakout Unit.
1 x Analog Dongle.
CAUTION
The SGR series transducers should not be operated at any torque load greater or
speed faster than that specified in the Product data sheet and on the Transducer.
CAUTION
The SGR series transducers should be installed using correct couplings rated for
the maximum torque and speed for the operation.
CAUTION
The SGR series transducers should not be operated in an environment where that
operation could be life threatenin
g
or a dan
g
er to personnel.
CAUTION
In electrically noisy environments, the SGR series transducers should be earthed
usin
g
the earthin
g
post located on the transducer.

Sensor Technology 2022
Page 6
SGR4384V (Rev 3)
Mechanical Installation
To obtain the best measurements from your torque transducer, it is essential that it is
correctly installed.
To avoid damaging the transducer during the installation process, it is highly recommended
that it is electrically connected and working, so that any torque overloads applied due to
handling can be monitored.
For Transducers above 1Nm or 10lbf.in. it is recommended that the body of the transducer
be restrained from rotation by using a strap or straps connected to the tapped holes in the
end plates and that it is not rigidly mounted. Couplings should be used to allow for angular
misalignment while the transducer shaft takes up any parallel misalignment. Care should be
taken not to induce any end loads or bending moments to the shaft, see below, as these
may induce inaccuracies to the torque measurement and in extreme cases damage the
transducer.
Should rapid variations in torque need to be measured in detail e.g.
torque fluctuations in gearboxes or multi vane pumps then it is
recommended using torsionally rigid couplings be fitted at both ends
of the transducer shaft such as single membrane couplings and that
these are correctly selected for the transducer rating and speed.
An undersized coupling will not transmit the torque while the high
inertia of an oversized coupling can result in instantaneous peak
torques far in excess of the measured torque. Alternatively, for lower
bandwidth applications where it is more important to measure the
‘average’ torque rather than fast torque fluctuations then couplings
with a degree of compliance would be more appropriate.
Never use a solid coupling to connect a SGR series transducers
Torque Transducer
For Transducers below 1Nm or 10lbf.in or if the application requires
the body to be rigidly mounted then it is recommended that double
couplings should be used at each end to compensate for any
misalignment of the input/output shafts and the system designed to
eliminate any end loads on the transducer shaft. For applications
where end loads cannot be avoided please consult the sales
department for advice prior to ordering.
When using a pulley or pulleys it is recommended a bearing block or
blocks should be used to ensure bending loads are not transmitted to
the transducer.
Lastly, consider using a guard over the transducer and couplings
Single membrane
coupling
(Flexible mounting)
Double membrane
coupling
(Rigid mounting)

Sensor Technology 2022 Page 7 SGR4384V (Rev 3)
Whilst the transducer is resistant to EMC interference to BS EN 61326-1:2006, the
sensible routing of cables is important to avoid possible EMC interference. Avoid
running the transducer cables close, and/or parallel, to high voltage cables, solenoid
valves, generators or inverters etc. If the cables must follow the same route as
interfering cables then additional screening such as metal conduit should be used to
provide isolation.
To avoid damaging the transducer during installation, it is highly recommended that
it is electrically connected and working during this process, so that any torque
overloads due to handling can be monitored.
Operating Principles
SGR510/520 series transducers operate using a four-element strain gauge wheatstone bridge,
which is connected to a miniature shaft mounted analog to digital converter and microcontroller.
The microcontroller conditions and measures the strain gauge bridge output as close to the
gauges as possible, eliminating any possible external noise pick up in the gauge wiring.
The shaft mounted electronic module is wirelessly powered by a radio frequency source which
drives a stator coil, the output of which is received by a rotor coil on the shaft thus making the
system completely contactless. This eliminates the need for slip rings and their associated wear
and noise problems.
The shaft microcontroller outputs a digital serial stream that is transferred back from rotor to
stator by modulating the impedance of the rotor coil and detecting the impedance changes at
the stator coil. A secondary high-performance microcontroller receives the serial stream from
the shaft microcontroller, which then performs calibration and temperature compensation
before outputting the results digitally via RS232, CAN bus or USB. A 16-bit digital to analog
converter also outputs the sensors data as a fully calibrated and compensated analog voltage
or current.
Pre-load, note:
All SGR510/520 transducers with a LED in the centre of the front label (connector side) have
a bearing pre-load spring fitted internally at the left hand side (pre-load end) when viewing the
front label of the transducer and with the earth stud bottom ride hand corner.
All SGR530/540 transducers with a LED on the separate electronics module have a bearing
pre-load spring fitted internally at the left hand side (pre-load end) of the transducer head when
viewing the label of the transducer head and the connector and gland facing towards you.
If there is a possibility of an end load being applied to the transducer, the transducer
should be orientated during installation such that the load is applied at the pre-load end
(side with the internally fitted spring). Excessive end loads must be avoided and it is
recommended that appropriate couplings be used to compensate for axial and radial
misalignment.

