Transmitter Solutions Reign XRE-100 User manual

WHAT’S INCLUDED
The REIGN XRE-100 Relay Extender is a revolutionary product that
will make any dry contact wireless with no programming or
configuration whatsoever - it literally is a plug and play device.
HOW IT WORKS...
Congratulations on your purchase of the Transmitter Solutions XRE-100 Relay Extender System. It has been
designed with state-of-the-art radio technology to extend relay closures, switches, indicators, sensors, and any
other simple ON/OFF status inputs and outputs up to 40 miles line-of-sight.
If you ordered your XRE-100s together, they are factory paired. All that is required to get up and running is 12-24
Volts AC/DC power and the DRY input closures you want to extend.
If you would like to survey the range capability before install, simply provide power to both units and press the
PROG/TEST button alternately on each unit. Successful transmission and reception will be indicated on the
transmit and receive LEDs on each unit as described below.
v.8.29.18
XRE–100
RELAY EXTENDER
There are two pieces that complete the XRE-100.
The Reign XRE-100 - Relay Extender kit includes 2- XRE-100 units. These units are interchangeable and can be
paired in the field.
Transmitter Solutions refers to the XRE-100 installed at the peripheral device as the Node and the XRE-100
installed at the primary unit the Hub. This is only important during technical support and the wiring diagram.
REIGN wireless
technology

2

SPECIFICATIONS
CONTENTS:
WIRING THE BOARD
Power Input: 12-24 Volt AC/DC
Relays: 10A 250 VAC/ 28VDC
12V: 50mA (idle)
1A (transmit)
24V: 25mA (idle)
500ma (transmit)
Range: 1/2 mile (Through obstructions)
Relays: 10A 250 VAC/ 28VDC
Minimum / Maximum Temperature Range:
-40°F to 185°F (-40°C to 85°C)
Security Encryption: AES
1. POWER DETAILS........................................................................................4
2. LED INDICATORS......................................................................................5
3. RELAY DIAGRAM AND WIRING......................................................................6
4. ALERT RELAYS..........................................................................................7
5. DIP SWITCHES..........................................................................................8
6. BATTERY BACKUP......................................................................................9
7. PAIRING IN THE FIELD...............................................................................9
TROUBLESHOOTING.................................................................................10
POWER INPUT: 12 to 24 VOLTS AC/DC. - 1 AMP Minimum
Always follow polarity when DC Power is used.
BATTERY INPUT: for 12 Volt Sealed Lead Acid (SLA) battery only.
Solid GREEN LED indicates battery charging. Momentarily flashing GREEN LED indicates battery is charged
and a trickle/conditioning charge is occurring.
3

1. POWER DETAILS
Each side of The XRE-100 (Hub and Node) need 1 amp of current draw to transmit at full power.
IMPORTANT - XRE REQUIRES AT LEAST 1AMP POWER SUPPLY
POWER INPUT:
Power Input: 12 to 24 VOLTS AC/DC. Always follow polarity when DC Power is used. 1 AMP Minimum
BATTERY INPUT:
Battery Input: for 12 Volt Sealed Lead Acid (SLA) battery only.
Solid Green LED = Battery charging
Momentary Flashing LED = Battery is fully charged and a trickle/conditioning charge is occurring
1
2
21
4

2. LED INDICATORS
STATUS LEDs:
RECEIVE - flashes GREEN momentarily when a valid radio transmission is received.
TRANSMIT - flashes RED momentarily when the unit transmits a packet as a result of an Relay Input change
event or handshake.
STATUS/ PROG - flashes yellow patterns indicating status of the unit: pairing, error, etc.
RUN - flashes ORANGE 1 second ON and 1 second OFF indicating the microprocessor is running.
POWER LED - Glows solid orange when power is present. 5 volt relay supply, 3.3 volt logic supply, and VPA
3.6 volt power amplifier supply.
1
3
1
2
3
4
5
4
2
5
5

3. RELAY DIAGRAM AND WIRING
–
RELAY INPUTS
Relay Inputs - The Reign XRE-100 comes with 2 relay inputs. Connect DRY closure from devices relay to be
extended. A closure on RLY1 input will result in a closure on RLY1 (NC/COM/NO) of the paired XRE-100. A
closure on RLY2/COM input will result in a closure on RLY2 (NC/COM/NO output) of the paired XRE-100.
RELAY OUTPUTS
Relay Outputs - The Reign XRE-100 comes with 2-relay outputs. Each output follows RELAY INPUTS from
remote paired XRE-100. When RLY1 or RLY2 INPUTS are closed RLY1 and RLY2 OUTPUTS are energized and
connect NC/COM/NO respectively. This relay state is also indicated by the GREEN ACTIVE LED above each
relay.
1
2
21
6

4. ALERT RELAYS
ALERT INPUT (when DIP switch 2 is on)
ALERT RELAY OUTPUT
Both RELAY 1 and RELAY 2 INPUTs are supervised when DIPSWITCH 2 in ON.
Supervised inputs detect fault or tampering of inputs and send an ALERT RELAY
activation to the opposite unit (Typically from the Node unit to the Base unit).
Supervised inputs will detect an input shorted to ground (or each other) or an open
input (loose or cut wire). Connect the supplied 1K ohm and 2K ohm resistors across
the device to be monitored as shown. IMPORTANT: resistors must be connected at
the device to be monitored NOT AT THE XRE-100 RELAY INPUT.
When in Supervise Mode, unused inputs must be terminated with the supplied 3K
ohm resistor. Simply insert the resistor into the Rx and COM pins on the desired
connector and tighten screw blocks.
If Supervised Inputs are not desired, simply leave DIPSWITCH 2 OFF and wire your
contact directly across the Rx and COM pins.
NOTE: Communication Loss - If the XRE-100 units stop communicating the Alert
Relay Output(Black relay) will trigger. Alerting on loss of communication between
devices.
1
2
2K OHM
3K OHM
3K OHM
1K OHM
BROWN
BLACK
RED
RED
BLACK
RED
ORANGE
BLACK
RED
GOLD
GOLD
GOLD
SUPERVISOR RESISTOR
COLOR CODES
Monitored
Contact
Unused Input
XRE-100
Customer
Wires
1K
2K
Detects: OPEN (cutwires) or,
SHORT (wire to each other or ground)
1. Supervise resistors (supplied) must be at con-
tact.
2. Associated DIPSWITCH SW2 must be ON
3. Connect contact directly, without resistors for
unsupervised inputs. SW5 and SW6 = OFF.
3K
7

