NNoottee:: If PS2 does not close within the 45 seconds, the
IFC will wait 10 minutes and repeat steps 3 & 4. If
on the third attempt during the same heating call,
PS2 does not close within the 45 second proving
time, the unit will run in 1st stage until the
thermostat R-W2 contacts open.
5 When the temperature raises enough to satisfy the
thermostat setting, contacts R-W2 will open, the 2nd
stage gas valve will close, the indoor blower motor
will ramp down to 1st stage, and the unit will
continue to run until R-W1 contacts open
6 When the temperature raises enough to satisfy the
thermostat setting, contacts R-W1 will open
7 The gas valve relay will open, closing the gas valve
The inducer will continue to run for approximately 5
seconds to remove any combustion byproducts
from inside the furnace
8 The indoor blower continues to run to remove heat
from the heat exchangers This blower off time is
field adjustable through the IFC menu setup option
The seven-segment LED will read 1DL = Idle, no
thermostat demand
SSiinnggllee SSttaaggee CCoooolliinngg
1 R-Y1-G contacts on the thermostat close sending
24VAC to the Y1 and G low voltage terminals on the
IFC Technician should read 24VAC between Y1-B/C
and between G-B/C
NNoottee:: For S8X2 units, the factory supplied Y1-O
jumper must remain in place for proper
seven-segment LED readout, and furnace
operation. If removed, the seven-segment
LED will read “
HP1
”.
2 24VAC is sent to the OD unit via thermostat wiring
3 The indoor blower ramps to the cooling airflow
The seven-segment LED for example will
alternately read:
•CL1 = Cooling, Stage 1 (S8X2)
•CP1 = Cooling, Stage 1 (S8B1/S8X1)
•tP3 = Tap 3
4 When the temperature is lowered enough to satisfy
the thermostat setting, contacts R-Y-G will open
5 The OD unit shuts off and the indoor blower shuts
off, unless a blower “Cool Off Delay” has been
enabled in the IFC setup menu options The seven-
segment LED will read “IDL” = Idle, no thermostat
demand
TTwwoo SSttaaggee CCoooolliinngg
1 See sequence of operation for Single stage cooling
operation above (steps 1–3)
2 R-Y2 contact on the thermostat close sending
24VAC to Y2 low voltage terminal on the IFC
Technician should read 24VAC between Y2 and B/C
3 24VAC is sent to the OD unit via thermostat wiring
4 The indoor airflow ramps to 2nd stage airflow The
seven-segment LED for example will read:
•CL2 = Cooling, Stage 2 (S8X2)
•CP2 = Cooling, Stage 2 (S8X1)
•tP7 = Tap 7
5 When the temperature is lowered enough to satisfy
the thermostat setting, contacts R-Y1-Y2-G will
open
6 The OD unit shuts off and the indoor blower shuts
off, unless a blower “Cool Off Delay” has been
enabled in the IFC setup menu options The seven-
segment LED will read 1DL = Idle, no thermostat
demand
SSiinnggllee SSttaaggee HHeeaatt PPuummpp
1 R-Y1-G contacts on the thermostat close sending
24VAC to the Y1 and G low voltage terminals on the
IFC Technician should read 24VAC between Y1-B/C
and between G-B/C
NNoottee:: For S8X2 units, the factory supplied Y1-O
jumper must be removed for proper
seven-segment LED readout and furnace
operation during defrost. If left in place,
the seven-segment LED will read
CL1
2 24 VAC is sent to the OD unit via thermostat wiring
3 The indoor blower ramps to the cooling airflow
The seven-segment LED for example will
alternately read:
•HP1 = Cooling, Stage 1 (S8X2)
•CP1 = Cooling, Stage 1 (S8B1/S8X1)
•tP3 = Tap 3
4 When the temperature is lowered enough to satisfy
the thermostat setting, contacts R-Y-G will open
5 The OD unit shuts off and the indoor blower shuts
off, unless a “Cool Off Delay” has been enabled in
the IFC setup menu options The seven-segment
LED will read 1DL = Idle, no thermostat demand
TTwwoo SSttaaggee HHeeaatt PPuummpp
1 See sequence of operation for single stage cooling
operations above (steps 1–3)
2 R-Y2 contact on the thermostat close sending
24VAC to Y2 low voltage terminal on the IFC
Technician should read 24VAC between Y2 and B/C
3 24VAC is sent to the OD unit via thermostat wiring
4 The indoor airflow ramps to 2nd stage airflow The
seven-segment LED for example will read:
•HP2 = Cooling, Stage 2 (S8X2)
•CP2 = Cooling, Stage 2 (S8X1)
•tP7 = Tap 7
5 When the temperature is raised enough to satisfy
the thermostat setting, contacts R-Y1-Y2-G will
open
6 The OD unit shuts off and the indoor blower shuts
off, unless a “Blower Off Delay” has been enabled
in the IFC setup menu options The seven-segment
LED will read 1dL = Idle, no thermostat demand
SSeeqquueennccee ooff OOppeerraattiioonn SS88BB11//SS88XX11//SS88XX22