Sensor Technology 2022 Page 8 SGR4384V (Rev 3)
Operation
Powering the transducer
To power the transducer a supply voltage of 12-32VDC is required with a minimum current of
1 amp (to supply peak start-up current). If a Transducer Display ETD is used, the ETD will
provide power to the transducer. If a Transducer Signal Breakout Unit is used, the power supply
should be plugged into the DC jack on the Breakout Unit. If a Digital Adaptor Lead is used, the
power supply should be plugged into the DC jack on the lead.
If a Transducer Display ETD, Transducer Signal Breakout Unit or a Digital Adaptor Lead are
not used, then power can be provided via the 15 way ‘D’ type connector on either the 2.5m
Analog or Digital Lead. A supply voltage of 12-32VDC should be connected on Pin 1, with
Ground on Pin 2.
Note: It is imperative that the voltage does not drop below 12V at any stage.
Using the transducer
1. Switch on the SGR series transducer by ensuring power is supplied.
2. Allow the transducer to carry out its Built In Test (BIT) procedure. Refer to the Built In
Test section for further details.
3. Allow five minutes for the equipment to reach thermal equilibrium before making any
measurements.
4. Zero the transducer, refer to the Zeroing the transducer section.
5. The transducer is ready for use, examples of different ways to extract data can be
found in the Examples of reading/collecting data section.
CAUTION
Only provide power through either the Analog or Digital lead.
Do NOT provide power through both leads simultaneously.

Sensor Technology 2022 Page 9 SGR4384V (Rev 3)
Built In Test (BIT)
When the SGR series transducer is switched on it will carry out its Built In Test (BIT) procedure.
While the BIT procedure is taking place there will be a series of green flashes from the LED,
this is followed by a steady green or an intermittent green flash depending upon the mode of
operation.
If the transducer fails its BIT procedure the transducer will display an error sequence identifying
the results of each system test. The sequence will repeat until the transducer is powered off.
The error sequence is prefixed with quick succession of red flashes, identifying the LED
sequence as an error condition
After a pause a sequence of green and red flashes will indicate the results of each system test.
The following table lists the tests and there test order, for each test the transducer will output
either a GREEN for PASS or RED for FAIL.
Test/Sequence Number System Checks
1 Electronics Check
2 Shaft Electronics
3 Temperature Sensor Check
4 Internal Voltage Check
5 Data Configuration Check
6 Calibration Check
7 SAW Parameters Check
8 ORT Parameters Check
9 SGR Parameters Check
If a failure condition exists, try power cycling the transducer. Contact the factory if the problem
continues.
If an error occurs during operation (solid RED LED), but is not present on power on, the BIT
procedure may not identify the fault. If the Zero Input has been wired, it is possible to display
the Built In Test output during a solid red, to do this, switch the Zero Input ON until the
transducer starts flashing RED.

Sensor Technology 2022
Page 10
SGR4384V (Rev 3)
Normal Operation
A solid green LED indicates normal mode and the transducer is working correctly.
An intermittent green flash indicates a special mode of operation; the led sequences below
show the different modes.
Peak Mode
Peak Mode is active, if configured to do so the analog output will output a peak value. Please
refer to the Peak Input section for further details.
Analog Scaling
The Analog Scaling status message is shown when a user defined data or voltage scale has
been applied to either analog channel. This message is only relevant on SGR520/540 series
transducers.
Peak Mode
Peak Mode and Analog Scaling
[SGR 520/540 Series ONLY]
Analog Scaling
[SGR 520/540 Series ONLY]