5. DIP SWITCHES
MODE SWITCHES
SWITCH 1 – PROG (PAIR) – Pairing mode when ON and Normal operating mode when OFF
SWITCH 2 – SUPERVISED INPUTS – Supervised inputs active when ON
SWITCH 3 – COMMS LOSS BEACON – Pulses Alert Relay if ON, otherwise Relay is steady on
SWITCH 4 – Not used
SWITCH 5 – Not used
SWITCH 6 – Not used
RELAY OUTPUT SWITCH:
Relay Output Switch - not used in XRE-100 to XRE-100 Relay Extension operation.
PROGRAM/TEST BUTTON:
Program/Test Button - used with MODE SWITCH 1 to field pair units as described above. Functions as a TEST
TRANSMIT button during normal operation. When pressed, the XRE-100 will send a radio test packet and the RED
TRANSMIT LED will illuminate. If the paired XRE-100 is online, it will acknowledge with a radio test packet –
indicated by a momentary GREEN RECEIVE LED.
RELAY DELAY POTENTIOMETER:
Relay Delay Potentiometer: not used in XRE-100 to XRE-100 Relay Extension operation.
13
4
1
2
3
4
8

6. BATTERY BACKUP
12 Volt Sealed Lead Acid (SLA) battery only. Solid GREEN LED indicates battery charging. Momentarily
flashing GREEN LED indicates battery is charged and a trickle/conditioning charge is occurring.
PAIRING
Flip Dipswitch 1 to ON on both units.
Press the PROG/TEST button on either unit
NOTE: Observe the STATUS/PROG LED flashing.
Flip Dipswitch 1 to OFF on both units
Press PROG/TEST and observe TRANSMIT and RECEIVE LEDs operating normally.
Pairing procedure overwrites any previous units. For example, if replacing a unit simply follow the above
procedure with the existing and replacement unit.
7. PAIRING UNIT IN THE FIELD
1
2
3
4
1
2
4
3
UNIT 1
UNIT 2
1
3
9

XRE-100 units are not communicating:
1 - Check the Run LED. Normal operation will be orange LED flashing once a second.
2 - Press the red program button on the XRE-100. When pressed, the XRE-100 will send a radio test packet and the
RED TRANSMIT LED will illuminate. If the paired XRE-100 is online, it will acknowledge with a radio test packet –
indicated by a momentary on the green receive LED.
If you do not see the transmit and receive LED lights activate:
1 - Power cycle both the XRE units.
2 - Move the XRE-100 units to a higher location and avoid mounting on/in metal objects
If you are not getting the desired range between XRE-100 units:
1 - Ensure that the both devices are powered by their own dedicated power supply
2 - Ensure that 1 amp of power draw is available to each device during transmission
3 - Move the XRE-100 units to a higher location - and avoiding mounting in/on metal objects
TROUBLESHOOTING
XRE LED GUIDE
10

The warranty period of this product is 24 months, beginning from the manufacturing date. During this period, if the
product does not operate correctly, due to a defective component, the product will be repaired or replaced at the sole
discretion of Transmitter Solutions. This warranty does not extend to the product casing which can be damaged by
conditions outside of the control of Transmitter Solutions.
EXCEPT AS SET FORTH ABOVE, TRANSMITTER SOLUTIONS MAKES NO WARRANTIES REGARDING THE GOODS, EXPRESS OR IMPLIED,
INCLUDING WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. BUYER MAKES NO RELIANCE ON
ANY REPRESENTATION OF TRANSMITTER SOLUTIONS, EXPRESS OR IMPLIED, WITH REGARD TO THE GOODS AND ACCEPTS THEM
“AS-IS/WHERE-IS”. TRANSMITTER SOLUTIONS SELLS THE GOODS TO BUYER ON CONDITION THAT TRANSMITTER SOLUTIONS WILL HAVE NO
LIABILITY OF ANY KIND AS A RESULT OF THE SALE. BUYER AGREES THAT TRANSMITTER SOLUTIONS SHALL HAVE NO LIABILITY FOR
DAMAGES OF ANY KIND, WHETHER DIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING INJURIES TO PERSONS OR PROPER-
TY, TO BUYER, ITS EMPLOYEES OR AGENTS, AS A RESULT OF THE SALE. BUYER ALSO AGREES TO HOLD TRANSMITTER SOLUTIONS
HARMLESS FROM ANY CLAIMS BUYER, OR ANY THIRD PARTY, MAY HAVE AS A RESULT OF BUYER’S USE OR DISPOSAL OF THE GOODS.
BUYER HAS READ THIS DISCLAIMER AND AGREES WITH ITS TERMS IN CONSIDERATION OF RECEIVING THE GOODS.
WARRANTY
11

PH 866.975.0101 • FX 866.975.0404
www.transmittersolutions.com
Table of contents