Sensor Technology 2022 Page 11 SGR4384V (Rev 3)
Warning Signals
A warning signal is indicated when the transducer detects a condition which impedes normal
operation or the transducer is operating outside of normal operating parameters.
Different hardware revisions indicate warnings in different ways, refer to the appropriate section
below for correct identification.
Firmware Version 5 or lower
A warning LED sequence is prefixed with a quick succession of alternating red/green flashes,
identifying the LED sequence as a warning condition. A warning sequence will override the
normal operation mode LED.
After a pause a sequence of green or red flashes will indicate which warning conditions are
flagged. The LED sequence will iterate through each of the flags in the table below, flashing
the LED for each. A RED flash indicates that a condition has been flagged; a GREEN flash
indicates that a condition is clear.
Firmware Version 6 or greater
A warning LED sequence is prefixed with a quick succession of flashing yellow lights. A warning
sequence will override the normal operation mode LED.
After a pause a sequence of green or yellow flashes will indicate which warning conditions are
flagged. The LED sequence will iterate through each of the flags in the sequence table, shown
on the next page, flashing the LED for each. A YELLOW flash indicates that a condition has
been flagged; a GREEN flash indicates that a condition is clear.

Sensor Technology 2022 Page 12 SGR4384V (Rev 3)
Once the LED sequence is complete, the sequence will restart, this will continue until the
warning has cleared.
Sequence
Number Warning Flag Reason and Action required
1 Analog Fault CH0
In voltage output mode the analog pin is short circuit,
in current output mode the analog output pin is open
circuit. Check the analog connector wiring for Analog
CH0.
2 Analog Fault CH1
In voltage output mode the analog pin is short circuit,
in current output mode the analog output pin is open
circuit. Check the analog connector wiring for Analog
CH1.
3 Zero Offset High
A torque offset greater than 10% of FSD has been
applied to the measured torque value. The offset is set
when the transducer is zeroed, either by the zero input
on the analog connector or via a digital command or
setting.
4 Exceeded Temp
Shaft temperature has exceeded normal operating
conditions. Temperature compensation may no longer
be effective or calibration valid.
5 Over Torque Torque greater than 201% of FSD has been applied.
6 Critical Over Torque Torque greater than 300% of FSD has been applied.
Contact the factory if the warning continues.
7 Head Disconnect
The transducer head has been disconnected. Power
off the transducer electronics and check the cabling.
This warning is only relevant for transducers with
separate heads.
8 Analog Fault CH2
(Firmware >= 6)
In voltage output mode the analog pin is short circuit,
in current output mode the analog output pin is open
circuit. Check the analog connector wiring for Analog
CH2.
For example, the following sequence would indicate warnings for ‘Analog Fault CH0’ and ‘Zero
Offset High‘:
Firmware Version 5 or lower
Firmware Version 6 or greater

Sensor Technology 2022
Page 13
SGR4384V (Rev 3)
Error Signals
An error or fault signal is indicated when the transducer detects a condition which effects its
fundamental operation. An error or fault condition will be indicated by a solid red LED. Any error
that occurs will latch the LED on and it will remain on until the transducer is reset. An error
condition will override a warning and normal mode LED sequence.
If the error persists across multiple power cycles, a fault may have developed with the
transducer and you will need to contact the factory.
Peak Input
The peak input is a control signal that has two main purposes. It can control what data gets
applied to the torque analog output, and it can be used to reset the torque peak values.
The peak input is activated by grounding pin 8 of the Analog 15 Way ‘D’ Socket. The best way
to control the peak input is to use a toggle switch.
Analog Output
When activated any analog output channel configured as “Torque – Auto Assign” will switch
from being the current torque value, to the highest measured torque value since reset, if the
analog output is not unipolar then the torque direction will be output.
Peak Reset
When the peak input is toggled, i.e. off-on-off or on-off-on, all torque peak values on both analog
and digital interfaces will be reset to defaults. A peak input toggle will also clear any latched
fault condition or limit trigger.

Sensor Technology 2022 Page 14 SGR4384V (Rev 3)
Analog Outputs
The transducer has multiple analog outputs which can be configured to different data values,
voltages, currents and scales. Transducers with Firmware Version 5 or lower, have 2 analog
channels, and transducers with Firmware Version 6 or greater, have 3 analog channels.
Basic models are preconfigured based on the model and options selected, advanced models
hand the configuration to the user. The configuration of the analog outputs for advanced models
is done using Transducer Control; please refer to the Transducer Control manual for further
details.
The following tables show the default assignments for each model and analog option.
Data Assignments
Firmware Version 5 or lower
Model Analog CH0 Analog CH1
SGR510 Torque – Auto Assign1
Scale: 0 – FSD
Torque – Peak
Scale: 0 – FSD
SGR530
SGR511
Torque – Auto Assign1
Scale: 0 – FSD
Speed Fast (RPM)
Scale: 0 – Max Speed
SGR512
SGR531
SGR532
SGR513 Torque – Auto Assign1
Scale: 0 – FSD
Power (Watts)
Scale: 0 – Max Watts
((FSD in Nm x Max Speed) / 9.551)
SGR533
SGR520 Advanced Model - User Selectable
Factory Default:
Torque – Auto Assign1
Scale: 0 – FSD
Advanced Model - User Selectable
Factory Default:
Torque – Peak
Scale: 0 – FSD
SGR540
SGR521 Advanced Model - User Selectable
Factory Default:
Torque – Auto Assign1
Scale: 0 – FSD
Advanced Model - User Selectable
Factory Default:
Speed Fast (RPM)
Scale: 0 – Max Speed
SGR522
SGR541
SGR542
1 The value output by channels assigned with “Torque – Auto Assign” is dependent on the peak switch. If
unconnected, or Peak is OFF, the channel is assigned with Torque, if Peak is ON, the channel is assigned
with Torque – Peak. Refer to the Peak Input section for more details.

Sensor Technology 2022 Page 15 SGR4384V (Rev 3)
Firmware Version 6 or greater
Model Analog CH0 Analog CH1 Analog CH2
SGR510 Torque – Actual
Scale: 0 – FSD
Torque – Peak
Scale: 0 – FSD
Torque – Auto Reset
Scale: 0 – FSD
SGR530
SGR511
Torque – Auto Assign1
Scale: 0 – FSD
Speed Fast (RPM)
Scale: 0 – Max Speed
Power (Watts)
Scale: 0 – Max Watts
((FSD in Nm x Max
Speed) / 9.551)
SGR512
SGR531
SGR532
SGR513
No longer available
SGR533
SGR520
Advanced Model - User
Selectable
Factory Default:
Torque – Actual
Scale: 0 – FSD
Advanced Model - User
Selectable
Factory Default:
Torque – Peak
Scale: 0 – FSD
Advanced Model - User
Selectable
Factory Default:
Torque – Auto Reset
Scale: 0 – FSD
SGR540
SGR521 Advanced Model - User
Selectable
Factory Default:
Torque – Auto Assign1
Scale: 0 – FSD
Advanced Model - User
Selectable
Factory Default:
Speed Fast (RPM)
Scale: 0 – Max Speed
Advanced Model - User
Selectable
Factory Default:
Power (Watts)
Scale: 0 – Max Watts
((FSD in Nm x Max
Speed
)
/ 9.551
)
SGR522
SGR541
SGR542
1 The value output by channels assigned with “Torque – Auto Assign” is dependent on the peak switch. If
unconnected, or Peak is OFF, the channel is assigned with Torque, if Peak is ON, the channel is assigned
with Torque – Peak. Refer to the Peak Input section for more details.

Sensor Technology 2022 Page 16 SGR4384V (Rev 3)
Voltage/Current Assignments
Assignments apply to all channels.
Option Analog Output Type Analog Output
OPTN-A
SGR51x/SGR53x Voltage Bipolar ±1V, 0V Zero
OPTN-B
SGR51x/SGR53x Voltage Bipolar ±5V, 0V Zero
OPTN-C
SGR51x/SGR53x Voltage Bipolar ±10V, 0V Zero
OPTN-D
SGR51x/SGR53x Current 0 - 20mA
OPTN-E
SGR51x/SGR53x Current 4 - 20mA
OPTN-U
SGR51x/SGR53x Voltage User specified when ordered
check transducer label
OPTN-V
SGR51x/SGR53x Current ±8mA, 12mA Zero
Advanced Model
SGR52x/SGR54x Voltage
User Selectable
Factory Default:
Bipolar ±10V, 0V Zero
Advanced Model (OPTN-F)
SGR52x/SGR54x
User Selectable
Voltage/Current
User Selectable
Factory Default:
Bipolar ±10V, 0V Zero

Sensor Technology 2022
Page 17
SGR4384V (Rev 3)
Fail Output
The fail output signals when an error or fault condition occurs within the transducer. The fail
output is linked to the internal transducer error flag. Any error condition detected will switch the
output on, and will remain on until the error clears. This behaviour is different from the LED
which latches.
The fail signal is an open collector output. The output should be pulled up with an appropriate
value resistor to the required signal level, using an external supply voltage. The external supply
can be anything from 1V to 60V. The fail output transistor will be switched on, grounding the
output, when a fail signal is active, when inactive, the output will be pulled up to the external
supply voltage.
The fail output is available on both the analog and digital connectors. The following diagrams
show two possible setups with the internal circuit:
Example 1 – Analog Connector
Example 2 – Digital Connector
The best use of the fail output is as a safety shutdown signal.
In firmware prior to version 5, the fail output is shared with the limits module. If the limits module
is active the fail output is overridden.

Sensor Technology 2022
Page 18
SGR4384V (Rev 3)
Limit Output
The limit output is driven by the limits module. The limits module is a configurable set of
parameters, which switch the limit output on or off when certain conditions are met. These
conditions include triggering when torque or speed goes above or below a set level. It also
includes more advanced functionality, like auto reset or triggering after a delay
The limits module is configured using Transducer Control; please refer to the Transducer
Control manual for further details.
The limit signal is an open collector output, with an internal 5V pullup, no external voltage should
be applied to this output. The output polarity is controlled by the configuration parameters.
The diagram below shows a setup example with the internal circuit. The limit output is available
on pin 10 of the Analog D connector.
In firmware prior to version 5, the limits module does not have a dedicated output pin, instead
the limit output is routed to the fail output pin (pin 11 on both Analog and Digital D connectors).
When the limits module is active the fail out signal is overridden.

Sensor Technology 2022
Page 19
SGR4384V (Rev 3)
Zeroing the transducer
Zeroing the transducer has the effect of introducing an offset to the torque reading. The zero
can be used to remove any offset that may have been introduced from its mechanical
installation, or from idle torque present. It must be stressed that the zero offset is no substitute
for correct installation.
When using high zero offsets, care must be taken not to overstrain the transducer. A zero offset
will not extend the full scale rating of the transducer, e.g. if a transducer was zeroed at 50%
then a further 50% was applied, the transducer will have reached full scale, even though the
transducer would be reading 50%. A zero offset of 10% or greater will trigger a warning
condition and will be indicated by a warning LED sequence.
The transducer can be zeroed by using either a digital command or an electrical signal.
There are 3 zero modes that can be used:
Normal Zero: Sets the zero offset to the current torque reading.
Average Zero: Sets the zero offset to the average of 8 consecutive torque readings.
Fixed Zero: A fixed value can be input and saved. Fixed Zero is only available in
Transducer Control.
Unless the zero is saved, any zero offset applied will be lost after a power cycle.
Electrical Signal
Zeroing the transducer electrically can be achieved by grounding the Zero Input on pin 7 of the
Analog 15 Way ‘D’ Socket. The best way of zeroing a transducer is to use a push button. A
simple circuit diagram using a push button is shown below.
The zero action is only carried out once the input has been ungrounded. Grounding the zero
input momentarily (less than 2 seconds) will initiate a normal zero, grounding the input for longer
will initiate other modes. When the zero input is grounded for more than 2 seconds the LED will
start flashing to indicate that a new mode has been selected, subsequent mode changes are
shown by an increase in flash frequency. The LED will not flash if an error condition is present.
The table below shows the various modes and timings.
Ground Hold Time LED Flash Zero Mode / Action
0 - 2 Seconds None Normal Zero
4 - 6 Seconds 1 Hz Green Flash Average Zero
Greater than
6 Seconds
2 Hz Green Flash
Transducer will save the current zero
offset so that it is retained across
power cycles.

Sensor Technology 2022 Page 20 SGR4384V (Rev 3)
Digital Command
There are multiple digital commands to select the different zero modes, refer to the transducer
communication protocol manual.
Our Torqview and Transducer Control software programs implement these commands
providing a simple way of zeroing the transducer.
Resetting transducer to factory default
To reset the transducer to the factory default settings (i.e. the functions set by the factory on
purchase) follow the steps below:
1. Turn off transducer.
2. While holding in the zero button, power the transducer. The LED will stay solid green
until the zero button is released.
3. Allow the transducer to carry out its BIT procedure.
4. When the LED is solid green again, all user-adjusted parameters will have been reset
to the factory defaults.
This manual suits for next models
15
Table of contents
Other TorqSense Transducer manuals